TeSys D reversing contactor-3P-AC3 440V 65A 48-130V ACDC coil
LC2D65AEHE
TeSys D reversing contactor-3P-AC3 440V 65A 48-130V ACDC coil
LC2D65AEHE

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 65A, 48 - 130V ACDC Coil

Catalogue Number: LC2D65AEHE
TeSys D reversing contactor-3P-AC3 440V 65A 48-130V ACDC coil
LC2D65AEHE
TeSys D reversing contactor-3P-AC3 440V 65A 48-130V ACDC coil
LC2D65AEHE
Retail
$5,636.94
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
reversing contactor
Device short name
LC2D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-1
    • AC-3
      • Device presentation
        preassembled with reversing power busbar
        Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 80 A (at <60 °C) at <= 440 V AC-1 for power circuit
      • 65 A (at <60 °C) at <= 440 V AC-3 for power circuit
        • Motor power kW
        • 18.5 kW at 220...230 V AC 50 Hz
        • 30 kW at 380...400 V AC 50 Hz
        • 37 kW at 415 V AC 50 Hz
        • 37 kW at 440 V AC 50 Hz
        • 37 kW at 500 V AC 50 Hz
        • 37 kW at 660...690 V AC 50 Hz
          • Motor power hp
          • 5 hp at 115 V AC 60 Hz for 1 phase motors
          • 10 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 20 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 20 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 40 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 50 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
            • AC at 50/60 Hz AC/DC electronic
            • DC AC/DC electronic
              • [Uc] control circuit voltage
              • 48...130 V AC 50/60 Hz
              • 48...130 V DC
                • Auxiliary contact composition
                  1 NO + 1 NC
                  [Uimp] rated impulse withstand voltage
                  6 kV conforming to IEC 60947
                  Overvoltage category
                  III
                  [Ith] conventional free air thermal current
                • 10 A (at 60 °C) for signalling circuit
                • 80 A (at 60 °C) for power circuit
                  • Irms rated making capacity
                  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • 1000 A at 440 V for power circuit conforming to IEC 60947
                    • Rated breaking capacity
                      1000 A at 440 V for power circuit conforming to IEC 60947
                      [Icw] rated short-time withstand current
                    • 100 A - 1 s for signalling circuit
                    • 120 A - 500 ms for signalling circuit
                    • 140 A - 100 ms for signalling circuit
                    • 520 A 40 °C - 10 s for power circuit
                    • 900 A 40 °C - 1 s for power circuit
                    • 110 A 40 °C - 10 min for power circuit
                    • 260 A 40 °C - 1 min for power circuit
                      • Associated fuse rating
                      • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                      • 125 A gG at <= 690 V coordination type 1 for power circuit
                      • 125 A gG at <= 690 V coordination type 2 for power circuit
                        • Average impedance
                          1.5 mOhm - Ith 80 A 50 Hz for power circuit
                          [Ui] rated insulation voltage
                        • power circuit: 690 V conforming to IEC 60947-4-1
                        • signalling circuit: 690 V conforming to IEC 60947-1
                          • Electrical durability
                          • 1.8 Mcycles 57 A AC-3 at Ue <= 440 V
                          • 0.5 Mcycles 80 A AC-1 at Ue <= 440 V
                            • Power dissipation per pole
                            • 9.6 W AC-1
                            • 6.3 W AC-3
                              • Protective cover
                                with
                                Interlocking type
                                mechanical
                                Mounting support
                              • rail
                              • plate
                                • Standards
                                • EN/IEC 60947-4-1
                                • EN/IEC 60947-5-1
                                • UL 60947-4-1
                                • CSA C22.2 No 60947-4-1
                                  • Product certifications
                                  • CCC
                                  • CSA
                                  • EAC
                                  • UL
                                  • KC
                                  • DNV-GL
                                  • LROS (Lloyds register of shipping)
                                    • Connections - terminals
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
                                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
                                      • Tightening torque
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                      • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                        • Operating time
                                        • 55...65 ms closing
                                        • 20...120 ms opening (date code >= 17221)
                                        • 20...80 ms opening (date code >= 18011)
                                          • Safety reliability level
                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Mechanical durability
                                              6 Mcycles
                                              Maximum operating rate
                                              3600 cyc/h 60 °C
                                              Coil technology
                                              built-in bidirectional peak limiting
                                              Inrush power in VA
                                              23-23 VA 50/60 Hz (at 20 °C)
                                              Inrush power in W
                                              19-19 W at 20 °C
                                              Hold-in power consumption in VA
                                              1.4-1.4 VA (at 20 °C) 50/60 Hz
                                              Hold-in power consumption in W
                                              0.9-0.9 W at 20 °C
                                              Heat dissipation
                                              0.9-0.9 W at 50/60 Hz
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Compatibility code
                                                  LC2D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Operating altitude
                                                  3000 m without derating
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Height
                                                    122 mm
                                                    Width
                                                    119 mm
                                                    Depth
                                                    120 mm
                                                    Net weight
                                                    2.174 kg
                                                    Unit Type of Package 1
                                                    PCE
                                                    Number of Units in Package 1
                                                    1
                                                    Package 1 Weight
                                                    2.291 kg
                                                    Package 1 Height
                                                    14 cm
                                                    Package 1 width
                                                    16.2 cm
                                                    Package 1 Length
                                                    19.8 cm
                                                    Unit Type of Package 2
                                                    S03
                                                    Number of Units in Package 2
                                                    4
                                                    Package 2 Weight
                                                    9.877 kg
                                                    Package 2 Height
                                                    30 cm
                                                    Package 2 width
                                                    30 cm
                                                    Package 2 Length
                                                    40 cm
                                                    Sustainable offer status
                                                    Green Premium product
                                                    EU RoHS Directive
                                                    Compliant
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    Product out of China RoHS scope. Substance declaration for your information
                                                    Environmental Disclosure
                                                    ENVPEP1607010EN
                                                    Circularity Profile
                                                    ENVEOLI1607010EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    Halogen content performance
                                                    Halogen free plastic parts & cables product
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • CAD Files and Packs

