Browse all
Browse all

Clipsal - Max 4 Arc Fault Detection Device (AFDD) 1PN 6A C curve 30mA Type A 6000A

Home ProductsCircuit ProtectionMax 4Arc Fault Detection Device (AFDD)

Clipsal - Max 4 Arc Fault Detection Device (AFDD) 1PN 6A C curve 30mA Type A 6000A

Item Number: 4AFRC206

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range MAX4
Product brand Clipsal
Product or component type arc fault detection RCBO

Physical

Standards
  • IEC 62606
  • AS/NZS 61009.1
[in] rated current 6 A
[ue] rated operational voltage
  • 230/240 V AC 50 Hz conforming to AS/NZS 61009.1
  • 230/240 V AC 50 Hz conforming to IEC 62606
Control type toggle
Local signalling ON, OFF, fault trip
Mounting mode clip-on
Mounting support DIN rail
Mechanical durability 20000 cycles
Electrical durability 20000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1
Cable entry top and bottom
Connections - terminals
  • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid
  • tunnel type terminal for 1 cable(s) 16-16 mm² rigid
  • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible
  • tunnel type terminal for 1 cable(s) 10-10 mm² flexible
Wire stripping length 14 mm
Height 91 mm
Width 36 mm
Depth 75 mm
Net weight 205 g
Ip degree of protection IP20 conforming to IEC 60529
Relative humidity 95 % at 55 °C
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...80 °C
Product certifications RCM
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2205013EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Legacy weee scope In
Outside of Europe
Warranty duration(in months) bmecat 18
Package 1 bare product quantity 1
Weee label N/A
Product name MAX4 AFDD
Product specific application arc fault detection
Device short name AFDD
Poles description 1P + N
Number of protected poles 1
Curve code C
Breaking capacity 6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Earth-leakage sensitivity 30 mA
Network type AC
Earth-leakage protection time delay instantaneous
Earth-leakage protection class class A
Neutral position left
Suitability for isolation yes
Residual current tripping technology voltage dependent
Trip unit technology thermal-magnetic
Earth-leakage protection integrated
Network frequency 50 Hz
Device location in system outgoer
Magnetic tripping limit 5...10 x In
[ics] rated service breaking capacity 6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Limitation class 3 conforming to AS/NZS 61009.1
Threshold tripping voltage 275 V for +/- 5 V
[uimp] rated impulse withstand voltage 4 kV conforming to AS/NZS 61009.1
Contact position indicator yes
Overvoltage category III
Locking options description padlocking device (A9A26970)
Tightening torque 2 N.m
Comb busbar and distribution block compatibility YES
9 mm pitches 4
Heat dissipation 1.53...1.53 W at 230 V - 6 A
Pollution degree
  • 2 conforming to AS/NZS 61009.1
  • 2 conforming to IEC 62606
Tropicalisation severity B conforming to IEC 60068-2-30 for 28 d
Operating altitude 2000 m
Quality labels RCM
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 7.5 cm
Package 1 width 3.6 cm
Package 1 length 9.1 cm
Package 1 weight 233.0 g
Sustainable packaging No
Pvc free No
Halogen-free status Halogen free plastic parts product
Silicone-free  No
Packaging made with recycled cardboard Yes
Scip number b078722f-7853-4e1e-a05b-29638f57b0ab
Halogen-free status Halogen free plastic parts product
Pvc free No
Silicone-free No
End of life manual availability ENVEOLI2205013EN
Warranty (in months) 18