Browse all
Browse all

TeSys D Contactor TeSys Deca, 3P(3 NO), AC-3, 0 to 440V, 65A, 12VAC 50 Hz coil

TeSys D Contactor TeSys Deca, 3P(3 NO), AC-3, 0 to 440V, 65A, 12VAC 50 Hz coil

Item Number: LC1D65AJ5

Datasheet

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range
  • TeSys
  • TeSys Deca
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current
  • 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Mechanical durability 6 Mcycles
Electrical durability
  • 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
  • 1.45 Mcycles 65 A AC-3 at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end
  • power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end
  • power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end
  • power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end
  • power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid without cable end
  • power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Standards
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • CSA C22.2 No 14
  • UL 60947-4-1
  • IEC 60335-2-40:Annex JJ
  • UL 60335-2-40:Annex JJ
  • IEC 60335-1:Clause 30.2
Product certifications
  • CCC
  • UL
  • CB Scheme
  • CSA
  • CE
  • UKCA
  • Marine
  • EAC
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 122 mm
Width 55 mm
Depth 120 mm
Net weight 0.86 kg

Others

Legacy weee scope In
Package 1 bare product quantity 1
At least in Europe
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty duration(in months) bmecat 18
Device short name LC1D
Contactor application
  • motor control
  • resistive load
Utilisation category
  • AC-3
  • AC-4
  • AC-1
Poles description 3P
[uc] control circuit voltage 12 V AC 50 Hz
Motor power kw
  • 11 kW at 400 V AC 50/60 Hz (AC-4)
  • 18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
  • 30 kW at 380...400 V AC 50/60 Hz (AC-3)
  • 37 kW at 500 V AC 50/60 Hz (AC-3)
  • 37 kW at 660...690 V AC 50/60 Hz (AC-3)
  • 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
  • 30 kW at 380...400 V AC 50/60 Hz (AC-3e)
  • 37 kW at 500 V AC 50/60 Hz (AC-3e)
  • 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
  • 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 5 hp at 115 V AC 50/60 Hz for 1 phase motors
  • 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
  • 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M2
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 80 A (at 60 °C) for power circuit
Irms rated making capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 640 A 40 °C - 10 s for power circuit
  • 900 A 40 °C - 1 s for power circuit
  • 110 A 40 °C - 10 min for power circuit
  • 260 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 125 A gG at <= 690 V coordination type 1 for power circuit
  • 125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
  • 9.6 W AC-1
  • 6.3 W AC-3
[ui] rated insulation voltage
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
  • power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC at 50 Hz
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
  • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50 Hz
  • 1...1.1 Uc (60-70 °C):operational AC 50 Hz
Inrush power in va 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 4...5 W at 50 Hz
Operating time
  • 4...19 ms opening
  • 12...26 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver Philips No 2
  • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
  • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
  • control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2
  • power circuit: 2.5 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor closed (15 Gn for 11 ms)
  • shocks contactor open (10 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 6 cm
Package 1 width 14 cm
Package 1 length 15 cm
Package 1 weight 0.85 kg
Sustainable packaging No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Data Bulletin

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity

Important: Some software files may need a mySchneider or Club login to download.