Item Number: VCF5GEN

Datasheet

Product Dimensions

Width icon

Width241 mm

Height icon

Height291 mm

Depth icon

Depth191 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Product or component type enclosed emergency stop switch disconnector
Warranty 18 months

Physical

Control type rotary handle
Marking 0 - 1
[ue] rated operational voltage 690 V AC
[ie] rated operational current 68.5 A (AC-23A) at 400 V
Mechanical durability 30000 cycles
Electrical durability
  • 30000 cycles AC-21
  • 30000 cycles DC-1...5
Environmental characteristic standard environment
Connections - terminals
  • screw clamp terminals70-70 mm² - flexible - with cable end
  • screw clamp terminals95-95 mm² - solid
Height 291 mm
Width 241 mm
Depth 191 mm
Net weight 2.19 kg
Standards
  • IEC 60947-4-1
  • IEC 60204
Ip degree of protection IP65 conforming to IEC 60529
Ambient air temperature for operation -20...50 °C
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2211019EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Package 1 bare product quantity 1
Legacy weee scope In
At least in Europe
Average percentage of recycled plastic content 0 %
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Product name TeSys VARIO
Device short name VCF
Performance level high performance
Poles description 3P
Type of operator long handle
Handle colour red
Handle front plate colour yellow
Rotary handle padlocking 1 to 3 padlocks 4-8 mm
[uimp] rated impulse withstand voltage 8 kV
[ithe] conventional enclosed thermal current 100 A
Rated operational power in w
  • 37 kW at 400 V (AC-23)
  • 30 kW at 400 V (AC-3)
Intermittent duty class 30
Making capacity
  • 1250 A at 400 V AC-21A
  • 1250 A at 400 V AC-22A
  • 1250 A at 400 V AC-23A
[icm] rated short-circuit making capacity 2.8 kA at 400 V at Ipeak
[icw] rated short-time withstand current 1500 A at 400 V duration: 1 s
Rated conditional short-circuit current
  • 10 kA at 400 V - associated fuse 125 A aM
  • 10 kA at 400 V - associated fuse 125 A gG
Breaking capacity
  • 1000 A at 400 V (AC-21A)
  • 1000 A at 400 V (AC-22A)
  • 1000 A at 400 V (AC-23A)
Suitability for isolation yes
Tightening torque 22.6...22.6 N.m - on screw clamp terminals
Fire resistance 960 °C conforming to IEC 60595-2-1
Base dimension 90 x 90 mm
Compatibility code enclosed switch disconnector
Protective treatment TC
Mechanical robustness
  • vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6
  • shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 30.000 cm
Package 1 width 25.000 cm
Package 1 length 20.000 cm
Package 1 weight 2.897 kg
Unit type of package 2 S04
Number of units in package 2 2
Package 2 height 30.000 cm
Package 2 width 40.000 cm
Package 2 length 60.000 cm
Package 2 weight 6.522 kg
Unit type of package 3 P06
Number of units in package 3 8
Package 3 height 75.000 cm
Package 3 width 60.000 cm
Package 3 length 80.000 cm
Package 3 weight 38.372 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 36 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 15.237546554734571
Carbon footprint of the manufacturing phase [a1 to a3] 15 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.5645290261022665
Carbon footprint of the distribution phase [a4] 0.6 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.4581174955159203
Carbon footprint of the installation phase [a5] 0.5 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 13.432378470046519
Carbon footprint of the use phase [b2, b3, b4, b6] 13 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 6.33881332710092
Carbon footprint of the end-of-life phase [c1 to c4] 6 kg CO2 eq.
Energy efficiency optimized False
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 36.0313848735002
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number 9ea58720-3cf9-4883-9af8-9d64d3981af2
China rohs label 1
End of life manual availability N/A
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Declaration of Conformity

  • Certificates (MSDS)

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.