Design

Range TeSys
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage power circuit: <= 1000 V AC 25...400 Hz
[ie] rated operational current 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Mechanical durability 6 Mcycles
Electrical durability 1.4 Mcycles 60 A AC-1 at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 1 2.5-25 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 2 2.5-16 mm² - cable stiffness: solid without cable end
Mounting support
  • rail
  • plate
Connections - terminals screw clamp terminals
Standards
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
Product certifications
  • UL
  • CSA
  • CCC
  • EAC
  • UKCA
  • CB
  • EU-RO-MR by DNV-GL
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand conforming to IACS E10 exposure to damp heat
Height 127 mm
Width 85 mm
Depth 125 mm
Net weight 1.44 kg
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1102005EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Average percentage of recycled plastic content 0 %
Package 1 bare product quantity 1
Legacy weee scope In
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application resistive load
Utilisation category AC-1
Poles description 4P
[uc] control circuit voltage 42 V AC 50/60 Hz
Compatibility code LC1D
Pole contact composition 2 NO + 2 NC
Protective cover with
[ith] conventional free air thermal current 60 A (at 60 °C) for power circuit
Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 320 A 40 °C - 10 s for power circuit
  • 720 A 40 °C - 1 s for power circuit
  • 72 A 40 °C - 10 min for power circuit
  • 165 A 40 °C - 1 min for power circuit
Associated fuse rating
  • 80 A gG at <= 690 V coordination type 1 for power circuit
  • 80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole 5.4 W AC-1
[ui] rated insulation voltage
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC at 50/60 Hz
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
  • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
  • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
  • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in va
  • 245 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 245 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va
  • 13 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 4...5 W at 50/60 Hz
Operating time
  • 4...19 ms opening
  • 12...26 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
  • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Contact compatibility M1
[uc] control circuit voltage 42 V
Rated thermal current (ith) 60 A
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • shocks contactor open (8 Gn for 11 ms)
  • shocks contactor closed (10 Gn for 11 ms)
  • vibrations contactor opened (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 11.400 cm
Package 1 width 13.600 cm
Package 1 length 15.800 cm
Package 1 weight 1.490 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 52 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 8.921945858891672
Carbon footprint of the manufacturing phase [a1 to a3] 9 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.1760063361869087
Carbon footprint of the distribution phase [a4] 0.2 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.2523595925959343
Carbon footprint of the installation phase [a5] 0.3 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 39.799710144927516
Carbon footprint of the use phase [b2, b3, b4, b6] 40 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 3.328416174215296
Carbon footprint of the end-of-life phase [c1 to c4] 3 kg CO2 eq.
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 52.47843810681733
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
End of life manual availability N/A
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.