Standard Series, Automatic Single Socket Outlet, 250VAC, 10A, Skirting Duct

Standard Series, Automatic Single Socket Outlet, 250VAC, 10A, Skirting Duct White Electric

Item Number: 12M-WE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Series 12M

Product or component type

socket-outlet

Product brand

Clipsal

Physical

Quantity per set

set of 1

Marking

without marking

Local signalling

without light indicator

Mounting support

skirt

Fixing mode

by screws

[in] rated current

10 A

[ue] rated operational voltage

250 V AC

Depth

29 mm

Length

63 mm

Width

43 mm

Number of poles

1

Standards

AS/NZS 3112|AS 3100|AS 3109|AS/NZS 3122:approval number S/1

Eu rohs directive

Compliant with Exemptions

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP120506EN

Circularity profile

N/A

Others

Package 1 bare product quantity

1

Cover type

complete housing

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

3 cm

Package 1 width

4.3 cm

Package 1 length

6 cm

Package 1 weight

68 g
Show all specifications

Frequently Asked Questions

hide show

What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

Issue:
LC1D09 - LC1D38 Coil tolerance

Product Line:
Contactors and Starters, IEC

Environment:
Tesys D Contactors

Cause:
Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

Resolution:
AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
DC standard coil for LP1D12 and D25: (-20% / +10%)
DC wide range coil for LP1D12 and D25 : (-30% to +25%)

What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

Issue:
Identifying maximum voltage of an LC1D contactor

Product Line:
TeSys D Contactors

Environment:
Contactors and Starters IEC

Resolution:
IThe maximum voltage per UL and CSA is 600VAC. 
 

What is the altitude derating for a TeSys D-Line contactor?

Issue:​
What is the altitude derating for a TeSys D-Line contactor?

Product Line:
Digest 177 Section 18 : Contactors and Starters, IEC

Environment:
North American Products

Resolution:
The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

Voltage
3500m x 0.90
4000m x 0.80
4500m x 0.70
5000m x 0.60

Current
3500m x 0.92
4000m x 0.90
4500m x 0.88
5000m x 0.86

For example, an LC1D80 at 5000 meters:
- The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
- The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



 

Can a molded case switch be reverse fed or backfed?

Issue:
Are the Powerpact and Legacy rated for feed in either direction?
 
Product Line:
Molded Case Switches
 
Resolution:
Yes, the molded case switches have been UL tested for reverse feed applications and are not marked line and load.

How do you change the carrier switching frequency in an ATV66 drive?

Issue:
Change the carrier switching frequency in an ATV66 drive

Product Line:
Altivar ATV66

Environment:
All

Cause:
Needs to change the switching frequency because of motor noise.

Resolution:
The only way to change carrier frequency is to go from CT or VT to VTLN or NOLD in menu 7.13.
There is no separate parameter available for switching frequency adjustment.
Refer to the ATV66 user manual VD0C06S305C  page 61.


CTA-ID : 2018068

What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

Issue:
Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

Product Line:
IEC Contactors and Starters

Environment:
Tesys D Contactors

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
stranded cable w/cable end: One or Two #18-10 AWG per terminal.
solid cable: One or Two #18-8 AWG per terminal.