                                                    • Technical Data Catalogues

                                                    • Product Environmental

                                                    • End of Life Manual

                                                    • Installation Instruction

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                                    The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                                    see data sheets for comparrisons...
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                                    User-added image.................User-added image

                                                    What is the part code for the contactor and overload that replaced the LR1D63359

                                                     The part codes are LC1D65A***  +  LRD365

                                                    What is the replacement code for the LC1D633Q?

                                                    The new code for this is LC1D65AU7.

                                                    Do the Everlink reversing contactors come with electrical interlocking?

                                                    Issue:
                                                    Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                    Product line:
                                                    Tesys D LC1D40A, LC1D50A, LC1D65A

                                                    Environment:
                                                    Everlink, all voltage codes

                                                    Cause:
                                                    Old D2 version offered an electrical interlock kit

                                                    Resolution:
                                                    The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                    What overload can be used with an LC1D65AU7?

                                                    You can use the Everlink range which is LRD313 - LRD365

                                                    How many wires can you install on the Power poles for the LC1D65A contactor?

                                                     Issue:
                                                    How many wires can you install on the Power poles for the LC1D65A contactor?

                                                    Product line:
                                                    Tesys D, Everlink

                                                    Environment:
                                                    LC1D40A LC1D50A LC1D65A

                                                    Cause:
                                                    Documentation not found

                                                    Resolution:
                                                    The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

                                                    Instruction bulletin attached.

                                                    What is the color scheme of the Tesys D-Line contactors?

                                                    Issue:
                                                    Looking for different color scheme of the Tesys D-Line contactors.

                                                    Product Line:
                                                    Tesys D Contactors

                                                    Environment:
                                                    LC1D contactors

                                                    Resolution:
                                                    Beige and dark gray.
                                                     

                                                    Does LC1D65AB7 3P (3 NO) TeSys Model D contactor have a normally opened and normally closed auxiliary contact?

                                                    What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                                    17-25 Amps = LRD325
                                                    23-32 Amps =LRD332

                                                    Are the D-Line contactors rated to break DC voltages?

                                                    Issue: 
                                                    Can the TeSys D line be used to control DC loads? 

                                                    Product Line:
                                                    Tesys D contactors

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     DC power circuit
                                                     
                                                    Resolution:
                                                     
                                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                    Devices are suitable but not UL Listed for DC applications.

                                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                     

                                                    What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                    Issue:
                                                    Tesys D SCCR

                                                    Product Line:
                                                    Contactors and Overload Relays

                                                    Environment:
                                                    TeSys™ D Contactors and Overload Relays
                                                     
                                                    Resolution:
                                                    The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                    They are as follows:
                                                    Horsepower SCCR (A)

                                                    0 thru 1 1,000
                                                    1 thru 50 5,000
                                                    51 thru 200 10,000
                                                    201 thru 400 18,000
                                                    401 thru 600 30,000
                                                    601 thru 900 42,000
                                                    901 thru 1600 85,000
                                                    1601+ 100,000