Browse all
Browse all

TeSys K Control Relay 1 NO + 1 NC, <= 690 V, 24V DC standard coil

TeSys K Control Relay 1 NO + 1 NC, <= 690 V, 24V DC standard coil

Item Number: CA3SK11BD

Datasheet

Product Dimensions

Width icon

Width27 mm

Height icon

Height56 mm

Depth icon

Depth55.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product TeSys SK control relay
Range TeSys
Product or component type control relay
Warranty 18 months

Physical

[ue] rated operational voltage <= 690 V <= 400 Hz
Mounting support
  • rail
  • plate
Connections - terminals
  • screw clamp terminals 1 cable(s) 1.5-6 mm²solid
  • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
  • screw clamp terminals 1 cable(s) 0.5-6 mm²flexible without cable end
  • screw clamp terminals 1 cable(s) 0.35-6 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 0.35-1.5 mm²flexible with cable end
  • screw clamp terminals 2 cable(s) 0.35-2.5 mm²flexible without cable end
Mechanical durability 10 Mcycles
Height 56 mm
Width 27 mm
Depth 55.5 mm
Net weight 0.132 kg
Standards
  • EN/IEC 60947-5-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-5-1
Product certifications
  • CB Scheme
  • cULus
  • EAC
  • CE
  • UKCA
Ip degree of protection IP2X
Ambient air temperature for operation -20...50 °C
Ambient air temperature for storage -50...70 °C
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1503003EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Legacy weee scope In
At least in Europe
Average percentage of recycled plastic content 0 %
Package 1 bare product quantity 1
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Product name TeSys CASK
Device short name CA3SK
Contactor application control circuit
Utilisation category
  • DC-13
  • AC-15
Pole contact composition 1 NO + 1 NC
Control circuit type DC standard
[uc] control circuit voltage 24 V DC
[ith] conventional free air thermal current 10 A (at 55 °C)
Associated fuse rating
  • 10 A gL conforming to VDE 0660
  • 10 A gL conforming to IEC 60947
[ui] rated insulation voltage
  • 690 V conforming to IEC 60947
  • 690 V conforming to VDE 0110 group C
  • 690 V conforming to BS 5424
  • 690 V conforming to UL 508
  • 690 V conforming to CSA C22.2 No 14
Tightening torque 0.8 N.m - on screw clamp terminals pozidriv No 1 screw head
Control circuit voltage limits
  • operational: 0.85...1.1 Uc (at <50 °C)
  • drop-out: 0.1...0.75 Uc (at <50 °C)
Operating time
  • 4...6 ms coil de-energisation and NO opening
  • 8...12 ms coil energisation and NO closing
  • 6...8 ms coil de-energisation and NC closing
  • 10...18 ms coil energisation and NC opening
Maximum operating rate 1200 cyc/h
Inrush power in w 2.2.2 W (at 20 °C)
Hold-in power consumption in w 2.2.2 W at 20 °C
Heat dissipation 2.2.2 W
Compatibility code CA3SK
Protective treatment TC conforming to IEC 60068
Operating altitude 2000 m without derating
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 3.5 cm
Package 1 width 6.0 cm
Package 1 length 6.5 cm
Package 1 weight 124.0 g
Unit type of package 2 S01
Number of units in package 2 40
Package 2 height 15.0 cm
Package 2 width 15.0 cm
Package 2 length 40.0 cm
Package 2 weight 5.182 kg
Total lifecycle carbon footprint 58 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 0.6367296351925431
Carbon footprint of the manufacturing phase [a1 to a3] 0.6 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.24574487804569767
Carbon footprint of the distribution phase [a4] 0.2 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.01689393980913248
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 56.65241524409139
Carbon footprint of the use phase [b2, b3, b4, b6] 57 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.1784574022562843
Carbon footprint of the end-of-life phase [c1 to c4] 0.2 kg CO2 eq.
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 57.730241099395045
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number bf876e8d-5be9-45ba-9d97-ac1c3aec5384
China rohs label 3
End of life manual availability ENVEOLI1503003
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.