Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LX1D6
Control circuit type
AC at 60 Hz
[Uc] control circuit voltage
480 V AC 60 Hz
Average resistance
480 Ohm at 20 °C
Inductance of closed circuit
23 H
Product compatibility
  • LC1D80
  • LC1D95
    • Mechanical durability
      10 Mcycles
      Maximum operating rate
      3600 cyc/h 60 °C
      Coil technology
      without built-in suppressor module
      Control circuit voltage limits
    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
      • Inrush power in VA
        220-220 VA 60 Hz cos phi 0.75 (at 20 °C)
        Hold-in power consumption in VA
        22-22 VA 60 Hz cos phi 0.3 (at 20 °C)
        Heat dissipation
        6-10 W at 50/60 Hz
        Ambient air temperature for operation
        -5-60 °C
        Net weight
        0.28 kg
        California proposition 65
        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        Frequently Asked Questions

        hide show

        What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

        Issue:
        AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

        Product Line:
        Tesys D Replacement Parts

        Environment:
        TeSys™ D AC Coils

        Resolution:

        What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

        Issue:
        Identifying power terminal lug data for the D2 style contactors

        Product Line:
        Tesys D line contactors

        Environment:
        Products sold and used in the United States

        Cause:
        Power terminal lug data required

        Resolution:
        For contactors with screw clamp terminals:
        stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
        stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
        solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

        What is the altitude derating for a TeSys D-Line contactor?

        Issue:​
        What is the altitude derating for a TeSys D-Line contactor?

        Product Line:
        Digest 177 Section 18 : Contactors and Starters, IEC

        Environment:
        North American Products

        Resolution:
        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

        Voltage
        3500m x 0.90
        4000m x 0.80
        4500m x 0.70
        5000m x 0.60

        Current
        3500m x 0.92
        4000m x 0.90
        4500m x 0.88
        5000m x 0.86

        For example, an LC1D80 at 5000 meters:
        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



         

        What is the 240V coil needed for a LC1D80008 contactor

         The coil is a LX1D6U7

        spare 415VAC coil for LC1D80 Contactor ?

        Code = LX1D6N7

        Are the D-Line contactors rated to break DC voltages?

        Issue: 
        Can the TeSys D line be used to control DC loads? 

        Product Line:
        Tesys D contactors

        Environment:
        Products sold and used in the United States
         
        Cause:
         DC power circuit
         
        Resolution:
         
        Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

        Devices are suitable but not UL Listed for DC applications.

        More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


         

        What is the color scheme of the Tesys D-Line contactors?

        Issue:
        Looking for different color scheme of the Tesys D-Line contactors.

        Product Line:
        Tesys D Contactors

        Environment:
        LC1D contactors

        Resolution:
        Beige and dark gray.
         

        What is the replacement for LC1D115 with LX1D6G7 coil?

        The replacement for LC1D115 with LX1D6G7 coil is LC1D1156F7

        LC1D1156F7
        TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 110 V AC 50/60 Hz coil

        For more information see:
        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D1156F7

        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

        Issue:
        Identifying maximum voltage of an LC1D contactor

        Product Line:
        TeSys D Contactors

        Environment:
        IEC contactors and starters used in North America

        Cause:
        n/a

        Resolution:
        IThe maximum voltage per UL and CSA is 600VAC. 
         

        What are the stand alone short circuit current ratings on the LC1D** contactors?

        Issue:
        Tesys D SCCR

        Product Line:
        Contactors and Overload Relays

        Environment:
        TeSys™ D Contactors and Overload Relays
         
        Resolution:
        The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

        They are as follows:
        Horsepower SCCR (A)

        0 thru 1 1,000
        1 thru 50 5,000
        51 thru 200 10,000
        201 thru 400 18,000
        401 thru 600 30,000
        601 thru 900 42,000
        901 thru 1600 85,000
        1601+ 100,000

        What is the 480V coil for a CA2DN31T6 IEC Relay?

        Issue:
        What is the 480V coil for a CA2DN31T6 IEC Relay?

