Browse all
Browse all

Canalis KDP Disribution Length 20A 24M

Canalis KDP Disribution Length 20A 24M

Item Number: KDP20ED224150

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range Canalis
Range of product Canalis
Product or component type busbar trunking
Product compatibility KDP
Device application
  • lighting
  • power socket distribution
Warranty 18 months

Physical

[ue] rated operational voltage 230...400 V
[ie] rated operational current 20 A at 35 °C
Type of packing spool
Standards
  • EN/IEC 61439-6
  • EN/IEC 60439-2
Length 24 m
Net weight 4.8 kg
Ip degree of protection IP55 conforming to IEC 60529
Ik degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation
  • 35...40 °C (93 % of In)
  • 40...45 °C (85 % of In)
  • 45...50 °C (76 % of In)
  • 50...55 °C (66 % of In)
  • 0...35 °C (100 % of In)
Environmental disclosure ENVPEP061103EN
Eu rohs directive Compliant

Others

Legacy weee scope In
Average percentage of recycled plastic content 0 %
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name KDP
Busbar description flexible bar
[uimp] rated impulse withstand voltage 4 kV
[ui] rated insulation voltage 690 V
[icw] rated short-time withstand current 0.34 kA
[ipk] rated peak withstand current 3.6 kA
Network frequency 50/60 Hz
Maximum radiated magnetic field 2 pT
Thdi
  • 0...15 % 20 A
  • 15...33 % 16 A
  • 33...100 % 14 A
Maximum voltage drop
  • <0.72 V with power factor = 1 at 50 Hz with 1A for 100 m long
  • <0.65 V with power factor = 0.9 at 50 Hz with 1A for 100 m long
  • <0.58 V with power factor = 0.8 at 50 Hz with 1A for 100 m long
  • <0.5 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
Linear resistance
  • 6.8 mΩ/m R20 20 °C phase conductor
  • 0.85 mΩ/m X0 20 °C symmetrical components method Ph/PE
  • 27.22 mΩ/m Z0 20 °C symmetrical components method Ph/PE
  • 13.61 mΩ/m Rb0 20 °C impedance method Ph/Ph
  • 13.61 mΩ/m Rb0 20 °C impedance method Ph/N
  • 13.61 mΩ/m Rb0 20 °C impedance method Ph/PE
  • 16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph
  • 16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N
  • 16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE
  • 0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph
  • 0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N
  • 8.3 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor
  • 0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE
  • 0.02 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor
  • 8.3 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor
  • 7.25 mΩ/m 20 °C protective conductor
  • 27.21 mΩ/m R0 20 °C symmetrical components method Ph/N
  • 0.85 mΩ/m X0 20 °C symmetrical components method Ph/N
  • 27.22 mΩ/m Z0 20 °C symmetrical components method Ph/N
  • 27.21 mΩ/m R0 20 °C symmetrical components method Ph/PE
Busbar trunking polarity L1 + N + PE
Tap-off unit interval 1500 mm
Sustainable packaging No
Pvc free Yes
Halogen-free status Halogen free product
Silicone-free  Yes
F-gas free N/A
Take-back No
Removable battery N/A
Average percentage of recycled metal content 0 %
Halogen-free status Halogen free product
Pvc free Yes
Silicone-free Yes
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18