Browse all
Browse all

TeSys D Contactor TeSys Deca, 4P(4 NO), AC-1, 0 to 440V, 80A, 24V DC standard coil

TeSys D Contactor TeSys Deca, 4P(4 NO), AC-1, 0 to 440V, 80A, 24V DC standard coil

Item Number: LC1DT80ABD

Datasheet

Product Dimensions

Width icon

Width70 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range
  • TeSys
  • TeSys Deca
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Mechanical durability 10 Mcycles
Electrical durability 0.5 Mcycles 80 A AC-1 at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end
  • power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end
  • power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end
  • power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end
  • power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid without cable end
  • power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Connections - terminals EverLink BTR screw connectors
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60947-4-1
  • IEC 60335-1
Product certifications
  • LROS (Lloyds register of shipping)
  • CSA
  • UL
  • BV
  • GOST
  • DNV
  • GL
  • CCC
  • RINA
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 122 mm
Width 70 mm
Depth 120 mm
Net weight 1.225 kg
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1503009EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Package 1 bare product quantity 1
Average percentage of recycled plastic content 0 %
At least in Europe
Legacy weee scope In
Package 2 bare product quantity 7
Package 3 bare product quantity 56
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application resistive load
Utilisation category AC-1
Poles description 4P
[uc] control circuit voltage 24 V DC
Compatibility code LC1D
Pole contact composition 4 NO
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 80 A (at 60 °C) for power circuit
Irms rated making capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 640 A 40 °C - 10 s for power circuit
  • 900 A 40 °C - 1 s for power circuit
  • 110 A 40 °C - 10 min for power circuit
  • 260 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 125 A gG at <= 690 V coordination type 1 for power circuit
  • 125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.6 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole 10.2 W AC-1
[ui] rated insulation voltage
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
  • power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type DC standard
Coil technology built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
  • 0.1...0.3 Uc (-40-70 °C):drop-out DC
  • 0.75...1.25 Uc (-40-60 °C):operational DC
  • 1...1.25 Uc (60-70 °C):operational DC
Inrush power in w 19 W (at 20 °C)
Hold-in power consumption in w 7.4...7.4 W at 20 °C
Operating time
  • 50 ±15 % ms closing
  • 16...24 ms opening
Time constant 34 ms
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
  • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Contact compatibility M7
Rated thermal current (ith) 80 A
[uc] control circuit voltage 24 V
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor closed (15 Gn for 11 ms)
  • shocks contactor open (10 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 7.700 cm
Package 1 width 13.800 cm
Package 1 length 15.300 cm
Package 1 weight 1.148 kg
Unit type of package 2 S02
Number of units in package 2 7
Package 2 height 15.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 8.348 kg
Unit type of package 3 P06
Number of units in package 3 56
Package 3 height 45.000 cm
Package 3 width 60.000 cm
Package 3 length 80.000 cm
Package 3 weight 71.500 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 128 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 5.685805895435857
Carbon footprint of the manufacturing phase [a1 to a3] 6 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.5330193797030365
Carbon footprint of the distribution phase [a4] 0.5 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.06943030581471846
Carbon footprint of the installation phase [a5] 0.1 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 119.76184204865028
Carbon footprint of the use phase [b2, b3, b4, b6] 120 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 1.6155102246436364
Carbon footprint of the end-of-life phase [c1 to c4] 2 kg CO2 eq.
Pvc free Yes
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 127.66560785424754
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
Pvc free Yes
End of life manual availability ENVEOLI1503009EN
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Data Bulletin

  • Installation Instruction

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.