Package 1 Bare Product Quantity
1
Relay type
level control relay
Relay monitored parameters
detection by discrete sensors
Time delay type
adjustable 0.1...5 s, +/- 10 %
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Maximum power consumption in VA
5 VA AC
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
Contacts type and composition
2 C/O
[Uc] control circuit voltage
24...240 V
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits
20.4...264 V AC/DC
Control circuit voltage limits
- 15 % + 10 % Un
Maximum power consumption in W
1.5 W DC
Nominal output current
5 A
Run-up delay at power-up
0.5 s
Measurement accuracy
- +/- 10 % of the full scale value
- +/- 20 % for the HS range
Repeat accuracy
+/- 2 % for time delay
Measurement error
0.5 %/°C with temperature variation
Sensitivity adjustment
5...100 %
Maximum supply current for sensors
40 mA
Cable capacitance
10 nF for probe cable
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
250 V conforming to IEC 60664-1
[Uimp] rated impulse withstand voltage
- 4 kV conforming to IEC 60255-5
- 4 kV conforming to IEC 60664-1
- 4 kV conforming to IEC 61000-4-5
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Safety reliability data
- B10d = 170000
- MTTFd = 182.6 years
Functionality
discrete sensor detection
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
- 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
- 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
48
Package 2 Weight
7.131 kg