Harmony Timer Relays Modular timing relay 8A, 1CO, 1s..100h, on delay, 24V DC / 24...240V AC/DC

Home ProductsIndustrialHarmonyModular timing relay

Harmony Timer Relays Modular timing relay 8A, 1CO, 1s..100h, on delay, 24V DC / 24...240V AC/DC

Item Number: RE17RAMU

Datasheet

Product Dimensions

Width icon

Width17.5 mm

Height icon

Height90 mm

Depth icon

Depth72 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Timer Relays

Product or component type

modular timing relay

Physical

Width

17.5 mm

Connections - terminals

screw connectors

[in] rated current

5 A

Height

90 mm

Depth

72 mm

Control type

selector switch front panel

Connections - terminals

  • screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Insulation resistance

100 MOhm at 500 V DC conforming to IEC 60664-1

Electrical durability

100000 cycles (8 A at 250 V AC maximum) for resistive load

Mechanical durability

10000000 cycles

Marking

CE

Mounting position

any position in relation to normal vertical mounting plane

Mounting support

35 mm DIN rail conforming to IEC 60715

Local signalling

  • LED indicator for on steady: relay energised, no timing in progress
  • LED indicator for flashing: timing in progress 80 % ON and 20 % OFF
  • LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF

Function available

  • A- Power on-delay relay-1 C/O
  • At- Power on-delay relay w/ pause/summation (Y1)-1 C/O

Net weight

0.07 kg

Control type

without test button

Standards

  • 2006/95/EC
  • 2004/108/EC
  • IEC 61812-1
  • IEC 61000-6-3
  • IEC 61000-6-1
  • IEC 61000-6-4
  • IEC 61000-6-2

Product certifications

  • CSA
  • cULus
  • GL

Ambient air temperature for storage

-30...60 °C

Ambient air temperature for operation

-20...60 °C

Ip degree of protection

  • IP20 (terminal block) conforming to IEC 60529
  • IP40 (housing) conforming to IEC 60529
  • IP50 (front panel) conforming to IEC 60529

Relative humidity

93 % without condensation conforming to IEC 60068...2-30

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP121117EN

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Reach regulation

Reference contains Substances of Very High Concern above the threshold

China rohs regulation

X

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Material

Contacts material

cadmium free

Others

Legacy weee scope

Out

Package 3 bare product quantity

640

Average percentage of recycled plastic content

0 %

Package 2 bare product quantity

40

At least in Europe

Weee label

No

Package 1 bare product quantity

1

Discrete output type

relay

Device short name

RE17R

Time delay type

power on-delay

Time delay range

  • 1...10 min
  • 10...100 h
  • 0.1...1 s
  • 6...60 s
  • 6...60 min
  • 1...10 s
  • 1...10 h

Nominal output current

8 A

[uc] control circuit voltage

  • 24 V
  • 24...240 V

Output type

relay

Contacts type and composition

1 C/O

[us] rated supply voltage

  • 24...240 V AC 50/60 Hz
  • 24 V DC

Voltage range

0.85...1.1 Us

Supply frequency

50...60 Hz +/- 5 %

Input voltage

10 V

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing

Repeat accuracy

+/- 0.5 % conforming to IEC 61812-1

Temperature drift

+/- 0.05 %/°C

Voltage drift

+/- 0.2 %/V

Setting accuracy of time delay

+/- 10 % of full scale at 25 °C conforming to IEC 61812-1

Time delay type

  • power on-delay - A- Power on-delay relay
  • power on-delay - At- Power on-delay relay w/ pause/summation (Y1)

Impulse duration

  • 100 ms with load in parallel typical
  • 30 ms typical

Reset time

120 ms on de-energisation typical

On-load factor

100 %

Power consumption in va

0...32 VA at 240 V AC

Maximum power consumption in w

0.6 W at 24 V DC

Minimum switching current

10 mA at 5 V DC

Maximum switching current

8 A AC/DC

Maximum switching voltage

250 V AC

Breaking capacity

2000 VA

Operating rate in hz

10 Hz

Dielectric strength

2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1

[uimp] rated impulse withstand voltage

5 kV during 1.2/50 µs

Maximum delay response

100 ms

Creepage distance

4 kV/3 conforming to IEC 60664-1

Safety reliability data

  • B10d = 270000
  • MTTFd = 296.8 years

Number of functions

2

Time delay type

A, At

Functionality

on-delay timing

Compatibility code

RE17

Immunity to microbreaks

20 ms

Vibration resistance

20 m/s² (f= 10-150 Hz) conforming to IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to IEC 60068-2-27

Electromagnetic compatibility

  • electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2
  • electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2
  • susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3
  • electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4
  • electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4
  • 1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5
  • 1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5
  • conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6
  • voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11
  • voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11
  • conducted and radiated emissions: , class B, conforming to EN 55022

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

2.400 cm

Package 1 width

7.800 cm

Package 1 length

9.900 cm

Package 1 weight

81.000 g

Unit type of package 2

S02

Number of units in package 2

40

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

3.670 kg

Unit type of package 3

P06

Number of units in package 3

640

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

65.060 kg

Total lifecycle carbon footprint

14 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

1.519944854210636

Carbon footprint of the manufacturing phase [a1 to a3]

2 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.05861637562945304

Carbon footprint of the distribution phase [a4]

0.1 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.0005583301512003458

Carbon footprint of the installation phase [a5]

0 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

12.73720034888232

Carbon footprint of the use phase [b2, b3, b4, b6]

13 kg CO2 eq.

Sustainable packaging

Yes

Carbon footprint of the end-of-life phase [c1 to c4]

0.1751479806231869

Carbon footprint of the end-of-life phase [c1 to c4]

0.2 kg CO2 eq.

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

14.491467889496796

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

Scip number

7bdc2711-0ad2-427c-8ece-532c5e9f09d7

End of life manual availability

ENVEOLI121113EN

Take-back

No

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Installation Instruction

  • Technical illustration

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.