Browse all
Browse all

TeSys D Reversing Contactor TeSys Deca, 3P(3 NO), AC-3, 0 to 440V, 18A, 24 to 60VAC/DC coil

Home ProductsIndustrialTeSysReversing Contactor

TeSys D Reversing Contactor TeSys Deca, 3P(3 NO), AC-3, 0 to 440V, 18A, 24 to 60VAC/DC coil

Item Number: LC2D18BNE

Datasheet

Product Dimensions

Width icon

Width90 mm

Height icon

Height77 mm

Depth icon

Depth86 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product TeSys Deca Advanced
Product or component type reversing contactor
Warranty 18 months

Physical

Device presentation preassembled with reversing power busbar
[ue] rated operational voltage power circuit: <= 690 V AC 25...400 Hz
[ie] rated operational current
  • 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Mounting support
  • plate
  • rail
Connections - terminals
  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable end
  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable end
  • power circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable end
  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end
  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid
  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid
Insulation resistance > 10 MOhm for signalling circuit
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10
  • conforming to IEC 60947-1 Annex Q category D
Ambient air temperature for operation
  • -40...60 °C
  • 60...70 °C with derating
Ambient air temperature for storage -60...80 °C
Height 77 mm
Width 90 mm
Depth 86 mm
Net weight 0.803 kg
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1609001EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Legacy weee scope In
Package 1 bare product quantity 1
Average percentage of recycled plastic content 0 %
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Product name TeSys Deca Advanced
Device short name LC2D
Contactor application
  • resistive load
  • motor control
Utilisation category
  • AC-1
  • AC-3
Poles description 3P
Pole contact composition 3 NO
Motor power kw
  • 4 kW at 220...230 V AC 50 Hz
  • 7.5 kW at 380...400 V AC 50 Hz
  • 9 kW at 415 V AC 50 Hz
  • 9 kW at 440 V AC 50 Hz
  • 10 kW at 500 V AC 50 Hz
  • 10 kW at 660...690 V AC 50 Hz
Motor power hp
  • 1 hp at 115 V AC 60 Hz for 1 phase motors
  • 3 hp at 230/240 V AC 60 Hz for 1 phase motors
  • 5 hp at 200/208 V AC 60 Hz for 3 phases motors
  • 5 hp at 230/240 V AC 60 Hz for 3 phases motors
  • 10 hp at 460/480 V AC 60 Hz for 3 phases motors
  • 15 hp at 575/600 V AC 60 Hz for 3 phases motors
Control circuit type
  • AC at 50/60 Hz AC/DC electronic
  • DC AC/DC electronic
[uc] control circuit voltage
  • 24...60 V AC 50/60 Hz
  • 24...60 V DC
Auxiliary contact composition 1 NO + 1 NC
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Overvoltage category III
[ith] conventional free air thermal current
  • 32 A (at 60 °C) for power circuit
  • 10 A (at 60 °C) for signalling circuit
Irms rated making capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 300 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 300 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 40 A 40 °C - 10 min for power circuit
  • 84 A 40 °C - 1 min for power circuit
  • 145 A 40 °C - 10 s for power circuit
  • 240 A 40 °C - 1 s for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 50 A gG at <= 690 V coordination type 1 for power circuit
  • 35 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit
[ui] rated insulation voltage
  • power circuit: 690 V conforming to IEC 60947-4-1
  • signalling circuit: 690 V conforming to IEC 60947-1
Power dissipation per pole
  • 2.5 W AC-1
  • 0.8 W AC-3
Protective cover with
Interlocking type mechanical
Tightening torque
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Maximum operating rate 3600 cyc/h 60 °C
Coil technology built-in bidirectional peak limiting
Control circuit voltage limits
  • <= 0.1 Uc (-40-70 °C):drop-out AC/DC
  • 0.85...1.1 Uc (-40-60 °C):operational AC
  • 0.8...1.1 Uc (-40-60 °C):operational DC
  • 1...1.1 Uc (60-70 °C):operational AC/DC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Compatibility code LC2D
[uc] control circuit voltage 24...60 V
Rated thermal current (ith) 32 A
Maximum motor phase current 18 A
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open: 2 Gn, 5...300 Hz
  • vibrations contactor closed: 4 Gn, 5...300 Hz
  • shocks contactor open: 10 Gn for 11 ms
  • shocks contactor closed: 15 Gn for 11 ms
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 11.5 cm
Package 1 width 9.4 cm
Package 1 length 13.8 cm
Package 1 weight 884.0 g
Unit type of package 2 S02
Number of units in package 2 6
Package 2 height 15.0 cm
Package 2 width 30.0 cm
Package 2 length 40.0 cm
Package 2 weight 5.689 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 22 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 6.629786625445716
Carbon footprint of the manufacturing phase [a1 to a3] 7 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.23937061554729366
Carbon footprint of the distribution phase [a4] 0.2 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.08935568519684885
Carbon footprint of the installation phase [a5] 0.1 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 14.046821052631584
Carbon footprint of the use phase [b2, b3, b4, b6] 14 kg CO2 eq.
Sustainable packaging No
Carbon footprint of the end-of-life phase [c1 to c4] 1.3731688305777097
Carbon footprint of the end-of-life phase [c1 to c4] 1 kg CO2 eq.
Halogen-free status Halogen free plastic parts & cables product
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 22.378502809399155
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number 7d699774-c34b-4bf4-9ecb-388a149eefdd
Halogen-free status Halogen free plastic parts & cables product
End of life manual availability ENVEOLI1609001EN
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.