Browse all
Browse all

TeSys D Contactor 3 poles - AC-3 440V 80 A - coil 12V DC

TeSys D Contactor 3 poles - AC-3 440V 80 A - coil 12V DC

Item Number: LC1D80JW

Datasheet

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth186 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Range of product TeSys D
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage power circuit: <= 1000 V AC 25...400 Hz
[ie] rated operational current
  • 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Mechanical durability 10000000 cycles
Connections - terminals
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • power circuit: screw terminals 1 4-50 mm² - cable stiffness: rigid
  • power circuit: screw terminals 2 4-25 mm² - cable stiffness: rigid
  • power circuit: screw terminals 1 4-50 mm² - cable stiffness: flexible without cable end
  • power circuit: screw terminals 2 4-25 mm² - cable stiffness: flexible without cable end
  • power circuit: screw terminals 1 4-50 mm² - cable stiffness: flexible with cable end
  • power circuit: screw terminals 2 4-16 mm² - cable stiffness: flexible with cable end
Insulation resistance > 10 MOhm for control circuit
Mounting support
  • rail
  • plate
Standards
  • EN 60947-5-1
  • CSA C22.2 No 14
  • EN 60947-4-1
  • IEC 60947-5-1
  • UL 508
  • IEC 60947-4-1
Product certifications
  • GL
  • RINA
  • BV
  • CSA
  • CCC
  • DNV
  • UL
  • GOST
  • LROS (Lloyds register of shipping)
Ip degree of protection
  • IP2X conforming to IEC 60529
  • IP2X conforming to VDE 0106
Climatic withstand conforming to IACS E10 exposure to damp heat
Height 127 mm
Width 85 mm
Depth 186 mm
Net weight 2.59 kg

Others

Legacy weee scope In
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • motor control
  • resistive load
Utilisation category
  • AC-2
  • AC-3
  • AC-1
  • AC-4
Poles description 3P
[uc] control circuit voltage 12 V DC
Motor power kw
  • 37 kW at 380...400 V AC 50 Hz
  • 55 kW at 500 V AC 50 Hz
  • 45 kW at 660...690 V AC 50 Hz
  • 22 kW at 220...230 V AC 50 Hz
  • 45 kW at 415...440 V AC 50 Hz
  • 45 kW at 1000 V AC 50 Hz
Motor power hp
  • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
  • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
  • 25 hp at 200/208 V AC 60 Hz for 3 phases motors
  • 30 hp at 230/240 V AC 60 Hz for 3 phases motors
  • 60 hp at 460/480 V AC 60 Hz for 3 phases motors
  • 60 hp at 575/600 V AC 60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for control circuit
  • 125 A (at 60 °C) for power circuit
Irms rated making capacity
  • 250 A DC for control circuit conforming to IEC 60947-5-1
  • 1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
  • 10 A gG for control circuit conforming to IEC 60947-5-1
  • 160 A gG at <= 690 V coordination type 2 for power circuit
  • 200 A gG at <= 690 V coordination type 1 for power circuit
Power dissipation per pole
  • 5.1 W AC-3
  • 12.5 W AC-1
[ui] rated insulation voltage
  • control circuit: 600 V CSA certified
  • control circuit: 600 V UL certified
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • control circuit: 690 V conforming to IEC 60947-1
  • power circuit: 1000 V conforming to IEC 60947-1
Overvoltage category III
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type DC wide range
Coil technology built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
  • 0.1...0.3 Uc (-40-70 °C):drop-out DC
  • 0.75...1.2 Uc (-40-55 °C):operational DC
  • 1...1.2 Uc (55-70 °C):operational DC
Inrush power in w 22 W (at 20 °C)
Hold-in power consumption in w 22 W at 20 °C
Operating time
  • 20...35 ms opening
  • 95...130 ms closing
Time constant 75 ms
Maximum operating rate 3600 cyc/h 60 °C
Tightening torque
  • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
  • control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
  • power circuit: 12 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
  • power circuit: 12 N.m - on screw terminal - with screwdriver hex (Allen key)4 mm
  • control circuit: 1.2 N.m - on lugs - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Minimum switching voltage 17 V for control circuit
Minimum switching current 5 mA for control circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contacts
  • 1.5 ms on energisation between NC and NO contacts
Permissible ambient air temperature around the device
  • -60...80 °C storage
  • -40...60 °C operation
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • shocks contactor opened (8 gn)
  • shocks contactor closed (10 Gn)
  • vibrations contactor opened (2 Gn, 5...300 Hz)
  • vibrations contactor closed (3 Gn, 5...300 Hz)
Unit type of package 1 PCE
Number of units in package 1 1
Sustainable packaging No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18