Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2RT
Product or component type
circuit breaker
Device application
motor
Trip unit technology
thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
  • AC-3 conforming to IEC 60947-4-1
  • category A conforming to IEC 60947-2
    • Network frequency
      50/60 Hz conforming to IEC 60947-4-1
      Fixing mode
    • 35 mm symmetrical DIN rail: clipped
    • panel: screwed (with adaptor plate)
      • Operating position
        any position
        Motor power kW
      • 5.5-5.5 kW at 220/230 V AC 50/60 Hz motor protection high peak current
      • 9-9 kW at 400/415 V AC 50/60 Hz motor protection high peak current
      • 11-11 kW at 400/415 V AC 50/60 Hz motor protection high peak current
      • 11-11 kW at 440 V AC 50/60 Hz motor protection high peak current
      • 11-11 kW at 500 V AC 50/60 Hz motor protection high peak current
      • 18.5-18.5 kW at 690 V AC 50/60 Hz motor protection high peak current
        • Breaking capacity
        • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
        • 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
        • 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 50 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
          • Control type
            toggle
            [In] rated current
            23 A
            Trip unit rating
            17-23 A
            Magnetic tripping current
            400-400 A
            [Ue] rated operational voltage
            690 V AC 50/60 Hz conforming to IEC 60947-2
            [Ui] rated insulation voltage
            690 V AC 50/60 Hz conforming to IEC 60947-2
            [Ith] conventional free air thermal current
            23 A conforming to IEC 60947-4-1
            [Uimp] rated impulse withstand voltage
            Power dissipation per pole
            2.5 W
            Mechanical durability
            100000 cycles
            Electrical durability
            100000 cycles for AC-3 at 440 V
            Maximum operating rate
            25 cyc/h
            Rated duty
            continuous conforming to IEC 60947-4-1
            Direct connector
            without
            Connections - terminals
          • screw clamp terminals 2 cable(s) 1-6 mm² solid
          • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
          • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
            • Tightening torque
              1.7 N.m on screw clamp terminals
              Suitability for isolation
              yes conforming to IEC 60947-1
              Height
              89 mm
              Width
              45 mm
              Depth
              78.5 mm
              Compatibility code
              GV2RT
              Standards
            • EN/IEC 60947-2
            • EN/IEC 60947-4-1
            • UL 60947-4-1
            • CSA C22.2 No 60947-4-1
              • Product certifications
              • IECEE CB Scheme
              • UL
              • CSA
              • CCC
              • EAC
              • BV
              • LROS (Lloyds register of shipping)
                • Protective treatment
                  TH
                  IP degree of protection
                  IP20 conforming to IEC 60529
                  IK degree of protection
                  IK04
                  Ambient air temperature for operation
                  -20-60 °C
                  Ambient air temperature for storage
                  -40-80 °C
                  Fire resistance
                  960 °C conforming to IEC 60695-2-1
                  Operating altitude
                  2000 m
                  Sustainable offer status
                  Green Premium product
                  REACh Regulation
                  Reference contains Substances of Very High Concern above the threshold
                  EU RoHS Directive
                  Compliant
                  Mercury free
                  Yes
                  RoHS exemption information
                  Yes
                  China RoHS Regulation
                  Product out of China RoHS scope. Substance declaration for your information
                  Environmental Disclosure
                  ENVPEP121004EN
                  WEEE
                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                  California proposition 65
                  WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                  Warranty
                  18 months

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Technical Data Catalogues

                  • Product Environmental

                  • Installation Instruction

                  • Data Bulletin

                  • eTechPub

                  Frequently Asked Questions

                  hide show

                  Can the GV* starters be used on 50 hertz applications?

                  Issue:
                  GV* Starter for 50/60hz application

                  Product Line:
                  Motor Starters and Protectors

                  Environment:
                  PowerPact™ Manual Starters

                  Resolution:
                  Yes, these starters are rated for 50/60 hertz.

                  This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                  Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                  Issue:
                  Mounting adaptor for GV2 and LC1D contactor

                  Product Line:
                  Motor Starters and Protectors

                  Environment:
                  TeSys GV Manual Starter and Protectors
                  Tesys D Contactors
                   
                  Resolution:
                  The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                  Are explosion proof enclosures available for GV manual motor starters.

                  Issue:
                  NEMA 7/9 rated enclosure for GV manual motor starters

                  Product Line:
                  Tesys GV Motor Starters and Protectors

                  Environment:
                  TeSys™ GV Manual Starters and Protectors

                  Resolution:
                  No hazardous duty enclosures are available for the GV product line.
                  For explosion proof applications consider the Class 2510 Type M or Type T offering.

                  Protection Rating for GV2E01

                  Issue:
                  What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                  Product Line:
                  GV2 Enclosure Accessories

                  Environment:
                  US Product

                  Cause:
                  The IP rating is not specified in the Digest 176

                  Resolution:
                  When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                  Is a padlocking device available for the GV2MC** type enclosures?

                  Issue:
                  Padlocking device for GV2MC Enclosures

                  Product Line:
                  TeSys GV2 Manual Starters and Protectors

                  Environment:
                  n/a

                  Resolution:
                  Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                  GV2P disconnect options

                  Issue:
                  What is the product number for a complete through-the-door disconnect device for a GV2P

                  Product Line:
                  GV2P Manual Starters and Protectors

                  Environment:
                  US product

                  Cause:
                  Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                  Resolution:
                  There are three devices which include mechanism, shaft and handle:
                  GV2APN01 has a NEMA 1, 12 rating and is black
                  GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                  GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                  What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                  Issue:
                  Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                  Product Line:
                  Contactors and Starters IEC

                  Environment:
                  Tesys D contactors and GV manual starters

                  Cause:
                  Spacer required

                  Resolution:
                  Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                  Do we offer a cable operated handle mechanism for the GV7 starters?

                  Issue:
                  They need to mount the GV7 back inside the enclosure and need a handle mechanism with a cable to operate. 

                  Product line:
                  Tesys GV7 manual motor controller

                  Environment:
                  all

                  Cause:
                  n/a

                  Resolution:
                  The GV7 do not offer a cable operator.  Consider switching to a Powerpact circuit breaker which offers the cable mechanism kits.

                  What is the catalog number for an external rotary handle for a GV7 manual starter ?

                  Issue:
                  GV7 Manual starter handle kit

                  Product Line:
                  Motor Starters and Protectors

                  Environment:
                  TeSys™ GV Manual Starters and Protectors

                  Resolution:
                  Use the GV7AP01 for a black handle with black legend or a GV7AP02 for a red handle with yellow legend.

                  What is the tripping class of the GV2 ME, GV2 P and GV2 RT?

                  The tripping class for GV2MExx, GV2Pxx, GV2RTxx circuit-breakers is class 10. Class 10 corresponds to a direct on-line motor starting time between 4 and 10 sec. Example of a tripping curve:




                   

                  Which enclosures can the GV2E01 sealing kit be used on?

                  Issue:
                  Which enclosures can the GV2E01 sealing kit be used on?

                  Product Line:
                  IEC Manual Starters/Protectors - GIC Product

                  Environment:
                  US Product

                  Cause:
                  Product Application

                  Resolution:
                  GV2MC01 and GV2MP01.

                  What would be the part number for an enclosure for the GV2ME20

                  Show More