Browse all
Browse all

TeSys GV4 Motor circuit breaker TeSys GV4, 3P, 2A, Icu 50kA, magnetic, lugs terminals

Home ProductsIndustrialTeSysMotor circuit breaker

TeSys GV4 Motor circuit breaker TeSys GV4, 3P, 2A, Icu 50kA, magnetic, lugs terminals

Item Number: GV4LE02N6

Datasheet

Product Dimensions

Width icon

Width81 mm

Height icon

Height155 mm

Depth icon

Depth116 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys Deca
Range of product TeSys GV4
Product or component type motor circuit breaker
Device application motor protection
Warranty 18 months

Physical

Control type toggle
[in] rated current 2 A
[ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 40000 cycles
Electrical durability
  • 5000 cycles for AC-3 at 415 V closing
  • 5000 cycles for AC-3 at 415 V opening
Connections - terminals lugs-ring terminals
Height 155 mm
Width 81 mm
Depth 116 mm
Net weight 1.5 kg
Standards
  • EN/IEC 60947-4-1
  • EN/IEC 60947-2
Product certifications
  • IEC
  • CCC
  • EAC
  • EU-RO MR
Climatic withstand conforming to IACS E10
Ik degree of protection IK07 conforming to IEC 62262
Ip degree of protection IP40 conforming to IEC 60529
Ambient air temperature for storage -50...85 °C
Ambient air temperature for operation -25...70 °C
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1704004EN
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Legacy weee scope In
Package 1 bare product quantity 1
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty duration(in months) bmecat 18
At least in Europe
Device short name GV4L
Product name TeSys GV4
Trip unit technology
  • magnetic
  • electronic
Poles description 3P
Utilisation category
  • category A conforming to IEC 60947-2
  • AC-3 conforming to IEC 60947-4-1
Operating position any position
Motor power kw
  • 0.25...0.25 kW at 400...415 V AC 50/60 Hz
  • 0.37...0.37 kW at 400...415 V AC 50/60 Hz
  • 0.55...0.55 kW at 400...415 V AC 50/60 Hz
  • 0.75...0.75 kW at 400...415 V AC 50/60 Hz
  • 0.37...0.37 kW at 500 V AC 50/60 Hz
  • 0.55...0.55 kW at 500 V AC 50/60 Hz
  • 0.75...0.75 kW at 500 V AC 50/60 Hz
  • 1.1.1 kW at 500 V AC 50/60 Hz
  • 0.55...0.55 kW at 660...690 V AC 50/60 Hz
  • 0.75...0.75 kW at 660...690 V AC 50/60 Hz
  • 1.1.1 kW at 660...690 V AC 50/60 Hz
  • 1.5...1.5 kW at 660...690 V AC 50/60 Hz
Breaking capacity
  • 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
  • 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
  • 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Magnetic tripping current 12...28 A
[ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional free air thermal current 115 A conforming to IEC 60947-4-1
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
Power dissipation per pole 6.1 W
Maximum operating rate 25 cyc/h
Rated duty continuous conforming to IEC 60947-4-1
Connection pitch
  • 27 mm without spreaders
  • 35 mm with spreaders
Direct connector without
Tightening torque
  • 9 N.m for cable 16-95 mm²
  • 5 N.m for cable 1.5-10 mm²
Mechanical robustness
  • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
  • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
  • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
Suitability for isolation yes conforming to IEC 60947-1
Pollution degree 3
Fire resistance 960 °C conforming to IEC 60695-2-11
Operating altitude 5000 m
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 16.5 cm
Package 1 width 11 cm
Package 1 length 22 cm
Package 1 weight 1.488 kg
Sustainable packaging No
Pvc free Yes
Halogen-free status Halogen free plastic parts product
Packaging made with recycled cardboard Yes
Packaging without single use plastic No
Scip number 1b259a2c-3a3c-401a-acdd-f0837efd4018
Halogen-free status Halogen free plastic parts product
Pvc free Yes
End of life manual availability ENVEOLI1704004EN
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Environmental Disclosure

  • End of Life Manual

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.