3P Micrologic 2.3 NSX630F- Compact circuit breaker

3P3T Micrologic 2.3 630A Nsx630F

Catalogue Number: LV432876
3P Micrologic 2.3 NSX630F- Compact circuit breaker
Retail
$6,167.78
RRP (Inc. GST)

Specifications

hide show
Range
Compact
Product name
Compact NSX
Range of product
NSX400...630
Device short name
Compact NSX630F
Product or component type
circuit breaker
Device application
distribution
Poles description
3P
Protected poles description
3t
[In] rated current
630 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
  • yes conforming to EN 60947-2
  • yes conforming to IEC 60947-2
    • Utilisation category
      category A
      Breaking capacity
    • 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    • 85 kA at 240 V AC 50/60 Hz conforming to UL 508
    • 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    • 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    • 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    • 35 kA at 480 V AC 50/60 Hz conforming to UL 508
    • 20 kA at 600 V AC 50/60 Hz conforming to UL 508
    • 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    • 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
      • Breaking capacity code
        F 36 kA 415 V AC
        Trip unit name
        Micrologic 2.3
        Trip unit technology
        electronic
        Trip unit protection functions
        LSoI
        Control type
        toggle
        Mounting mode
        fixed
        [Ui] rated insulation voltage
        800 V AC 50/60 Hz
        [Uimp] rated impulse withstand voltage
        8 kV
        [Ics] rated service breaking capacity
      • 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
      • 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
      • 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
      • 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
      • 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
      • 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • Mechanical durability
          15000 cycles
          Electrical durability
        • 6000 cycles 690 V In/2 conforming to IEC 60947-2
        • 2000 cycles 690 V In conforming to IEC 60947-2
        • 4000 cycles 440 V In conforming to IEC 60947-2
        • 8000 cycles 440 V In/2 conforming to IEC 60947-2
          • Mounting support
            backplate
            Upside connection
            front
            Downside connection
            front
            Connection pitch
            45 mm
            Protection type
          • L : for overload protection (long time)
          • So : for short time short-circuit protection with fixed delay
          • I : for instantaneous short-circuit protection
            • Trip unit rating
              630-630 A at 40 °C
              Long time pick-up adjustment type Ir
              adjustable 9 settings
              Long time pick-up adjustment range
              0.9...1 x Io
              Long time delay adjustment type
              fixed
              [tr] long-time delay adjustment range
              16-16 s at 6 x Ir
              Thermal memory
              20 minutes before and after tripping
              Short-time pick-up adjustment type Isd
              adjustable 9 settings
              [Isd] short-time pick-up adjustment range
              1.5...10 x Ir
              Short-time delay adjustment type
              fixed
              Instantaneous pick-up adjustment type Ii
              fixed
              Instantaneous pick-up adjustment range
              6900 A
              Auxiliary contact composition
              without
              Local signalling
            • LED ready
            • LED 90 % Ir
            • LED 105 % Ir
              • Width
                140 mm
                Height
                255 mm
                Depth
                110 mm
                Net weight
                6.2 kg
                Compatibility code
                NSX630
                Standards
              • EN/IEC 60947
              • UL 508
                • Product certifications
                • Marine
                • EAC
                • CCC
                  • Overvoltage category
                    class II
                    Electrical shock protection class
                    class II
                    Pollution degree
                    3 conforming to IEC 60664-1
                    IP degree of protection
                    IP40 conforming to IEC 60529
                    IK degree of protection
                    IK07 conforming to IEC 62262
                    Ambient air temperature for operation
                    -35-70 °C
                    Ambient air temperature for storage
                    -55-85 °C
                    Unit Type of Package 1
                    PCE
                    Number of Units in Package 1
                    1
                    Package 1 Weight
                    5.686 kg
                    Package 1 Height
                    15 cm
                    Package 1 width
                    15.6 cm
                    Package 1 Length
                    29 cm
                    Unit Type of Package 2
                    S04
                    Number of Units in Package 2
                    3
                    Package 2 Weight
                    18.622 kg
                    Package 2 Height
                    30 cm
                    Package 2 width
                    40 cm
                    Package 2 Length
                    60 cm
                    Sustainable offer status
                    Green Premium product
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP120606EN
                    Circularity Profile
                    ENVEOLI120604EN
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • End of Life Manual

