Browse all
Browse all

TeSys D Contactor 3P(3 NO), AC-3, <= 440 V 12A, 240V AC coil

TeSys D Contactor 3P(3 NO), AC-3, <= 440 V 12A, 240V AC coil

Item Number: LC1D123U7

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height99 mm

Depth icon

Depth86 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current
  • 16 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability 15 Mcycles
Electrical durability
  • 2 Mcycles 12 A AC-3 at Ue <= 440 V
  • 0.8 Mcycles 25 A AC-1 at Ue <= 440 V
Connections - terminals
  • power circuit: spring terminals 1 2.5-2.5 mm² - cable stiffness: flexible without cable end
  • power circuit: spring terminals 2 2.5-2.5 mm² - cable stiffness: flexible without cable end
  • control circuit: spring terminals 1 2.5-2.5 mm² - cable stiffness: flexible without cable end
  • control circuit: spring terminals 2 2.5-2.5 mm² - cable stiffness: flexible without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 508
Product certifications
  • LROS (Lloyds register of shipping)
  • BV
  • CCC
  • GOST
  • CSA
  • RINA
  • UL
  • GL
  • DNV
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 99 mm
Width 45 mm
Depth 86 mm
Net weight 0.325 kg
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1501004EN
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity 1
Legacy weee scope In
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • resistive load
  • motor control
Utilisation category
  • AC-1
  • AC-3
  • AC-4
  • AC-3e
Poles description 3P
[uc] control circuit voltage 240 V AC 50/60 Hz
Motor power kw
  • 3 kW at 220...230 V AC 50/60 Hz (AC-3)
  • 5.5 kW at 380...400 V AC 50/60 Hz (AC-3)
  • 5.5 kW at 415...440 V AC 50/60 Hz (AC-3)
  • 7.5 kW at 500 V AC 50/60 Hz (AC-3)
  • 7.5 kW at 660...690 V AC 50/60 Hz (AC-3)
  • 3.7 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp
  • 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
  • 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
  • 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M2
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 16 A (at 60 °C) for power circuit
Irms rated making capacity
  • 250 A at 440 V for power circuit conforming to IEC 60947
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 105 A 40 °C - 10 s for power circuit
  • 210 A 40 °C - 1 s for power circuit
  • 30 A 40 °C - 10 min for power circuit
  • 61 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 40 A gG at <= 690 V coordination type 1 for power circuit
  • 25 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 16 A 50 Hz for power circuit
Power dissipation per pole
  • 0.36 W AC-3
  • 1.56 W AC-1
[ui] rated insulation voltage
  • power circuit: 690 V conforming to IEC 60947-4-1
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC at 50/60 Hz
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
  • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
  • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
  • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in va
  • 70 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va
  • 7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 2...3 W at 50/60 Hz
Operating time
  • 12...22 ms closing
  • 4...19 ms opening
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor open (10 Gn for 11 ms)
  • shocks contactor closed (15 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 11.4 cm
Package 1 width 10.5 cm
Package 1 length 5.4 cm
Package 1 weight 330 g
Sustainable packaging No
Pvc free Yes
China rohs label 1
Pvc free Yes
End of life manual availability ENVEOLI1501004EN
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • Data Bulletin

  • Installation Instruction

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.