Key Features & Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-1
    • AC-3
    • AC-4
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 16 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
        • 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
          • Motor power kW
          • 3 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 5.5 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 5.5 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 7.5 kW at 500 V AC 50/60 Hz (AC-3)
          • 7.5 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 3.7 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                AC at 50/60 Hz
                [Uc] control circuit voltage
                240 V AC 50/60 Hz
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 16 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 250 A at 440 V for power circuit conforming to IEC 60947
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • Rated breaking capacity
                    250 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 105 A 40 °C - 10 s for power circuit
                  • 210 A 40 °C - 1 s for power circuit
                  • 30 A 40 °C - 10 min for power circuit
                  • 61 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 40 A gG at <= 690 V coordination type 1 for power circuit
                    • 25 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2.5 mOhm - Ith 16 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 2 Mcycles 12 A AC-3 at Ue <= 440 V
                        • 0.8 Mcycles 25 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 0.36 W AC-3
                          • 1.56 W AC-1
                            • Protective cover
                              with
                              Mounting support
                            • rail
                            • plate
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • LROS (Lloyds register of shipping)
                                • BV
                                • CCC
                                • GOST
                                • CSA
                                • RINA
                                • UL
                                • GL
                                • DNV
                                  • Connections - terminals
                                  • power circuit: spring terminals 1 cable(s) 2.5-2.5 mm²flexible without cable end
                                  • power circuit: spring terminals 2 cable(s) 2.5-2.5 mm²flexible without cable end
                                  • control circuit: spring terminals 1 cable(s) 2.5-2.5 mm²flexible without cable end
                                  • control circuit: spring terminals 2 cable(s) 2.5-2.5 mm²flexible without cable end
                                    • Operating time
                                    • 12...22 ms closing
                                    • 4...19 ms opening
                                      • Safety reliability level
                                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                        • Mechanical durability
                                          15 Mcycles
                                          Maximum operating rate
                                          3600 cyc/h 60 °C
                                          Coil technology
                                          without built-in suppressor module
                                          Control circuit voltage limits
                                        • drop-out: 0.3...0.6 Uc AC 50/60 Hz (at 60 °C)
                                        • operational: 0.8...1.1 Uc AC 50 Hz (at 60 °C)
                                        • operational: 0.85...1.1 Uc AC 60 Hz (at 60 °C)
                                          • Inrush power in VA
                                          • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
                                          • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
                                            • Hold-in power consumption in VA
                                            • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
                                            • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
                                              • Heat dissipation
                                                2-3 W at 50/60 Hz
                                                Auxiliary contacts type
                                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                • Signalling circuit frequency
                                                  25...400 Hz
                                                  Minimum switching current
                                                  5 mA for signalling circuit
                                                  Minimum switching voltage
                                                  17 V for signalling circuit
                                                  Non-overlap time
                                                • 1.5 ms on de-energisation between NC and NO contact
                                                • 1.5 ms on energisation between NC and NO contact
                                                  • Insulation resistance
                                                    > 10 MOhm for signalling circuit
                                                    Contact compatibility
                                                    M2
                                                    Compatibility code
                                                    LC1D
                                                    IP degree of protection
                                                    IP20 front face conforming to IEC 60529
                                                    Protective treatment
                                                    TH conforming to IEC 60068-2-30
                                                    Pollution degree
                                                    3
                                                    Ambient air temperature for operation
                                                    -5-60 °C
                                                    Ambient air temperature for storage
                                                    -60-80 °C
                                                    Permissible ambient air temperature around the device
                                                    -40-70 °C at Uc
                                                    Operating altitude
                                                    3000 m without
                                                    Fire resistance
                                                    850 °C conforming to IEC 60695-2-1
                                                    Flame retardance
                                                    V1 conforming to UL 94
                                                    Mechanical robustness
                                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                  • shocks contactor open: 10 Gn for 11 ms
                                                  • shocks contactor closed: 15 Gn for 11 ms
                                                    • Height
                                                      99 mm
                                                      Width
                                                      45 mm
                                                      Depth
                                                      86 mm
                                                      Net weight
                                                      0.325 kg
                                                      Sustainable offer status
                                                      Green Premium product
                                                      REACh Regulation
                                                      Reference contains Substances of Very High Concern above the threshold
                                                      REACh free of SVHC
                                                      Yes
                                                      EU RoHS Directive
                                                      Pro-active compliance (Product out of EU RoHS legal scope)
                                                      Toxic heavy metal free
                                                      Yes
                                                      Mercury free
                                                      Yes
                                                      RoHS exemption information
                                                      Yes
                                                      China RoHS Regulation
                                                      X
                                                      Environmental Disclosure
                                                      ENVPEP1501004EN
                                                      Circularity Profile
                                                      ENVEOLI1501004EN
                                                      WEEE
                                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                      CALIFORNIA PROPOSITION 65
                                                      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.p65warnings.ca.gov
                                                      Warranty
                                                      18 months

                                                      Documents & downloads

                                                      hide show
                                                      Filter items
                                                      • All

                                                      • CAD Files and Packs

                                                      • Product Brochures

                                                      • Movies

                                                      • Technical Data Catalogues

                                                      • Catalog Page

                                                      • Technical Leaflet

                                                      • End of Life Manual

                                                      • Data Bulletin

                                                      • Installation Instruction

                                                      • Product Environmental

                                                      • Handout

                                                      • Operating Manuals

                                                      • Application Solutions

                                                      • Certificates (MSDS)

                                                      • Declaration of Conformity

                                                      • White Paper

                                                      • eTechPub

                                                      • Marine Certificate

                                                      • Software - Released