Extended rotary handle - padlockable - black
Extended standard rotary handle- NSX400-630 circuit breaker accessory
Extended standard rotary handle- NSX100-250 circuit breaker accessory
Extended rotary handle - padlockable - black
Extended standard rotary handle- NSX400-630 circuit breaker accessory
Extended standard rotary handle- NSX100-250 circuit breaker accessory

Compact NSX Extended Standard Rotary Handle, Padlockable

Catalogue Number: LV432598
Extended rotary handle - padlockable - black
Extended standard rotary handle- NSX400-630 circuit breaker accessory
Extended standard rotary handle- NSX100-250 circuit breaker accessory
Extended rotary handle - padlockable - black
Extended standard rotary handle- NSX400-630 circuit breaker accessory
Extended standard rotary handle- NSX100-250 circuit breaker accessory
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
  • Easypact CVS400...630
  • NSX400...630
  • PowerPact multistandard
  • TeSys GV6
    • Product or component type
      rotary handle
      Accessory / separate part type
      control accessories
      Handle front plate colour
      black
      Rotary handle padlocking
    • 1 to 3 padlocks
    • padlock in OFF position
      • Rotary handle mounting location
        front
        Handle colour
        black
        Rotary handle mounting style
        extended
        Compatibility code
        extended rotary handle
        Sustainable offer status
        Green Premium product
        EU RoHS Directive
        Pro-active compliance (Product out of EU RoHS legal scope)
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
        Product out of China RoHS scope. Substance declaration for your information
        Environmental Disclosure
        ENVPEP110804EN
        Circularity Profile
        ENVEOLI111011EN
        Warranty
        18 months

        Documents & downloads

        hide show
        Filter items
        • All

        • CAD Files and Packs

        • Product Brochures

        • Technical Data Catalogues

        • Installation Instruction

        • Operating Manuals

        • Corporate Marketing

        Frequently Asked Questions

        hide show

        Will the Compact NSX breaker be for sale in the USA or Canada?

        Issue:
        Where can I buy a Compact NSX breaker?

        Product Line:
        Circuit Breakers

        Cause:
        This breaker is popular overseas and there is interest in the US

        Resolution:
        There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

        If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

        For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
        https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page

        Are EasyPact CVS circuit breakers for sale in the USA or Canada?

        Product Line:
        EasyPact CVS circuit breakers

        Cause:
        This breaker is popular overseas and there is interest in the US

        Resolution:
        There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.

        Are EasyPact EZC or EZD circuit breakers for sale in the USA or Canada?

        Product Line:
        EasyPact EZC and EZD circuit breakers

        Cause:
        This breaker is popular overseas and there is interest in the US

        Resolution:
        There are no plans for a general release of the EasyPact EZC or EZD circuit breaker line in North America.

        LV432403 / NSX400 - needing handle extended rotary - what is the code?

        Code = LV432598

        What is the part number for a terminal sheilds for the NSX400/630 C/B's?

        The part numbers for a terminal sheilds for the NSX400/630 C/B's are - 3 pole short - LV432591, 3 pole long - LV432593 , 4 pole short - LV432592 , 4 pole long - LV432594

        For further information , visit links below:
        https://www.schneider-electric.com.au/en/search/LV432591
        https://www.schneider-electric.com.au/en/search/LV432593
        https://www.schneider-electric.com.au/en/search/LV432592
        https://www.schneider-electric.com.au/en/search/LV432594
        User-added image
        User-added image

        User-added image

        Will extended rotary handle LV432598 fit a NS400/630 Breaker?

        The extended rotary handle  LV432598 will fit a NS400/630 Breaker.
         

        What is the Australia equivalent for a LV432733?

        The LV432733 combo pack is not sold in Australia.

        What you will have to get is buy the LV432693 breaker and the add on LV432453 vigi module separately.

        LV432693 breaker - https://www.schneider-electric.com.au/en/product/LV432693/circuit-breaker-compact-nsx400n---micrologic-2.3---400-a---3-poles-3d
        LV432453 vigi module - https://www.schneider-electric.com.au/en/product/LV432453/earth-leakage-module-compact-vigi-mb---300..30000-ma---440..550-v---3-poles

         

        What is the Length of LV432598?

        The length is 195mm - 600mm to back of door from the base, where the breaker is mounted.
        For more information please see the instruction sheet .....https://www.schneider-electric.com.au/sites/australia/en/support/substitution-tool/substitution-tool.page..
         

        What is the part number for a NSX630 C/B with Micrologic 2.3 overload , extended rotary handle and long terminal covers?

        The part numbers for a NSX630 C/B with Micrologic 2.3 overload , extended rotary handle and long terminal covers are - LV432893 , LV432598 & LV432593
        For further information , visit link below:-
        https://www.schneider-electric.com.au/en/search/LV432893
        https://www.schneider-electric.com.au/en/search/+LV432598
        https://www.schneider-electric.com.au/en/search/LV432593
        User-added image
        User-added image
        User-added image

        Will the NSX100F , LV438568 , and the NSX100N , LV438580 fit the same chassis?

        Yes , dimensions are the same.....
        For further information , visit links below:-
        https://www.schneider-electric.com.au/en/search/LV438568
        https://www.schneider-electric.com.au/en/search/LV438580

        User-added image
        User-added image
         

        What are the terminal spreaders that can be used for the INS320?

        LV432490 - 52.5mm Pitch
        Please follow the link for the data sheet:
        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LV432490
         

        What is the part number for a spreader set to suit the LV432693?

