Design

Range of product TeSys K control relay
Range TeSys
Product or component type control relay
Warranty 18 months

Physical

[ue] rated operational voltage <= 690 V <= 400 Hz
Mounting support
  • plate
  • rail
Connections - terminals
  • screw clamp terminals 1 cable(s) 1.5-4 mm²solid
  • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
  • screw clamp terminals 1 cable(s) 0.75-4 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end
  • screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible without cable end
Mechanical durability 10 Mcycles
Insulation resistance > 10 MOhm
Height 58 mm
Width 45 mm
Depth 57 mm
Net weight 0.18 kg
Standards
  • EN/IEC 60947-5-1
  • GB/T 14048.5
  • UL 60947-5-1
  • CSA C22.2 No 60947-5-1
  • JIS C8201-5-1
Product certifications
  • CB Scheme
  • CCC
  • UL
  • CSA
  • EAC
  • CE
  • UKCA
Ip degree of protection IP2X
Ambient air temperature for operation -25...50 °C
Ambient air temperature for storage -50...80 °C
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1503003EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation X
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Average percentage of recycled plastic content 0 %
Package 1 bare product quantity 1
Legacy weee scope In
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Product name TeSys CAK
Device short name CA2K
Contactor application control circuit
Utilisation category
  • AC-15
  • DC-13
Pole contact composition 3 NO + 1 NC
Control circuit type AC at 50/60 Hz
[uc] control circuit voltage 48 V AC 50/60 Hz
[ith] conventional free air thermal current 10 A (at 50 °C)
Irms rated making capacity 110 A conforming to IEC 60947
Associated fuse rating
  • 10 A gG conforming to IEC 60947
  • 10 A gG conforming to VDE 0660
[ui] rated insulation voltage
  • 690 V conforming to IEC 60947
  • 750 V conforming to VDE 0110 group C
  • 690 V conforming to BS 5424
  • 600 V conforming to CSA C22.2 No 14
Tightening torque
  • 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
  • 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Control circuit voltage limits
  • drop-out: 0.2...0.75 Uc (at <50 °C)
  • operational: 0.8...1.15 Uc (at <50 °C)
Operating time
  • 10...20 ms coil de-energisation and NO opening
  • 10...20 ms coil energisation and NO closing
  • 15...25 ms coil de-energisation and NC closing
  • 5...15 ms coil energisation and NC opening
Maximum operating rate 10000 cyc/h
Immunity to microbreaks 2 ms
Inrush power in va 30 VA (at 20 °C)
Hold-in power consumption in va 4.5...4.5 VA (at 20 °C)
Heat dissipation 1.3...1.3 W
Minimum switching voltage 17 V
Minimum switching current 5 mA
Non overlap distance 0.5 mm
Compatibility code CA2K
Protective treatment TC conforming to IEC 60068
Operating altitude 2000 m without derating
Flame retardance
  • V1 conforming to UL 94
  • requirement 2 conforming to NF F 16-101
  • requirement 2 conforming to NF F 16-102
Mechanical robustness
  • vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
  • vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
  • shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
  • shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 4.8 cm
Package 1 width 6.2 cm
Package 1 length 6.6 cm
Package 1 weight 180.0 g
Unit type of package 2 S02
Number of units in package 2 50
Package 2 height 15.0 cm
Package 2 width 30.0 cm
Package 2 length 40.0 cm
Package 2 weight 9.43 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 72 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 0.9242849543117562
Carbon footprint of the manufacturing phase [a1 to a3] 0.9 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.35672643587278696
Carbon footprint of the distribution phase [a4] 0.4 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.024523461013256826
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 70.81551905511422
Carbon footprint of the use phase [b2, b3, b4, b6] 71 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.25905106779138043
Carbon footprint of the end-of-life phase [c1 to c4] 0.3 kg CO2 eq.
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 72.3801049741034
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
End of life manual availability ENVEOLI1503003
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.