Modicon TM3 Input/output analog module 2 or temperature inputs, 1 output (screw) 24VDC
Item Number: TM3TM3
Specifications
Design
Range of product
Product or component type
Physical
Range compatibility
- Modicon M221
- Modicon M241
- Modicon M251
- Modicon M262
Load type
Type of cable
Local signalling
Marking
Mounting support
- top hat type TH35-15 rail conforming to IEC 60715
- top hat type TH35-7.5 rail conforming to IEC 60715
- plate or panel with fixing kit
Height
Depth
Width
Net weight
Standards
Product certifications
- CE
- UKCA
- RCM
- EAC
- cULus
- cULus HazLoc
Ambient air temperature for operation
- -10...55 °C horizontal installation
- -10...35 °C vertical installation
Ambient air temperature for storage
Relative humidity
- 10...95 %, without condensation (in operation)
- 10...95 %, without condensation (in storage)
Ip degree of protection
Reach regulation
Eu rohs directive
Toxic heavy metal free
Mercury free
Rohs exemption information
China rohs regulation
Environmental disclosure
Circularity profile
California proposition 65
Others
Package 3 bare product quantity
Package 2 bare product quantity
Package 1 bare product quantity
Analogue input number
Analogue input type
- current 4...20 mA
- current 0...20 mA
- voltage 0...10 V
- voltage - 10...10 V
- thermocouple - 200...1000 °C with thermocouple J
- thermocouple - 200...1300 °C with thermocouple K
- thermocouple 0...1760 °C with thermocouple R
- thermocouple 0...1760 °C with thermocouple S
- thermocouple 0...1820 °C with thermocouple B
- thermocouple - 200...400 °C with thermocouple T
- thermocouple - 200...1300 °C with thermocouple N
- thermocouple - 200...800 °C with thermocouple E
- thermocouple 0...2315 °C with thermocouple C
- Ni 100/Ni 1000 temperature probe - 60...180 °C
- Pt 100 temperature probe - 200...850 °C
- Pt 1000 temperature probe - 200...600 °C
Analogue output number
Analogue output type
- current: 4...20 mA
- current: 0...20 mA
- voltage: 0...10 V
- voltage: - 10...10 V
Analogue input resolution
- 16 bits
- 15 bits + sign
Permissible continuous overload
- 13 V, analogue input type: voltage
- 40 mA, analogue input type: current
Input impedance
- <= 50 Ohm current
- >= 1 MOhm voltage
- >= 1 MOhm thermocouple
- >= 1 MOhm temperature probe
Analogue output resolution
Lsb value
- 0.15 mV 0...10 Vvoltage
- 0.30 mV - 10...10 Vvoltage
- 0.30 µA 0...20 mAcurrent
- 0.244 µA 4...20 mAcurrent
- 0.1 °Ctemperature probe
- 0.1 °Cthermocouple
- 2.44 mV 0...10 V voltage
- 4.88 mV - 10...10 V voltage
- 4.88 µA 0...20 mA current
- 3.91 µA 4...20 mA current
Load impedance ohmic
- 1 kOhm voltage
- 300 Ohm current
Stabilisation time
Conversion time
- 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple
- 100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe
- 10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current
Sampling duration
- 10 ms, analogue input type: voltage/current
- 100 ms, analogue input type: voltage/current
- 100 ms, analogue input type: thermocouple
- 100 ms, analogue input type: temperature probe
Absolute accuracy error
- +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
- +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
- +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
- +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
- +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
- +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
- +/- 0.1 % of full scale at 25 °C for analogue input voltage/current
- +/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C
- +/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
- +/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
- +/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C
- +/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C
- +/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C
- +/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C
- +/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C
- +/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C
- +/- 0.1 % of full scale at 25 °C for analogue output voltage/current
Temperature drift
Repeat accuracy
- +/-0.5 %FS for input
- +/- 0.4 %FS for output
Non-linearity
- +/- 0.01 %FS, analogue output type: analog output
- +/- 0.1 %FS, analogue input type: analog input
Output ripple
Cross talk
[us] rated supply voltage
Supply voltage limits
Current consumption
- 55 mA at 24 V DC via external supply no load
- 55 mA at 5 V DC via bus connector no load
- 60 mA at 5 V DC via bus connector full load
- 80 mA at 24 V DC via external supply full load
Electrical connection
Insulation
- between input and supply at 1500 V AC
- between input and internal logic at 500 V AC
- between output and supply at 1500 V AC
- between output and internal logic at 500 V AC
Surge withstand
- 1 kV power supply common mode conforming to IEC 61000-4-5
- 0.5 kV power supply differential mode conforming to IEC 61000-4-5
- 1 kV I/O common mode conforming to IEC 61000-4-5
- 0.5 kV I/O differential mode conforming to IEC 61000-4-5
Resistance to electrostatic discharge
- 8 kV in air conforming to IEC 61000-4-2
- 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields
- 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
- 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
- 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields
Resistance to fast transients
Resistance to conducted disturbances
- 10 V 0.15...80 MHz conforming to IEC 61000-4-6
- 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
- radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to IEC 55011
- radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230-1000 MHz conforming to IEC 55011
Immunity to microbreaks
Pollution degree
Operating altitude
Storage altitude
Vibration resistance
- 3.5 mm at 5-8.4 Hz on DIN rail
- 3 gn at 8.4-150 Hz on DIN rail
Shock resistance
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight
Unit type of package 2
Number of units in package 2
Package 2 height
Package 2 width
Package 2 length
Package 2 weight
Unit type of package 3
Number of units in package 3
Package 3 height
Package 3 width
Package 3 length
Package 3 weight
Packaging made with recycled cardboard
Packaging without single use plastic
Weee
Pvc free
Pvc free
Take-back
Take-back
Product contributes to saved and avoided emissions
Removable battery
Carbon footprint (kg.eq.co2 per cr, total life cycle)
Global warming ; total life cycle
Minimum percentage of recycled plastic content
Documents & downloads
hide show-
All
-
CAD Files and Packs
-
Technical Data Catalogues
-
Installation Instruction
-
End of Life Manual
-
Environmental Disclosure
-
Operating Manuals
-
Technical Drawing
-
eTechPub
-
Certificates (MSDS)
-
Declaration of Conformity
-
Firmware