Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2

Soft-Start Stop 6A 200 480V

Catalogue Number: ATSU01N206LT
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Soft start-soft stoft unit ATS U01N2
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
Altistart U01 and TeSys U
Product or component type
soft starter
Product destination
asynchronous motors
Product specific application
simple machine
Device short name
ATSU01
Network number of phases
3 phases
[Us] rated supply voltage
200...480 V - 10...10 %
Motor power kW
  • 3 kW, 3 phases at 400 V
  • 0.75 kW, 3 phases at 230 V
  • 2.2 kW, 3 phases at 400 V
  • 1 kW, 3 phases at 230 V
  • 1.5 kW, 3 phases at 400 V
    • Motor power hp
    • 1 hp, 3 phases at 230 V
    • 2 hp, 3 phases at 460 V
    • 3 hp, 3 phases at 460 V
    • 1.5 hp, 3 phases at 230 V
      • IcL starter rating
        6 A
        Utilisation category
        AC-53B conforming to EN/IEC 60947-4-2
        Current consumption
        65 mA
        Type of start
        start with voltage ramp
        Power dissipation in W
      • 1.5 W at full load and at end of starting
      • 61.5 W in transient state
        • Assembly style
          with heat sink
          Function available
          integrated bypass
          Supply voltage limits
          180-528 V
          Supply frequency
          50...60 Hz - 5...5 %
          Network frequency
          47.5...63 Hz
          Output voltage
          <= power supply voltage
          [Uc] control circuit voltage
          24 V DC +/- 10 %
          Starting time
        • 1 s / 100
        • 5 s / 20
        • 10 s / 10
        • adjustable from 1 to 10 s
          • Deceleration time symb
            adjustable from 1 to 10 s
            Starting torque
            30...80 % of starting torque of motor connected directly on the line supply
            Discrete input type
            logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
            Discrete input voltage
            24...40 V
            Input output isolation
            galvanic between power and control
            Discrete input logic
            positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
            Discrete output current
          • 2 A DC-13
          • 3 A AC-15
            • Discrete output type
            • open collector logic LO1 end of starting signal
            • relay outputs R1A, R1C NO
              • Discrete output voltage
                24 V (voltage limits: 6...30 V) open collector logic
                Minimum switching current
                10 mA at 6 V DC for relay outputs
                Maximum switching current
              • relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
              • relay outputs: 2 A at 250 V AC AC-15 cos phi = 0.5 and L/R = 20 ms inductive load
                • Maximum switching voltage
                  440 V relay outputs
                  Display type
                • 1 LED (green) for starter powered up
                • 1 LED (yellow) for nominal voltage reached
                  • Tightening torque
                  • 1.9-2.5 N.m
                  • 0.5-0.5 N.m
                    • Electrical connection
                    • 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
                    • screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
                    • screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
                    • screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
                    • 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
                    • 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
                      • Marking
                        CE
                        Operating position
                        vertical +/- 10 degree
                        Height
                        234 mm
                        Width
                        45 mm
                        Depth
                        150 mm
                        Net weight
                        0.34 kg
                        Power range
                      • 0.55-1 kW at 200-240 V 3 phases
                      • 1.1-2 kW at 380-440 V 3 phases
                      • 2.2-3 kW
                        • Motor starter type
                          soft starter
                          Electromagnetic compatibility
                        • conducted and radiated emissions level B conforming to CISPR 11
                        • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                        • voltage/current impulse level 3 conforming to IEC 61000-4-5
                        • conducted and radiated emissions level 3 conforming to IEC 61000-4-6
                        • immunity to conducted interference caused by radio-electrical fields conforming to IEC 61000-4-11
                        • conducted and radiated emissions level B conforming to IEC 60947-4-2
                        • damped oscillating waves level 3 conforming to IEC 61000-4-12
                        • electrostatic discharge level 3 conforming to IEC 61000-4-2
                        • EMC immunity conforming to EN 50082-1
                        • EMC immunity conforming to EN 50082-2
                        • harmonics conforming to IEC 1000-3-2
                        • harmonics conforming to IEC 1000-3-4
                        • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                          • Standards
                            EN/IEC 60947-4-2
                            Product certifications
                          • CCC
                          • UL
                          • C-Tick
                          • CSA
                            • IP degree of protection
                              IP20
                              Pollution degree
                              2 conforming to EN/IEC 60947-4-2
                              Vibration resistance
                            • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                            • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                              • Shock resistance
                                15 gn for 11 ms conforming to EN/IEC 60068-2-27
                                Relative humidity
                                5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
                                Ambient air temperature for operation
                              • -10-40 °C (without)
                              • 40-50 °C (with current derating of 2 % per °C)
                                • Ambient air temperature for storage
                                  -25-70 °C conforming to EN/IEC 60947-4-2
                                  Operating altitude
                                • <= 1000 m without
                                • > 1000 m with current derating of 2.2 % per additional 100 m
                                  • REACh Regulation
                                    Free of Substances of Very High Concern above the threshold
                                    REACh free of SVHC
                                    Yes
                                    EU RoHS Directive
                                    Pro-active compliance (Product out of EU RoHS legal scope)
                                    Toxic heavy metal free
                                    Yes
                                    Mercury free
                                    Yes
                                    RoHS exemption information
                                    Yes
                                    China RoHS Regulation
                                    X
                                    Circularity Profile
                                    ENVEOLI100217EN
                                    WEEE
                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                    Warranty
                                    18 months

                                    Documents & downloads

                                    hide show
                                    Filter items
                                    • All

                                    • CAD Files and Packs

                                    • Product Brochures

                                    • Technical Data Catalogues

                                    • End of Life Manual

                                    • Installation Instruction

                                    • Handout

                                    • Product Environmental

                                    • Data Bulletin

                                    • Certificates (MSDS)

                                    • eTechPub

                                    Frequently Asked Questions

                                    hide show

                                    What are the adjustment ranges for the dials on an ATSU01N2..LT?

                                    For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                                    For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                                    CTA-ID : 2061385

                                    Does the ATS01 come with a shorting contactor?

                                    Issue:
                                    Does the ATS01 come with a shorting contactor?

                                    Product Line:
                                    Altistat 01

                                    Environment:
                                    All

                                    Cause:
                                    N/A

                                    Resolution:
                                    All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.