Specifications
Design
Range
- TeSys
- TeSys Deca
Range of product
Product or component type
Warranty
Physical
[ue] rated operational voltage
[ie] rated operational current
- 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
- 125 A (at <60 °C) at <= 690 V AC-1 for power circuit
Mechanical durability
Electrical durability
- 1.2 Mcycles 95 A AC-3
- 1.3 Mcycles 125 A AC-1
Connections - terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
- power circuit: screw terminals 1 4-50 mm² - cable stiffness: rigid
- power circuit: screw terminals 2 4-25 mm² - cable stiffness: rigid
- power circuit: screw terminals 1 4-50 mm² - cable stiffness: flexible without cable end
- power circuit: screw terminals 2 4-25 mm² - cable stiffness: flexible without cable end
- power circuit: screw terminals 1 4-50 mm² - cable stiffness: flexible with cable end
- power circuit: screw terminals 2 4-16 mm² - cable stiffness: flexible with cable end
Insulation resistance
Mounting support
- plate
- rail
Standards
- EN/IEC 60947-1
- EN/IEC 60947-4-1
- EN/IEC 60947-5-1
- GB/T 14048.4
Product certifications
- IECEE CB Scheme
- CCC
- EAC
- LROS (Lloyds register of shipping)
- RINA
- BV
- DNV-GL
Ip degree of protection
Climatic withstand
Height
Width
Depth
Net weight
Eu rohs directive
Toxic heavy metal free
Mercury free
Rohs exemption information
China rohs regulation
Others
Device short name
Contactor application
- motor control
- resistive load
Utilisation category
- AC-3
- AC-3e
- AC-4
- AC-1
Poles description
[uc] control circuit voltage
Motor power kw
- 25 kW at 220...230 V AC 50 Hz (AC-3)
- 45 kW at 380...400 V AC 50 Hz (AC-3)
- 45 kW at 415...440 V AC 50 Hz (AC-3)
- 55 kW at 500 V AC 50 Hz (AC-3)
- 45 kW at 660...690 V AC 50 Hz (AC-3)
- 15 kW at 400 V AC 50 Hz (AC-4)
- 25 kW at 220...230 V AC 50 Hz (AC-3e)
- 45 kW at 380...400 V AC 50 Hz (AC-3e)
- 45 kW at 415...440 V AC 50 Hz (AC-3e)
- 55 kW at 500 V AC 50 Hz (AC-3e)
- 45 kW at 660...690 V AC 50 Hz (AC-3e)
Motor power hp
- 7.5 hp at 115 V AC 60 Hz for 1 phase motors
- 15 hp at 230/240 V AC 60 Hz for 1 phase motors
- 25 hp at 200/208 V AC 60 Hz for 3 phases motors
- 30 hp at 230/240 V AC 60 Hz for 3 phases motors
- 60 hp at 460/480 V AC 60 Hz for 3 phases motors
- 60 hp at 575/600 V AC 60 Hz for 3 phases motors
Compatibility code
Pole contact composition
Protective cover
[ith] conventional free air thermal current
- 10 A (at 60 °C) for signalling circuit
- 125 A (at 60 °C) for power circuit
Irms rated making capacity
- 1100 A at 440 V AC for power circuit conforming to IEC 60947
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
[icw] rated short-time withstand current
- 1100 A 40 °C - 1 s for power circuit
- 800 A 40 °C - 10 s for power circuit
- 400 A 40 °C - 1 min for power circuit
- 135 A 40 °C - 10 min for power circuit
- 140 A - 100 ms for signalling circuit
- 120 A - 500 ms for signalling circuit
- 100 A - 1 s for signalling circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 160 A gG at <= 690 V coordination type 2 for power circuit
- 200 A gG at <= 690 V coordination type 1 for power circuit
Average impedance
Power dissipation per pole
- 12.5 W AC-1
- 7.2 W AC-3
[ui] rated insulation voltage
- power circuit: 1000 V conforming to IEC 60947-1
- signalling circuit: 690 V conforming to IEC 60947-1
Overvoltage category
[uimp] rated impulse withstand voltage
Safety reliability level
- B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
Coil technology
Control circuit voltage limits
- 0.1...0.3 Uc (-40-70 °C):drop-out DC
- 0.75...1.2 Uc (-40-55 °C):operational DC
- 1...1.2 Uc (55-70 °C):operational DC
Inrush power in w
Hold-in power consumption in w
Operating time
- 20...35 ms opening
- 95...130 ms closing
Time constant
Tightening torque
- control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
- control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
- power circuit: 12 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
- power circuit: 12 N.m - on screw terminal - with screwdriver hex (Allen key)4 mm
- control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver pozidriv No 2
Auxiliary contact composition
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Minimum switching voltage
Minimum switching current
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contacts
- 1.5 ms on energisation between NC and NO contacts
Contact compatibility
Protective treatment
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
- shocks contactor opened (8 Gn for 11 ms)
- shocks contactor closed (10 Gn for 11 ms)
- vibrations contactor opened (2 Gn, 5...300 Hz)
- vibrations contactor closed (3 Gn, 5...300 Hz)
Unit type of package 1
Number of units in package 1
Weee