Red rotary handle & yellow front plate GVAPR54 for TeSys GV2, TeSys GV3, TeSys U starter-controller with error status, IP54

TeSys GV2 & TeSys GV3 & TeSys U, Rotary Handle, IP54

Catalogue Number: GVAPR54
Red rotary handle & yellow front plate GVAPR54 for TeSys GV2, TeSys GV3, TeSys U starter-controller with error status, IP54
Retail
$166.68
RRP (Inc. GST)

Specifications

hide show
Range of product
  • TeSys GV2
  • TeSys U
  • TeSys GV3
    • Range
      TeSys
      Device short name
      GVAP
      Product or component type
      rotary handle
      Accessory / separate part category
      control accessory
      Handle colour
      red
      Handle front plate colour
      yellow
      Range compatibility
    • TeSys GV2
    • TeSys GV3
    • TeSys U
      • Rotary handle padlocking
        padlock in OFF position
        Rotary handle mounting style
        direct
        Locking options description
        1 to 3 padlocks
        Height
        43 mm
        Width
        60 mm
        Depth
        60 mm
        Net weight
        0.15 kg
        Compatibility code
        GVAP
        IP degree of protection
        IP54
        Package 1 Weight
        0.18 kg
        Package 1 Height
        0.65 dm
        Package 1 width
        0.9 dm
        Package 1 Length
        1.35 dm
        Sustainable offer status
        Green Premium product
        EU RoHS Directive
        Compliant
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
        Product out of China RoHS scope. Substance declaration for your information
        Environmental Disclosure
        ENVPEP111252EN
        WEEE
        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Installation Instruction

        • eTechPub

        Frequently Asked Questions

        hide show

        What does Pitch refer to in regards to the GV2G busbar system?

        Issue: 
        Need to know what 45mm, 54mm, and 72mm pitch means

        Product Line:
        GV2 Manual Starters

        Environment:
        n/a

        Resolution:
        The pitch is the spacing between slots.  In order to select the correct pitch, total up the width of the device, plus any side mounted auxiliaries.  Use the total width for selecting the proper pitch. The busbar pitch selection must be the same or greater than the sum of device and auxiliaries.

        GV2P disconnect options

        Issue:
        What is the product number for a complete through-the-door disconnect device for a GV2P

        Product Line:
        GV2P Manual Starters and Protectors

        Environment:
        US product

        Cause:
        Digest 176 is unclear as to what is a complete mechanism with shaft and handle

        Resolution:
        There are three devices which include mechanism, shaft and handle:
        GV2APN01 has a NEMA 1, 12 rating and is black
        GV2APN02 has a NEMA 1, 12 rating and is red/yellow
        GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

        What is the length of the shaft in the GV3APN02 kit?

         The shaft included in the GV3APN02 kit is a GVAPA1. It has a length of 315 mm.
         

        What is the current rating of the GV1G02?

        Issue:
        GV1G02 electrical ratings

        Product Line:
        GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection

        Environment:
        Additional GV2 Wiring Accessories

        Resolution:
        25 amp maximum

        What is the short circuit current rating for TeSys GV2G Comb Busbar.

        The short-circuit current withstand rating (KA) of Tesys Comb Busbar is compatible with the breaking capacity of Motor Protection Circuit Breakers (MPCB) of GV series. The GV Series Comb Busbar does not have a conditional short-circuit current rating.

        The maximum permissible peak current for GV2G*** Series Comb Busbar is 11KA and for GV3G*64 series Comb Busbar is 20KA.

        Example: Use a circuit breaker or fuse in upstream of the Tesys GV2G for a short circuit value up to 11KAmps as the permissible peak current of GV2G354 is 11KA.

        Is there a through the door operating mechanism for the GV3P manual starters?

        Issue: 
        Is there a through the door operating mechanism for the GV3P manual starters?

        Product Line:
        IEC Contactors and Starters

        Environment:
        GV3P Manual Starters and Protectors

        Cause:
        Product selection/feature
         
        Resolution:
        There are three different through the door operating mechanisms for the GV3P. There is the GV3APN01 which is rated
        NEMA 1 and 12 in black with trip indication; the GV3APN02 which is also NEMA 1 and 12 in red/yellow with trip indication,
        and the GV3APN04 which is NEMA 4/X red/yellow without trip indication.
         

        Is there a thru the door external operator for the GV2ME and GV2P manual starters?

        Issue:
        What is the through-the-door operating mechanism for a GV2 Manual starter?

        Product Line: 
        Digest 177 Section 18 : Contactors and Starters - IEC

        Environment:
        North American Products

        Cause:
        Needs  the through-the-door operating mechanism for a GV2P Manual starter

        Resolution:
        There are no available kits for the GV2ME devices, only the GV2P devices (as listed below)
        GV2APN01 - Nema 1 Black
        GV2APN02 - Nema 1, 12 Red/Yellow
        GV2APN04 - Nema 3R, 4, 4X Red/Yellow