Acti9 iC60 RCBO Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 16A, 30mA, A type, 6000A

Home ProductsCircuit ProtectionActi9Residual current breaker with overcurrent protection (RCBO)

Acti9 iC60 RCBO Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 16A, 30mA, A type, 6000A

Item Number: A9DC6916

Datasheet

Product Dimensions

Width icon

Width54 mm

Height icon

Height112 mm

Depth icon

Depth77.2 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Physical

[in] rated current

16 A at 30 °C

[ue] rated operational voltage

400/415 V

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

112 mm

Width

54 mm

Depth

77.2 mm

Net weight

462 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

screw clamp terminal (top) 1-25 mm² rigid without cable end

Wire stripping length

power circuit: 11 mm for bottom connection

Standards

AS/NZS 61009.1

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-5...60 °C

Ambient air temperature for storage

-25...70 °C

Reach free of svhc

Yes

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP2308033_V2

Eu rohs directive

Compliant

Reach regulation

Free of Substances of Very High Concern above the threshold

Eu rohs directive

Compliant

China rohs regulation

Pro-active China RoHS declaration (out of China RoHS legal scope)

Others

Package 1 bare product quantity

1

Legacy weee scope

In

Outside of Europe

Package 2 bare product quantity

16

Average percentage of recycled plastic content

0 %

Weee label

N/A

Weee applicability

Finished product

Circuit breaker application

distribution

Product name

Acti9 iC60 RCBO

Device short name

iC60N3 RCBO

Poles description

3P + Ns

Earthing system

TN

Curve code

C

Earth-leakage sensitivity

30 mA

Breaking capacity

6000 A Icn at 400/415 V

Neutral position

left

Number of protected poles

3

Device location in system

outgoer

Network frequency

50/60 Hz

Network type

AC

Trip unit technology

thermal-magnetic

Residual current tripping technology

voltage dependent

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

[icw] rated short-time withstand current

Icw: 250 A during 8/20 µs impulse withstand

[ics] rated service breaking capacity

6000 A

Limitation class

3

[ui] rated insulation voltage

500 V

[uimp] rated impulse withstand voltage

4 kV

Surge current

250 A

Suitability for isolation

yes conforming to IEC 61009-1

Comb busbar and distribution block compatibility

YES

9 mm pitches

6

Provision for padlocking

padlockable with padlock Ø 4 mm

Locking options description

ON/OFF locking facilities

Tightening torque

power circuit: 2.5...2.5 N.m top

Earth-leakage protection

integrated

Test button operating voltage

260...457 V

Operating voltage earthleakage protection

150...457 V

Grid distance

45 mm

Locking options description

handle sealable with cable diameter 1.4mm in OFF or ON position

Tropicalisation

2

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

12.7 cm

Package 1 width

6.6 cm

Package 1 length

9 cm

Package 1 weight

539 g

Unit type of package 2

S02

Number of units in package 2

16

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

9.376 kg

Green premium status for reporting

Green Premium product

Total lifecycle carbon footprint

44 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

5.16357713717693

Carbon footprint of the manufacturing phase [a1 to a3]

5 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.0466229642147117

Carbon footprint of the distribution phase [a4]

0 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.0822505427435387

Carbon footprint of the installation phase [a5]

0.1 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

37.42

Carbon footprint of the use phase [b2, b3, b4, b6]

37 kg CO2 eq.

Sustainable packaging

No

Carbon footprint of the end-of-life phase [c1 to c4]

1.32113936381709

Carbon footprint of the end-of-life phase [c1 to c4]

1 kg CO2 eq.

Pvc free

Yes

Halogen-free status

Product contains halogen above thresholds

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

44.0335900079522

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

No

Packaging without single use plastic

No

China rohs label

1

Halogen-free status

Product contains halogen above thresholds

Pvc free

Yes

End of life manual availability

ENVEOLI2308033EN

Take-back

No

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.