Specifications
Design
| Range | Acti9 |
|---|---|
| Product or component type | residual current breaker with overcurrent protection (RCBO) |
Physical
| [in] rated current | 16 A at 30 °C |
|---|---|
| [ue] rated operational voltage | 400/415 V |
| Control type | toggle |
| Local signalling | ON/OFF indication |
| Mounting mode | clip-on |
| Mounting support | DIN rail |
| Height | 112 mm |
| Width | 54 mm |
| Depth | 77.2 mm |
| Net weight | 462 g |
| Mechanical durability | 20000 cycles |
| Electrical durability | 5000 cycles |
| Connections - terminals | screw clamp terminal (top) 1-25 mm² rigid without cable end |
| Wire stripping length | power circuit: 11 mm for bottom connection |
| Standards | AS/NZS 61009.1 |
| Ip degree of protection | IP20 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -5...60 °C |
| Ambient air temperature for storage | -25...70 °C |
| Reach free of svhc | Yes |
| Toxic heavy metal free | Yes |
| Mercury free | Yes |
| Rohs exemption information | Yes |
| Environmental disclosure | ENVPEP2308033EN |
| Reach regulation | Free of Substances of Very High Concern above the threshold |
| China rohs regulation | Product out of China RoHS scope |
| Eu rohs directive | Compliant |