Browse all
Browse all

TeSys LR9 Electronic Thermal Overload Relay 3P, 22…110A

Home ProductsIndustrialTeSysElectronic Thermal Overload Relay

TeSys LR9 Electronic Thermal Overload Relay 3P, 22…110A

Item Number: LR9D110S

Datasheet

Product Dimensions

Width icon

Width65 mm

Height icon

Height107 mm

Depth icon

Depth79.9 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Product or component type electronic thermal overload relay
Product compatibility
  • LC1D50A
  • LC1D38
  • LC1D25
  • LC1D40A
  • LC1D80
  • LC1D65A
  • LC1D115
  • LC1D95
  • LC1D32

Physical

Power consumption in w 300 mW
Mounting support
  • plate
  • rail
[ue] rated operational voltage
  • 690 V for power circuit
  • 660 V for signalling circuit
Control type
  • red push-button: stop and manual reset
  • white 2 microswitches: adjustable trip class
  • red knob: automatic reset
  • white dial: full-load current adjustment
Connections - terminals
  • control circuit: screw clamp terminals 1 cable 2.5-2.5 mm² - cable stiffness: solid or flexible - without cable end
  • power circuit: screw clamp terminals 1 cable 50-50 mm² - cable stiffness: solid or flexible - without cable end
Height 107 mm
Width 65 mm
Depth 79.9 mm
Net weight 0.6 kg
Standards
  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
  • GB/T 14048.5
Product certifications
  • IECEE CB Scheme
  • UL
  • CSA
  • CCC
Ip degree of protection IP20 front face conforming to IEC 60529
Ambient air temperature for operation -25...70 °C conforming to IEC 60255...8
Ambient air temperature for storage -55...80 °C
Reach free of svhc Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1502001EN
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Others

Legacy weee scope In
Package 1 bare product quantity 1
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
At least in Europe
Product name TeSys LRD
Device short name LR9D
Relay application motor protection
Thermal overload class class 5…30
Thermal protection adjustment range 22...110 A
[ui] rated insulation voltage
  • power circuit: 1000 V
  • signalling circuit: 690 V
Tripping threshold 1.25 In conforming to IEC 60947-4-1
Time range 1.5...4 min - automatic reset time
[ith] conventional free air thermal current 5 A for signalling circuit
Associated fuse rating
  • 5 A gG for signalling circuit
  • 5 A BS for signalling circuit
[uimp] rated impulse withstand voltage 6 kV
Phase failure sensitivity phase difference > 40% 3-3 s conforming to IEC 60947-4-1
Electromagnetic compatibility
  • surge withstand: 2 kV common mode conforming to IEC 61000-4-5
  • resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2
  • immunity to radiated radio-electrical interference: 10 V/m conforming to IEC 61000-4-3
  • immunity to fast transients: 2 kV conforming to IEC 61000-4-4
Tightening torque
  • control circuit: 0.8 N.m on screw clamp terminals
  • power circuit: 9 N.m on screw clamp terminals
Operating altitude 2000 m without derating
Mechanical robustness
  • vibrations 10...150 Hz: 6 Gn conforming to IEC 60068-2-6
  • shocks 11 ms: 15 gn conforming to IEC 60068-2-7
Dielectric strength 6 kV 50 Hz conforming to IEC 60255-5
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 6.7 cm
Package 1 width 12.1 cm
Package 1 length 12.3 cm
Package 1 weight 690.9 g
Sustainable packaging No
End of life manual availability ENVEOLI1502001EN
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Documents & downloads

Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Data Bulletin

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.