        Product Line:
        Tesys Relays

        Environment:
        Obsolete relays

        Cause:
        Product selection

        Resolution:
        The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


        CTA-ID : 2048217

        Is 240 volt replacement control coil available for LC1D11500?

        Issue:
        Identifying replacement coil part number

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Replacement control coil needed for older style Tesys Contactor

        Resolution:
        Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


        CTA-ID : 11321

        What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

        Issue:
        LC*D09-38 coil consumption

        Product Line:
        Contactors and Overload Relays

        Environment:
        TeSys™ D Contactors and Overload Relays

        Resolution:
        The standard DC coil is 5.4 watts of consumption.

        What is the 240v coil to fit an LC1D1506

         The 240v coil is an LX1D8U7

        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

        Issue:
        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

        Product Line:
        Contactors and Starters IEC

        Environment:
        Tesys D contactors and GV manual starters

        Cause:
        Spacer required

        Resolution:
        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

        What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

        Issue:
        What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

        Product Line:
        IEC Contactors

        Environment:
        Ordering

        Cause:
        Selection

        Resolution:
        The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

        AC Volts ___Code     AC Volts ___Code
        12 ___ J7                   208 ___ LE7
        21 ___ Z7                   220 ___ M7
        24 ___ B7                  230 ___ P7
        32 ___ C7                  240 ___ U7
        36 ___ CC7               277 ___ W7
        42 ___ D7                  380 ___ Q7
        48 ___ E7                   400 ___ V7
        60 ___ EE7                415 ___ N7
        100 ___ K7                440 ___ R7
        110 ___ F7                480 ___ T7
        115 ___ FE7              575 ___ SC7
        120 ___ G7                600 ___ X7
        127 ___ FC7              690 ___ Y7
        200 ___ L7                
                       
        Standard Coil                Low Consumption
        DC Volts ___Code          DC Volts ___Code
        12 ___ JD                           5 ___ AL
        24 ___ BD                         12 ___ JL
        36 ___ CD                         20 ___ ZL
        48 ___ ED                         24 ___ BL
        60 ___ ND                         48 ___ EL
        72 ___ SD                         72 ___ SL
        110 ___ FD                       96 ___ DL
        125 ___ GD                     110 ___ FL
        220 ___ MD                    220 ___ ML
        250 ___ UD                     250 ___ UL
        440 ___ RD                

        LC1D6511 contactor with 220V coil - NZ equivalent?

        LC1D65A contactor with a U7 240VAC coil is the closest.

        What is the code for a 240VAC coil for the LC1D65A Contactor?

        The LC1D65A is the Everlink contactor and the coil code is LXD3U7. 

        The code for complete contactor + 240VAC coil is LC1D65AU7
         

        How many wires can you install on the Power poles for the LC1D65A contactor?

         Issue:
        How many wires can you install on the Power poles for the LC1D65A contactor?

        Product line:
        Tesys D, Everlink

        Environment:
        LC1D40A LC1D50A LC1D65A

        Cause:
        Documentation not found

        Resolution:
        The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2. 

        Instruction bulletin attached.

        Can our "D" contactors handle 480volts?

        Our "D" Contactors LC1D09 - LC1D65A are rated to 690volts AC and the LC1D80 to LC1D150 are rated up to 1000VAC/ 690VDC.

        What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

        Product Line:
         
        Tesys D line Contactors and Accessories

        Resolution:
         
        Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
         

        Will the LR3D325 overload relay fit a LC1D65G7 contactor?

        Issue:
        Will the LC1D65G7 mount to the LR3D325 overload relay?

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Identifying product compatibility

        Resolution:
        No, the LR3D325 is a overload relay with Everlink termination and will direct mount only to the LC1D40A to LC1D65A contactors.


        CTA-ID : 2050461

        What does the (3) designate in the part number LC1D123G7?

        For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



        CTA-ID : 2053127

        Do the Everlink reversing contactors come with electrical interlocking?

        Issue:
        Looking for electrical interlock kit for the LC1D65A Everlnk contactors

        Product line:
        Tesys D LC1D40A, LC1D50A, LC1D65A

        Environment:
        Everlink, all voltage codes

        Cause:
        Old D2 version offered an electrical interlock kit

        Resolution:
        The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.