Specifications

hide show
Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2L
Product or component type
circuit breaker
Device application
motor
Poles description
3P
Network type
AC
Utilisation category
  • category A conforming to IEC 60947-2
  • AC-3 conforming to IEC 60947-4-1
    • Network frequency
      50/60 Hz conforming to IEC 60947-2
      Breaking capacity
    • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
    • 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
    • 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    • 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    • 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
      • [Ics] rated service short-circuit breaking capacity
      • 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
      • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
      • 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
      • 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
      • 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
        • Trip unit technology
          magnetic
          Magnetic tripping current
          170-170 A
          Fixing mode
        • 35 mm symmetrical DIN rail: clipped
        • panel: screwed (with 2 x M4 screws)
          • Operating position
            any position
            Motor power kW
          • 5.5-5.5 kW at 400/415 V AC 50/60 Hz
          • 7.5-7.5 kW at 500 V AC 50/60 Hz
          • 9-9 kW at 690 V AC 50/60 Hz
          • 11-11 kW at 690 V AC 50/60 Hz
            • Control type
              rotary knob
              [In] rated current
              14 A
              [Ue] rated operational voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ui] rated insulation voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Uimp] rated impulse withstand voltage
              Power dissipation per pole
              1.8 W
              Mechanical durability
              100000 cycles
              Electrical durability
              100000 cycles for AC-3 at 415 V
              Maximum operating rate
              40 cyc/h
              Rated duty
              continuous conforming to IEC 60947-4-1
              Direct connector
              without
              Connections - terminals
            • screw clamp terminals 2 cable(s) 1-6 mm² solid
            • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
              • Tightening torque
                1.7 N.m on screw clamp terminals
                Mechanical robustness
              • shocks: 30 Gn conforming to IEC 60068-2-27
              • vibrations: 5 Gn, 5...150 Hz conforming to IEC 60068-2-6
                • Suitability for isolation
                  yes conforming to IEC 60947-1
                  Height
                  89 mm
                  Width
                  45 mm
                  Depth
                  97 mm
                  Net weight
                  0.33 kg
                  Compatibility code
                  GV2L
                  Standards
                • EN/IEC 60947-2
                • EN/IEC 60947-4-1
                • CSA C22.2 No 60947-4-1
                • UL 60947-4-1
                  • Product certifications
                  • IECEE CB Scheme
                  • UL
                  • CSA
                  • CCC
                  • EAC
                  • RINA
                  • LROS (Lloyds register of shipping)
                  • DNV-GL
                  • BV
                    • Protective treatment
                      TH
                      IP degree of protection
                      IP20 conforming to IEC 60529
                      IK degree of protection
                      IK04
                      Ambient air temperature for operation
                      -20-60 °C
                      Ambient air temperature for storage
                      -40-80 °C
                      Fire resistance
                      960 °C conforming to IEC 60695-2-1
                      Operating altitude
                      0...2000 m
                      Sustainable offer status
                      Green Premium product
                      REACh Regulation
                      Reference contains Substances of Very High Concern above the threshold
                      EU RoHS Directive
                      Compliant
                      Mercury free
                      Yes
                      RoHS exemption information
                      Yes
                      China RoHS Regulation
                      Product out of China RoHS scope. Substance declaration for your information
                      Environmental Disclosure
                      ENVPEP121004EN
                      WEEE
                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                      California proposition 65
                      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                      Warranty
                      18 months

                      Documents & downloads

                      hide show
                      Filter items
                      • All

                      • CAD Files and Packs

                      • Product Brochures

                      • Technical Data Catalogues

                      • Installation Instruction

                      • Product Environmental

                      • Data Bulletin

                      • eTechPub

                      Frequently Asked Questions

                      hide show

                      Can the GV* starters be used on 50 hertz applications?

                      Issue:
                      GV* Starter for 50/60hz application

                      Product Line:
                      Motor Starters and Protectors

                      Environment:
                      PowerPact™ Manual Starters

                      Resolution:
                      Yes, these starters are rated for 50/60 hertz.

