Browse all
Browse all

Acti9 Arc fault detection switch Acti9 iARC, 1P+N, 25A, 10000A

Home ProductsCircuit ProtectionActi9Arc fault detection switch

Acti9 Arc fault detection switch Acti9 iARC, 1P+N, 25A, 10000A

Item Number: A9TS1225

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range Acti9
Product or component type arc fault detection switch

Physical

[in] rated current 25 A
[ue] rated operational voltage 230...240 V AC 50 Hz conforming to IEC 62606
Control type toggle
Local signalling ON, OFF, fault trip
Mounting mode clip-on
Mounting support DIN rail
Mechanical durability 20000 cycles
Electrical durability 10000 cycles 240 V AC 50 Hz conforming to IEC 62606
Connections - terminals
  • tunnel type terminal2 cable(s) 2.5-2.5 mm² rigid
  • tunnel type terminal1 cable(s) 16-16 mm² rigid
  • tunnel type terminal2 cable(s) 2.5-2.5 mm² flexible
  • tunnel type terminal1 cable(s) 10-10 mm² flexible
Cable entry top and bottom
Wire stripping length 14 mm
Height 91 mm
Width 36 mm
Depth 75 mm
Net weight 205 g
Ip degree of protection IP20 conforming to IEC 60529
Relative humidity 95 % at 55 °C
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...80 °C
Standards IEC 62606
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2205013EN
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Legacy weee scope In
Package 1 bare product quantity 1
Outside of Europe
Warranty duration(in months) bmecat 18
Weee label N/A
Product specific application arc fault detection
Product name Acti9 iARC
Device short name iARC
Poles description 1P + N
Neutral position left
Network type AC
Rated breaking and making capacity Im = 500 A
Rated conditional short-circuit current
  • upstream MCB 25A: Inc 10 kA
  • upstream RCBO 25A: Inc 10 kA
Device location in system outgoer
Network frequency 50 Hz
[ui] rated insulation voltage
  • 250 V AC 50 Hz between phase and neutral
  • 400 V AC 50 Hz between phases
[uimp] rated impulse withstand voltage 4 kV conforming to IEC 62606
Threshold tripping voltage 275 V for +/- 5 V
Contact position indicator yes
Heat dissipation 4.38...4.38 W at 240 V - 25 A
Total power losses 4.4 W
Power losses per pole 4.4 W
Locking options description padlocking device
Tightening torque 2 N.m
9 mm pitches 4
Pollution degree 2 conforming to IEC 62606
Overvoltage category III
Tropicalisation severity B conforming to IEC 60068-2-30 for 28 d
Operating altitude 2000 m
Quality labels RCM
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 7.5 cm
Package 1 width 3.6 cm
Package 1 length 9.1 cm
Package 1 weight 240.0 g
Sustainable packaging No
Pvc free No
Halogen-free status Halogen free plastic parts product
Take-back No
Average percentage of recycled metal content 0 %
Scip number 8b63a121-e746-45cc-9c47-575c8603416f
Halogen-free status Halogen free plastic parts product
Pvc free No
End of life manual availability ENVEOLI2205013EN
Take-back No
Warranty (in months) 18