                    • Product Environmental

                    • Installation Instruction

                    • Operating Manuals

                    • Declaration of Conformity

                    Frequently Asked Questions

                    hide show

                    Will the Compact NSX breaker be for sale in the USA or Canada?

                    Issue:
                    Where can I buy a Compact NSX breaker?

                    Product Line:
                    Circuit Breakers

                    Cause:
                    This breaker is popular overseas and there is interest in the US

                    Resolution:
                    There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                    If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                    For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                    https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

                    Are EasyPact CVS circuit breakers for sale in the USA or Canada?

                    Product Line:
                    EasyPact CVS circuit breakers

                    Cause:
                    This breaker is popular overseas and there is interest in the US

                    Resolution:
                    There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.

                    Are EasyPact EZC or EZD circuit breakers for sale in the USA or Canada?

                    Product Line:
                    EasyPact EZC and EZD circuit breakers

                    Cause:
                    This breaker is popular overseas and there is interest in the US

                    Resolution:
                    There are no plans for a general release of the EasyPact EZC or EZD circuit breaker line in North America.

                    What parts come with a LV432475

                     It comes with a set of two short rear connections

                    What is the Australia equivalent for a LV432733?

                    The LV432733 combo pack is not sold in Australia.

                    What you will have to get is buy the LV432693 breaker and the add on LV432453 vigi module separately.

                    LV432693 breaker - https://www.schneider-electric.com.au/en/product/LV432693/circuit-breaker-compact-nsx400n---micrologic-2.3---400-a---3-poles-3d
                    LV432453 vigi module - https://www.schneider-electric.com.au/en/product/LV432453/earth-leakage-module-compact-vigi-mb---300..30000-ma---440..550-v---3-poles

                     

                    What is the alternative to the MG NS400N MCCB, 32693?

                    The NS400N equivalent is  LV432403 (NAX400N frame) + LV432081 (trip unit).

                    LV432403 / NSX400 - needing handle extended rotary - what is the code?

                    Code = LV432598

                    Can I connect aluminium or copper, flexible or rigid cables to the single and double terminals of the NSX 400 to 630 range.?

                    In the NSX 400 to 630 range:

                    Single terminals, part numbers LV432479 or LV432480, can take: aluminium or copper rigid cables with cross-section 35 to 300 mm² and flexible cables with cross-section 240 mm² maximum.

                    Double terminals, part numbers LV432481 or LV432482, can take: aluminium or copper rigid cables with cross-section 35 to 240 mm² and flexible cables with cross-section 185 mm² maximum.

                    Can LV432631 be locked in ON position?

                    Part number LV432631 can be locked in ON or OFF position.

                    What is the part number for a NSX630 C/B with Micrologic 2.3 overload , extended rotary handle and long terminal covers?

                    The part numbers for a NSX630 C/B with Micrologic 2.3 overload , extended rotary handle and long terminal covers are - LV432893 , LV432598 & LV432593
                    For further information , visit link below:-
                    https://www.schneider-electric.com.au/en/search/LV432893
                    https://www.schneider-electric.com.au/en/search/+LV432598
                    https://www.schneider-electric.com.au/en/search/LV432593
                    User-added image
                    User-added image
                    User-added image

                    Micrologic trip unit 320Amp needed for motor protection

                    Use a LV432069

                    What is a 3P 50kA MCCB with 125A trip unit and vigi block, would also need a 125Amp RCBO

                    Use a LV430406 - 160Amp frame + LV430431 125Amp trip unit + LV429211 Vigi module + LV431536 connector = 125Amp RCBO