Harmony Control Relays Modular frequency Control Relay 5A, 1CO+1CO, 120…277V AC

Home ProductsIndustrialHarmonyModular frequency Control Relay

Harmony Control Relays Modular frequency Control Relay 5A, 1CO+1CO, 120…277V AC

Item Number: RM35HZ21FM

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

frequency control relay

Warranty

18 months

Physical

Connections - terminals

screw connectors

[in] rated current

5 A

Width

35 mm

Marking

  • CE : 73/23/EEC
  • CE : EMC 89/336/EEC

Insulation resistance

  • > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
  • > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
  • > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
  • > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1

Connections - terminals

  • screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Control type

without test button

Standards

  • IEC 60255-6
  • NF EN 60255-6

Product certifications

  • GL
  • UL
  • CSA
  • C-Tick
  • GOST

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

Ip degree of protection

  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529

Mercury free

Yes

Environmental disclosure

ENVPEP1601004EN

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Reach regulation

Reference contains Substances of Very High Concern above the threshold

China rohs regulation

X

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Material

Contacts material

cadmium free

Others

Package 1 bare product quantity

1

Legacy weee scope

Out

Package 2 bare product quantity

48

Weee label

No

Average percentage of recycled plastic content

0 %

At least in Europe

Relay type

frequency control relays

Relay name

RM35HZ21FM

Relay monitored parameters

overfrequency and underfrequency 50 or 60 Hz

Time delay type

adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault

Switching capacity in va

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum power consumption in va

6 VA AC

Measurement range

40...70 Hz

Utilisation category

  • AC-12 conforming to IEC 60947-5-1
  • AC-13 conforming to IEC 60947-5-1
  • AC-14 conforming to IEC 60947-5-1
  • AC-15 conforming to IEC 60947-5-1
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1
  • DC-14 conforming to IEC 60947-5-1

[uc] control circuit voltage

120...277 V

Contacts type and composition

2 C/O

Reset time

2000 ms time delay

Maximum switching voltage

250 V AC/DC

[us] rated supply voltage

120...277 V AC

[us] rated supply voltage

120...277 V AC, non self-powered

Supply voltage limits

102...308 V AC

Control circuit frequency

40...70 Hz

Output contacts

1 C/O + 1 C/O

Nominal output current

5 A

Input frequency

70 Hz

Maximum measuring cycle

200 ms measurement cycle as true rms value

Run-up delay at power-up

0.5 s

Hysteresis

0.3...0.3 % fixed

Measurement accuracy

  • +/- 10 % of the full scale value in input
  • +/- 10 % of the full scale value in time delay

Repeat accuracy

  • +/- 0.5 % for input and measurement circuit
  • +/- 0.5 % for time delay

Measurement error

  • +/- 0.05 %/°C with temperature variation
  • < +/- 1 % over the whole range with voltage variation

Threshold setting

  • -2...10 Hz
  • -10...2 Hz

Overvoltage category

III conforming to IEC 60664-1

[ui] rated insulation voltage

400 V conforming to IEC 60664-1

Control circuit voltage limits

- 15 % + 10 % Un

Supply frequency

50/60 Hz +/- 10 %

Insulation

no galvanic insulation between supply and measurement

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Status led

  • 1 LED green for power ON
  • 1 LED yellow for correct frequency (high R1)
  • 1 LED yellow for correct frequency (low R2)

Operating rate

<= 360 operations/hour full load

Compatibility code

RM3

Immunity to microbreaks

10 ms

Electromagnetic compatibility

  • emission standard for industrial environments conforming to IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
  • immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Vibration resistance

  • 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
  • 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1

Shock resistance

15 gn for 11 ms conforming to IEC 60255-21-1

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

2 kV AC 50 Hz

Non-dissipating shock wave

4 kV

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.600 cm

Package 1 width

8.000 cm

Package 1 length

9.700 cm

Package 1 weight

126.000 g

Unit type of package 2

S03

Number of units in package 2

48

Package 2 height

30.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

6.838 kg

Green premium status for reporting

Green Premium product

Total lifecycle carbon footprint

36 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

8.417139325189062

Carbon footprint of the manufacturing phase [a1 to a3]

8 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.01634580424665503

Carbon footprint of the distribution phase [a4]

0 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.04055864601512507

Carbon footprint of the installation phase [a5]

0 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

26.8064

Carbon footprint of the use phase [b2, b3, b4, b6]

27 kg CO2 eq.

Sustainable packaging

Yes

Carbon footprint of the end-of-life phase [c1 to c4]

0.23466586678301338

Carbon footprint of the end-of-life phase [c1 to c4]

0.2 kg CO2 eq.

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

35.51510964223385

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

End of life manual availability

ENVEOLI1601004EN

Take-back

No

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Application Notes

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.