Package 1 Bare Product Quantity
1
Relay type
pump control relays
Product specific application
for 3-phase and single-phase pump
Relay monitored parameters
- overcurrent and undercurrent control
- phase sequence on 3-phase supply
- phase failure on 3-phase supply
Time delay type
- adjustable 1...60 s, +/- 10 % Ti on energisation
- fixed 0.3 s reset on terminal Y2
- adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Maximum power consumption in VA
5 VA AC
Measurement range
1...10 A AC
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
[Uc] control circuit voltage
Contacts type and composition
1 C/O
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
- 208...480 V AC 3 phases
- 230 V AC single phase
[Us] rated supply voltage
- 208...480 V AC 3 phases
- 230 V AC 1 phase
Supply voltage limits
183...528 V AC
Control circuit voltage limits
- 15 % + 10 % Un
Resistance across terminals
0.01 Ohm at E1-L2 terminals
Nominal output current
5 A
Maximum measuring cycle
140 ms as true rms value
Run-up delay at power-up
0.5 s
Hysteresis
5 % of threshold
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
- +/- 1 % for input and measurement circuit
- +/- 1 % for time delay
Measurement error
- 1 % by volt over the whole range
- +/- 0.05 %/°C
Response time
< 300="" ms="" (in="" the="" event="" of="" a="">
Input current
- 11 A permanent at 25 °C E1-L2 terminals
- 50 A non repetitive < 1="" s="" at="" 25="" °c="" e1-l2="">
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Supply frequency
50/60 Hz +/- 10 %
Operating position
any position
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Status LED
- 1 LED green for power ON
- 1 LED yellow for fault
- 1 LED yellow for relay ON
Operating rate
<= 360="" operations/hour="" full="">=>
Immunity to microbreaks
500 ms
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree
3 conforming to IEC 60664-1
Dielectric strength
2 kV AC 50 Hz (shock wave 4 kV)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
48
Package 2 Weight
6.526 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins