Specifications

hide show
Range
TeSys
Product name
TeSys GV4
Device short name
GV4L
Product or component type
circuit breaker
Device application
motor protection
Poles description
3P
Utilisation category
category A
Trip unit technology
  • magnetic
  • electronic
    • Protection type
      short-circuit
      [In] rated current
      115 A
      Breaking capacity
    • Icu 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
    • Icu 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
    • Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    • Icu 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
      • [Ics] rated service breaking capacity
      • 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
      • 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
      • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
      • 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • Trip unit rating
          690-1610 A
          Control type
          rotary handle
          [Ue] rated operational voltage
          690 V AC 50/60 Hz conforming to IEC 60947-2
          Motor power kW
        • 37-37 kW at 400...415 V AC 50/60 Hz
        • 45-45 kW at 400...415 V AC 50/60 Hz
        • 55-55 kW at 400...415 V AC 50/60 Hz
        • 45-45 kW at 500 V AC 50/60 Hz
        • 55-55 kW at 500 V AC 50/60 Hz
        • 75-75 kW at 500 V AC 50/60 Hz
        • 75-75 kW at 660...690 V AC 50/60 Hz
        • 90-90 kW at 660...690 V AC 50/60 Hz
        • 110-110 kW at 660...690 V AC 50/60 Hz
          • [Uimp] rated impulse withstand voltage
            [Ui] rated insulation voltage
            800 V conforming to IEC 60947-2
            Mounting mode
          • by clips
          • by screws
            • Mounting support
            • plate
            • 75 mm symmetrical DIN rail
            • 35 mm symmetrical DIN rail
              • Suitability for isolation
                yes conforming to IEC 60947-1
                Mechanical durability
                40000 cycles
                Electrical durability
              • 10000 cycles for AC-3 at 440 V In/2
              • 5000 cycles for AC-3 at 440 V In
                • Local signalling
                  green indicatorpresence of auxiliary contacts:
                  Number of slots
                • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                  • Rotary handle padlocking
                    padlock in OFF or ON position
                    Connection pitch
                    27 mm
                    Connections - terminals
                    lugs-ring terminals
                    Tightening torque
                  • 9-9 N.m for 16-95 mm²
                  • 5-5 N.m for 1.5-10 mm²
                    • Quality labels
                      CE
                      Standards
                    • EN/IEC 60947-2
                    • EN/IEC 60947-4-1
                      • Height
                        155 mm
                        Width
                        81 mm
                        Depth
                        165 mm
                        Net weight
                        1.65 kg
                        Product certifications
                      • IEC
                      • CCC
                      • EAC
                      • EU-RO MR
                        • Tropicalisation
                          2 conforming to IEC 68-2
                          IP degree of protection
                          IP40 front face conforming to IEC 60529
                          IK degree of protection
                          IK07 conforming to IEC 62262
                          Pollution degree
                          3 conforming to IEC 60947-1
                          Mechanical robustness
                        • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                        • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                        • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                          • Ambient air temperature for operation
                            -25-70 °C
                            Ambient air temperature for storage
                            -50-85 °C
                            Operating altitude
                          • 0...2000 m without derating
                          • 2000...5000 m with derating
                            • Sustainable offer status
                              Green Premium product
                              EU RoHS Directive
                              Compliant
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              Product out of China RoHS scope. Substance declaration for your information
                              Environmental Disclosure
                              ENVPEP1704004EN
                              Circularity Profile
                              ENVEOLI1704004EN
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • CAD Files and Packs

                              • Product Brochures

                              • Movies

                              • Technical Data Catalogues

                              • Technical Leaflet

                              • Installation Instruction

                              • Product Environmental

                              • End of Life Manual

                              • Operating Manuals

                              • eTechPub

                              • White Paper

                              • Certificates (MSDS)

                              • Declaration of Conformity

                              • Marine Certificate

                              Frequently Asked Questions

                              hide show

                              What is the recommended circuit breaker for the ATV31CU22M2 IP54 rated drive?

                              Issue:
                              What is the recommended circuit breaker for the ATV31CU22M2 IP54 rated drive?

                              Product Line:
                              Altivar ATV31C

                              Environment:
                              All

                              Cause:
                              Wants to use a circuit breaker on the ATV31CU22M2 drive.

                              Resolution:
                              Recommended breakers for the ATV31C........ M2 units are

                              ATV31C018M2=  GV2L08
                              ATV31C037M2=  GV2L10
                              ATV31C055M2=  GV2L14
                              ATV31C075M2=  GV2L14
                              ATV31CU11M2=  GV2L16
                              ATV31CU15M2=  GV2L20
                              ATV31CU22M2=  GV2L22
                               

                              What is the part code for a contact block for GV3P40 n/o n/c to fit the left side of the Motor Starter?

                              The Part code is GVAN11
                              See link for data sheet:
                              https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=GVAN11

                              What is the part number to get 2 extra N/C auxillary contacts on to a GV Motor C/B?

                              The part numbers to get 2 extra N/C auxillary contacts on to a GV Motor C/B are - GVAE11 & GVAN11
                              For further information , visit links below:-
                              https://www.schneider-electric.com.au/en/search/GVAE11
                              https://www.schneider-electric.com.au/en/search/GVAN11
                               

                              What is the part number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B ,GV2ME08?

                              The part  number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B , GV2ME08 is - GVAN11
                              For further information , visit link below:-
                              https://www.schneider-electric.com.au/en/search/GVAN11
                              User-added image

                              Will the Compact NSX breaker be for sale in the USA or Canada?

                              Issue:
                              Where can I buy a Compact NSX breaker?

                              Product Line:
                              Circuit Breakers

                              Cause:
                              This breaker is popular overseas and there is interest in the US

                              Resolution:
                              There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                              If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                              For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                              https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum power voltage of an LC1D contactor

                              Product Line:
                              Digest 177 Section 18: IEC Contactors

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying ratings per UL and CSA

                              Resolution:
                              It is 600Vac.