Browse all
Browse all

TeSys D Contactor 3P(3NO), AC-3/AC-3e ,<=440V 18A, 110V DC coil

TeSys D Contactor 3P(3NO), AC-3/AC-3e ,<=440V 18A, 110V DC coil

Item Number: LC1D18FD

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth95 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current
  • 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability 30 Mcycles
Electrical durability
  • 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
  • 1 Mcycles 32 A AC-1 at Ue <= 440 V
  • 1.65 Mcycles 18 A AC-3e at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 1 1-6 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Connections - terminals screw clamp terminals
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60947-4-1
  • IEC 60335-1:Clause 30.2
  • IEC 60335-2-40:Annex JJ
  • UL 60335-2-40:Annex JJ
  • CSA C22.2 No 60947-4-1
Product certifications
  • UL
  • CCC
  • CSA
  • Marine
  • UKCA
  • EAC
  • CB Scheme
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 77 mm
Width 45 mm
Depth 95 mm
Net weight 0.49 kg
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP110230EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Average percentage of recycled plastic content 0 %
Package 2 bare product quantity 15
Package 1 bare product quantity 1
Legacy weee scope In
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • motor control
  • resistive load
Utilisation category
  • AC-4
  • AC-1
  • AC-3
  • AC-3e
Poles description 3P
[uc] control circuit voltage 110 V DC
Motor power kw
  • 4 kW at 220...230 V AC 50/60 Hz (AC-3)
  • 7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
  • 9 kW at 415...440 V AC 50/60 Hz (AC-3)
  • 10 kW at 500 V AC 50/60 Hz (AC-3)
  • 10 kW at 660...690 V AC 50/60 Hz (AC-3)
  • 4 kW at 400 V AC 50/60 Hz (AC-4)
  • 4 kW at 220...230 V AC 50/60 Hz (AC-3e)
  • 7.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
  • 9 kW at 415...440 V AC 50/60 Hz (AC-3e)
  • 10 kW at 500 V AC 50/60 Hz (AC-3e)
  • 10 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
  • 1 hp at 115 V AC 50/60 Hz for 1 phase motors
  • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
  • 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 32 A (at 60 °C) for power circuit
Irms rated making capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 300 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 300 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 145 A 40 °C - 10 s for power circuit
  • 240 A 40 °C - 1 s for power circuit
  • 40 A 40 °C - 10 min for power circuit
  • 84 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 50 A gG at <= 690 V coordination type 1 for power circuit
  • 35 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit
Power dissipation per pole
  • 2.5 W AC-1
  • 0.8 W AC-3
  • 0.8 W AC-3e
[ui] rated insulation voltage
  • power circuit: 690 V conforming to IEC 60947-4-1
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type DC standard
Coil technology with integral suppression device
Control circuit voltage limits
  • 0.1...0.25 Uc (-40-70 °C):drop-out DC
  • 0.7...1.25 Uc (-40-60 °C):operational DC
  • 1...1.25 Uc (60-70 °C):operational DC
Inrush power in w 5.4...5.4 W (at 20 °C)
Hold-in power consumption in w 5.4...5.4 W at 20 °C
Operating time
  • 63 ±15 % ms closing
  • 20 ±20 % ms opening
Time constant 28 ms
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Contact compatibility M4
Maximum motor phase current 18 A
[uc] control circuit voltage 110 V
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor open (10 Gn for 11 ms)
  • shocks contactor closed (15 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 5.000 cm
Package 1 width 9.200 cm
Package 1 length 11.200 cm
Package 1 weight 526.000 g
Unit type of package 2 S02
Number of units in package 2 15
Package 2 height 15.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 8.088 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 39 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 2.7103153960992956
Carbon footprint of the manufacturing phase [a1 to a3] 3 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.1497941374842545
Carbon footprint of the distribution phase [a4] 0.1 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.041480539446657784
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 35.11783783783784
Carbon footprint of the use phase [b2, b3, b4, b6] 35 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 1.3125800413083537
Carbon footprint of the end-of-life phase [c1 to c4] 1 kg CO2 eq.
Pvc free Yes
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 39.3320079521764
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number 50ae7612-fd2e-41e4-a369-50d0dea6e592
Pvc free Yes
End of life manual availability ENVEOLI1102030EN
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.