Modicon TM3, Remote receiver module

Home ProductsIndustrialModiconRemote receiver module

Modicon TM3, Remote receiver module

Item Number: TM3XREC1

Datasheet

Product Dimensions

Width icon

Width23.65 mm

Height icon

Height90 mm

Depth icon

Depth73.3 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Modicon TM3

Product or component type

remote receiver module

Physical

Range compatibility

  • Modicon M221
  • Modicon M251
  • Modicon M241
  • Modicon M262

Local signalling

  • 1 LED green for power supply
  • 1 LED green for Link (Link Status)

Mounting support

  • top hat type TH35-15 rail conforming to IEC 60715
  • top hat type TH35-7.5 rail conforming to IEC 60715
  • plate or panel with fixing kit

Height

90 mm

Width

23.65 mm

Depth

73.3 mm

Net weight

0.075 kg

Ip degree of protection

IP20

Marking

CE

Product certifications

  • Merchant Navy
  • GOST
  • C-Tick
  • CSA HazLoc
  • CE
  • UKCA
  • RCM
  • EAC
  • cULus

Standards

  • CSA C22.2 No 213 Class I Division 2 Group A
  • CSA C22.2 No 213 Class I Division 2 Group B
  • CSA C22.2 No 213 Class I Division 2 Group C
  • CSA C22.2 No 213 Class I Division 2 Group D
  • UL 1604 Class 1 Division 2
  • CSA C22.2 No 142
  • IEC 61131-2
  • UL 508

Ambient air temperature for operation

  • -10...55 °C (horizontal installation)
  • -10...50 °C (vertical installation)

Ambient air temperature for storage

-40...70 °C

Relative humidity

5...95 % without condensation

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP1403011EN

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Reach regulation

Reference contains Substances of Very High Concern above the threshold

China rohs regulation

X

Eu rohs directive

Compliant By Exemption

China rohs regulation

X

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope

In

Average percentage of recycled plastic content

0 %

Package 3 bare product quantity

144

At least in Europe

Package 2 bare product quantity

18

Package 1 bare product quantity

1

Warranty duration(in months) bmecat

18

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Maximum number of i/o expansion module

7

[us] rated supply voltage

24 V DC by external supply (- 15...20 %)

Power supply output current

  • 560 mA 5 V for expansion bus
  • 560 mA 24 V for expansion bus

Current consumption

40 mA at 24 V DC via bus connector

Maximum power dissipation in w

1 W

Cable distance between devices

0.5 mm extension cable with 2 RJ45 conductor between receiver and transmitter

Electrical connection

  • RJ45 connector for connecting the bus transmitter
  • removable screw terminal block, 3 terminal(s) for connecting the 24 V DC power supply

Dc supply voltage

24 V

Network type

DC

Number of hw interfaces can

0

Number of hw interfaces industrial ethernet

0

Number of hw interfaces profinet

0

Number of hw interfaces serial rs232

0

Number of hw interfaces serial rs422

0

Number of hw interfaces serial rs485

0

Number of hw interfaces serial tty

0

Number of hw interfaces usb

0

Number of hw interfaces parallel

0

Number of hw interfaces wireless

0

Number of hw interfaces other

1

Supporting protocol for ethercat

false

Supporting protocol for tcp/ip

false

Supporting protocol for profibus

false

Supporting protocol for can

false

Supporting protocol for interbus

false

Supporting protocol for asi

false

Supporting protocol for knx

false

Supporting protocol for modbus

false

Supporting protocol for data-highway

false

Supporting protocol for devicenet

false

Supporting protocol for suconet

false

Supporting protocol for lon

false

Supporting protocol for sercos

false

Supporting protocol for profinet io

false

Supporting protocol for profinet cba

false

Supporting protocol for foundation fieldbus

false

Supporting protocol for ethernet/ip

false

Supporting protocol for as-interface safety at work

false

Supporting protocol for devicenet safety

false

Supporting protocol for interbus-safety

false

Supporting protocol for profisafe

false

Supporting protocol for safetybus p

false

Supporting protocol for other bus systems

false

Radio standard bluetooth

false

Radio standard wi-fi 802.11

false

Radio standard gprs

false

Radio standard egprs

false

Radio standard gsm

false

Radio standard lte

false

Radio standard umts

false

Io-link master present

false

System accessory

false

Potential separation present

false

Bearing track assembly possible

true

Wall mounting/direct mounting possible

false

Front installation possible

false

Rack-assembly possible

false

Suitable for safety functions

false

Electromagnetic emission

  • radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to IEC 55011
  • radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230-1000 MHz conforming to IEC 55011

Operating altitude

0...2000 m

Pollution degree

2

Vibration resistance

  • 3.5 mm (f = 5-8.4 Hz) on DIN rail
  • 3 gn (f = 8.4-150 Hz) on DIN rail
  • 3.5 mm (f = 5-8.4 Hz) on panel mounting
  • 3 gn (f = 8.4-150 Hz) on panel mounting

Shock resistance

15 gn for 11 ms

Performance level according to en iso 13849-1

none

Appendant operation agent (ex ia)

false

Appendant operation agent (ex ib)

false

Certified for ul hazardous location class i

false

Certified for ul hazardous location class ii

false

Certified for ul hazardous location class iii

false

Certified for ul hazardous location division 1

false

Certified for ul hazardous location division 2

false

Certified for ul hazardous location group a (acetylene)

false

Certified for ul hazardous location group b (hydrogen)

false

Certified for ul hazardous location group c (ethylene))

false

Certified for ul hazardous location group d (propane))

false

Certified for ul hazardous location group e (metal dusts)

false

Certified for ul hazardous location group f (carbonaceous dust)

false

Certified for ul hazardous location group g (non conductive dust)

false

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.414 cm

Package 1 width

10.483 cm

Package 1 length

12.587 cm

Package 1 weight

160.0 g

Unit type of package 2

S03

Number of units in package 2

18

Package 2 height

30 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

3.631 kg

Unit type of package 3

P12

Number of units in package 3

144

Package 3 height

75 cm

Package 3 width

60 cm

Package 3 length

80 cm

Package 3 weight

40 kg

Green premium status for reporting

Green Premium product

Total lifecycle carbon footprint

21 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

1.3682172373

Carbon footprint of the manufacturing phase [a1 to a3]

1 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.0206432113

Carbon footprint of the distribution phase [a4]

0 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.0004451192

Carbon footprint of the installation phase [a5]

0 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

19.5927483525

Carbon footprint of the use phase [b2, b3, b4, b6]

20 kg CO2 eq.

Sustainable packaging

Yes

Carbon footprint of the end-of-life phase [c1 to c4]

0.044094451

Carbon footprint of the end-of-life phase [c1 to c4]

0 kg CO2 eq.

Pvc free

Yes

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

21.0261483714

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

Scip number

91cf81c4-f22d-428b-a036-2e24fcc66509

China rohs label

5

Pvc free

Yes

End of life manual availability

ENVEOLI1403011EN

Take-back

No

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Warranty (in months)

18
Show all specifications

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Operating Manuals

  • Technical Drawing

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.