                      This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                      GV2P disconnect options

                      Issue:
                      What is the product number for a complete through-the-door disconnect device for a GV2P

                      Product Line:
                      GV2P Manual Starters and Protectors

                      Environment:
                      US product

                      Cause:
                      Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                      Resolution:
                      There are three devices which include mechanism, shaft and handle:
                      GV2APN01 has a NEMA 1, 12 rating and is black
                      GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                      GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                      Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                      Issue:
                      Mounting adaptor for GV2 and LC1D contactor

                      Product Line:
                      Motor Starters and Protectors

                      Environment:
                      TeSys GV Manual Starter and Protectors
                      Tesys D Contactors
                       
                      Resolution:
                      The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                      Is a padlocking device available for the GV2MC** type enclosures?

                      Issue:
                      Padlocking device for GV2MC Enclosures

                      Product Line:
                      TeSys GV2 Manual Starters and Protectors

                      Environment:
                      n/a

                      Resolution:
                      Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                      Are explosion proof enclosures available for GV manual motor starters.

                      Issue:
                      NEMA 7/9 rated enclosure for GV manual motor starters

                      Product Line:
                      Tesys GV Motor Starters and Protectors

                      Environment:
                      TeSys™ GV Manual Starters and Protectors

                      Resolution:
                      No hazardous duty enclosures are available for the GV product line.
                      For explosion proof applications consider the Class 2510 Type M or Type T offering.

                      What is the part code for the Adaptor to join the GV2P16 to a LC1D09BL

                      You can use GV2AF3 or GV2AF4 + LAD31

                      What is the replacement for a GV2M06

                      Use a GV2ME06.

                      Protection Rating for GV2E01

                      Issue:
                      What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                      Product Line:
                      GV2 Enclosure Accessories

                      Environment:
                      US Product

                      Cause:
                      The IP rating is not specified in the Digest 176

                      Resolution:
                      When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                      Issue:
                      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                      Product Line:
                      Contactors and Starters IEC

                      Environment:
                      Tesys D contactors and GV manual starters

                      Cause:
                      Spacer required

                      Resolution:
                      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                      What is the operation of the GV2AD fault signalling contacts of the GV2 circuit-breakers?

                      GV2ME, GV2P, GV2L, GV2LE, GV3P and GV3L circuit-breakers can be fitted with the following optional fault indicating contact blocks:
                       

                      GVAD0110
                      GVAD0101
                      GVAD1010
                      GVAD1001

                      These blocks comprise of fault signalling contacts and instantaneous auxiliary contacts

                      GVAD0110

                      A N/O instantaneous auxiliary contact (terminals 53-54), closed when the device is energized and open when the device is de-energized

                      A N/C fault signalling contact (terminals 95-96), closed if there is no fault, open when a fault (magnetic or thermal) occurs. 

                      GVAD0101

                      A N/C instantaneous auxiliary contact (terminals 51-52), closed when the device is de-energised and open when the device is energised.

                      A N/C fault signalling contact (terminals 95-96), closed if there is no fault, open when a fault (magnetic or thermal) occurs. 

                      GVAD1010 

                      A N/O instantaneous auxiliary contact (terminals 53-54), closed when the device is energized and open when the device is de-energized.

                      A N/O fault signalling contact (terminals 97-98), open if there is no fault, closed when a fault (magnetic or thermal) occurs. 
                       

                      GVAD1001

                      A N/C instantaneous auxiliary contact (terminals 51-52), closed when the device is de-energized and open when the device is energized.

                      A N/O fault signalling contact (terminals 97-98), open if there is no fault, closed when a fault (magnetic or thermal) occurs. 
                       


                      The instantaneous auxiliary contact test is performed by creating a state of transition of the handle actuator between the de-energized position and the energized position.

                      The fault contact test is performed by pressing the test button when the handle actuator is in the closed position.