Browse all
Browse all

TeSys D Contactor 3P(3 NO), AC-3/AC-3e, 0 to 440V, 25A, 230VAC 50/60Hz coil

TeSys D Contactor 3P(3 NO), AC-3/AC-3e, 0 to 440V, 25A, 230VAC 50/60Hz coil

Item Number: LC1D25P7

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height85 mm

Depth icon

Depth92 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current
  • 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability 15 Mcycles
Electrical durability
  • 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
  • 1.4 Mcycles 40 A AC-1 at Ue <= 440 V
  • 1.65 Mcycles 25 A AC-3e at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: solid without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Connections - terminals screw clamp terminals
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60947-4-1
  • IEC 60335-1:Clause 30.2
  • IEC 60335-2-40:Annex JJ
  • UL 60335-2-40:Annex JJ
  • CSA C22.2 No 60947-4-1
Product certifications
  • UL
  • CCC
  • CSA
  • Marine
  • UKCA
  • EAC
  • CB Scheme
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 85 mm
Width 45 mm
Depth 92 mm
Net weight 0.37 kg
Reach free of svhc Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1102029EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Legacy weee scope In
Package 2 bare product quantity 20
Package 3 bare product quantity 320
Average percentage of recycled plastic content 0 %
Package 1 bare product quantity 1
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • resistive load
  • motor control
Utilisation category
  • AC-3
  • AC-4
  • AC-1
  • AC-3e
Poles description 3P
[uc] control circuit voltage 230 V AC 50/60 Hz
Motor power kw
  • 5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
  • 11 kW at 380...400 V AC 50/60 Hz (AC-3)
  • 11 kW at 415...440 V AC 50/60 Hz (AC-3)
  • 15 kW at 500 V AC 50/60 Hz (AC-3)
  • 15 kW at 660...690 V AC 50/60 Hz (AC-3)
  • 5.5 kW at 400 V AC 50/60 Hz (AC-4)
  • 5.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
  • 11 kW at 380...400 V AC 50/60 Hz (AC-3e)
  • 11 kW at 415...440 V AC 50/60 Hz (AC-3e)
  • 15 kW at 500 V AC 50/60 Hz (AC-3e)
  • 15 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
  • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
  • 2 hp at 115 V AC 50/60 Hz for 1 phase motors
  • 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
  • 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 40 A (at 60 °C) for power circuit
Irms rated making capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 450 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 450 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 240 A 40 °C - 10 s for power circuit
  • 380 A 40 °C - 1 s for power circuit
  • 50 A 40 °C - 10 min for power circuit
  • 120 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 63 A gG at <= 690 V coordination type 1 for power circuit
  • 40 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm - Ith 40 A 50 Hz for power circuit
Power dissipation per pole
  • 3.2 W AC-1
  • 1.25 W AC-3
  • 1.25 W AC-3e
[ui] rated insulation voltage
  • power circuit: 690 V conforming to IEC 60947-4-1
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC at 50/60 Hz standard
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
  • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
  • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
  • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in va
  • 70 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va
  • 7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 2...3 W at 50/60 Hz
Operating time
  • 12...22 ms closing
  • 4...19 ms opening
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Contact compatibility M2
Maximum motor phase current 25 A
[uc] control circuit voltage 230 V
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor closed (15 Gn for 11 ms)
  • shocks contactor open (8 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 5.000 cm
Package 1 width 9.200 cm
Package 1 length 11.000 cm
Package 1 weight 402.000 g
Unit type of package 2 S02
Number of units in package 2 20
Package 2 height 15.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 8.320 kg
Unit type of package 3 P06
Number of units in package 3 320
Package 3 height 75.000 cm
Package 3 width 60.000 cm
Package 3 length 80.000 cm
Package 3 weight 143.500 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 127 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 2.689379557743361
Carbon footprint of the manufacturing phase [a1 to a3] 3 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.2030432791138008
Carbon footprint of the distribution phase [a4] 0.2 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 123.4211523629405
Carbon footprint of the use phase [b2, b3, b4, b6] 123 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 1.062565520235433
Carbon footprint of the end-of-life phase [c1 to c4] 1 kg CO2 eq.
Pvc free Yes
Energy efficiency optimized False
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 127.3761407200331
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
Pvc free Yes
End of life manual availability ENVEOLI110229EN
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Data Bulletin

  • Technical illustration

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.