Browse all
Browse all

TeSys D Contactor 3P(3 NO), AC-3, <lt/>= 440V, 95A, 110V DC coil

TeSys D Contactor 3P(3 NO), AC-3, <lt/>= 440V, 95A, 110V DC coil

Item Number: LC1D95FW

Datasheet

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth186 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range
  • TeSys
  • TeSys Deca
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage power circuit: <= 690 V AC 25...400 Hz
[ie] rated operational current
  • 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
  • 125 A (at <60 °C) at <= 690 V AC-1 for power circuit
Mechanical durability 10 Mcycles
Electrical durability
  • 1.2 Mcycles 95 A AC-3
  • 1.3 Mcycles 125 A AC-1
Connections - terminals
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • power circuit: screw terminals 1 4-50 mm² - cable stiffness: rigid
  • power circuit: screw terminals 2 4-25 mm² - cable stiffness: rigid
  • power circuit: screw terminals 1 4-50 mm² - cable stiffness: flexible without cable end
  • power circuit: screw terminals 2 4-25 mm² - cable stiffness: flexible without cable end
  • power circuit: screw terminals 1 4-50 mm² - cable stiffness: flexible with cable end
  • power circuit: screw terminals 2 4-16 mm² - cable stiffness: flexible with cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • plate
  • rail
Standards
  • EN/IEC 60947-1
  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • GB/T 14048.4
Product certifications
  • IECEE CB Scheme
  • CCC
  • EAC
  • LROS (Lloyds register of shipping)
  • RINA
  • BV
  • DNV-GL
Ip degree of protection IP20 conforming to IEC 60529
Climatic withstand conforming to IACS E10 exposure to damp heat
Height 127 mm
Width 85 mm
Depth 186 mm
Net weight 2.61 kg
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
China rohs regulation X
Eu rohs directive Compliant

Others

Legacy weee scope In
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • motor control
  • resistive load
Utilisation category
  • AC-3
  • AC-3e
  • AC-4
  • AC-1
Poles description 3P
[uc] control circuit voltage 110 V DC
Motor power kw
  • 25 kW at 220...230 V AC 50 Hz (AC-3)
  • 45 kW at 380...400 V AC 50 Hz (AC-3)
  • 45 kW at 415...440 V AC 50 Hz (AC-3)
  • 55 kW at 500 V AC 50 Hz (AC-3)
  • 45 kW at 660...690 V AC 50 Hz (AC-3)
  • 15 kW at 400 V AC 50 Hz (AC-4)
  • 25 kW at 220...230 V AC 50 Hz (AC-3e)
  • 45 kW at 380...400 V AC 50 Hz (AC-3e)
  • 45 kW at 415...440 V AC 50 Hz (AC-3e)
  • 55 kW at 500 V AC 50 Hz (AC-3e)
  • 45 kW at 660...690 V AC 50 Hz (AC-3e)
Motor power hp
  • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
  • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
  • 25 hp at 200/208 V AC 60 Hz for 3 phases motors
  • 30 hp at 230/240 V AC 60 Hz for 3 phases motors
  • 60 hp at 460/480 V AC 60 Hz for 3 phases motors
  • 60 hp at 575/600 V AC 60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M9
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 125 A (at 60 °C) for power circuit
Irms rated making capacity
  • 1100 A at 440 V AC for power circuit conforming to IEC 60947
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 1100 A 40 °C - 1 s for power circuit
  • 800 A 40 °C - 10 s for power circuit
  • 400 A 40 °C - 1 min for power circuit
  • 135 A 40 °C - 10 min for power circuit
  • 140 A - 100 ms for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 100 A - 1 s for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 160 A gG at <= 690 V coordination type 2 for power circuit
  • 200 A gG at <= 690 V coordination type 1 for power circuit
Average impedance 0.8 Ohm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
  • 12.5 W AC-1
  • 7.2 W AC-3
[ui] rated insulation voltage
  • power circuit: 1000 V conforming to IEC 60947-1
  • signalling circuit: 690 V conforming to IEC 60947-1
Overvoltage category III
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type DC wide range
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.1...0.3 Uc (-40-70 °C):drop-out DC
  • 0.75...1.2 Uc (-40-55 °C):operational DC
  • 1...1.2 Uc (55-70 °C):operational DC
Inrush power in w 22 W (at 20 °C)
Hold-in power consumption in w 22 W at 20 °C
Operating time
  • 20...35 ms opening
  • 95...130 ms closing
Time constant 75 ms
Tightening torque
  • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
  • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
  • power circuit: 12 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
  • power circuit: 12 N.m - on screw terminal - with screwdriver hex (Allen key)4 mm
  • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contacts
  • 1.5 ms on energisation between NC and NO contacts
Protective treatment TH (pollution degree 3) conforming to IEC 60068-2-30
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • shocks contactor opened (8 Gn for 11 ms)
  • shocks contactor closed (10 Gn for 11 ms)
  • vibrations contactor opened (2 Gn, 5...300 Hz)
  • vibrations contactor closed (3 Gn, 5...300 Hz)
Unit type of package 1 PCE
Number of units in package 1 1
Sustainable packaging No
China rohs label 1
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.