        The Spreader set for LV432693 is the LV432490.

        What is the alternative to the MG NS400N MCCB, 32693?

        The NS400N equivalent is  LV432403 (NAX400N frame) + LV432081 (trip unit).

        What is the code for the bag screws for compact NSX400 - 630 ?

        LV432552 is the code for the bag of spare screws

        Can LV432631 be locked in ON position?

        Part number LV432631 can be locked in ON or OFF position.

        Micrologic trip unit 320Amp needed for motor protection

        Use a LV432069

        What is the motor trip unit needed for a LV430403 frame, 150A

        Use a LV430500

        What is the part code for an MCCB, 250Amp 1P 160Amp DC rated

        Use a LV438693

        What parts come with a LV432475

         It comes with a set of two short rear connections

        Will a LV432455 Vigi add on fit to a NS630H MCCB?

        A LV432455 Vigi add on will not fit a NS630H MCCB only a 32455 will fit otherwise will need to change MCCB to LV432895.
         

        What is the replacement code for a 29587 breaker

         Use a LV438575 - NSX100N 30Amp 1P 50kA breaker

        What is the replacement for NS630H with STR23SE trip unit?

        The replacement for NS630H with STR23SE trip unit is LV432895
        Schneider Electric LV432895 Image
        LV432895

        Circuit breaker Compact NSX630H - Micrologic 2.3 - 630 A - 3 poles 3d


        PR_Product_OPS_Structure
        Circuit Breakers and
        Switches
        Molded case circuit
        Breakers
        Compact NSX
        For further information see:https://www.schneider-electric.com/en/product/LV432895/circuit-breaker-compact-nsx630h---micrologic-2.3---630-a---3-poles-3d/

        3P INS250 long terminal shield for front connections code?

        Code = LV429518

        What is part number for spreader bars for NSX400 breaker?

        The part number for spreader bars for NSX400 breaker is LV432490
        LV432490 Product picture
        LV432490

        Spreaders, Compact NSX 400/630, 52.5 mm pitch, flat connection, set of 3 parts

        PR_Product_OPS_Structure
        Circuit Breakers and
        Switches
        Molded case circuit
        Breakers
        Compact NSX

        For further information see:https://www.se.com/au/en/product/LV432490/spreaders%2C-compact-nsx-400-630%2C-52.5-mm-pitch%2C-flat-connection%2C-set-of-3-parts/
         

        Can I connect aluminium or copper, flexible or rigid cables to the single and double terminals of the NSX 400 to 630 range.?

        In the NSX 400 to 630 range:

        Single terminals, part numbers LV432479 or LV432480, can take: aluminium or copper rigid cables with cross-section 35 to 300 mm² and flexible cables with cross-section 240 mm² maximum.

        Double terminals, part numbers LV432481 or LV432482, can take: aluminium or copper rigid cables with cross-section 35 to 240 mm² and flexible cables with cross-section 185 mm² maximum.

        What is code for NS400N?

        We no longer do the NS Range of MCCB's. The new model is  NSX400N and the code for the frame is LV432403

        Are the captive Nuts from the Main terminals on the NSX100 - 250 MCCBs available as a spare part?

        Yes but not on their own. They are available in a pack of 12 (1 whole set plus an extra set)
        The part number is LV429234 (NSX100) or LV430554 (NSX160-250)

        What is the part number for special cover if the 4P Vigi is used with a 3P circuit breaker?

        Part no will be LV429214 for NSX100/250/160 breakers
        Part no will be LV432457 for NSX400/650  Breakers

        What is a 3P 50kA MCCB with 125A trip unit and vigi block, would also need a 125Amp RCBO

        Use a LV430406 - 160Amp frame + LV430431 125Amp trip unit + LV429211 Vigi module + LV431536 connector = 125Amp RCBO

        What is the part number for terminal shields for NSX160 Breaker?

         The part number for terminal shields for NSX160 Breaker is LV429517 ( LONG 3P), LV429515 ( SHORT 3P), LV429518 ( LONG 4P), LV429516 ( SHORT 4P)
        Image result for LV429517

        LV429517 
        long terminal shield - 3 poles - for NSX100..250
        https://www.schneider-electric.com.au/en/product-range-selector/1887-compact-nsx--630a/?p_url=http%3A%2F%2Fwww.ops-ecat.schneider-electric.com%2Fecatalogue%2Fbrowse.do%3Fel_typ%3Dproduct%26cat_id%3DBU_ED_1887_L3_Z010%26conf%3Dbasket%26prd_id%3DLV429517%26scp_id%3DZ010

        What is the difference Between NSX Vigi Block  LV429210 & LV431535?

        LV429210 - Is Vigi block MH type for NSX100/160 (200 to 440 V)

        LV431535 - Is Vigi block MH type for NSX250 (200 to 440 V)

        Even though Tech datasheet specifies the LV429210 is rated for NSX upto 250, It is recommeded to use the VIgi module only for NSX 100/160. 

        However, LV431535 can be used for NSX100/160/250. 

         

        Why does the FDM128 (LV434128) ask to verify an IP Address different than the one configured during the firmware update?

        Issue
        After updating the FDM128, the display shows a Runtime message that asks to verify the IP address that is not the one I configured.  After the FDM128 does a power cycle, the configured address is returned to the configured value.

        Example screenshot:
        FDM128_VerifyIPAddress_on_FW_Update.jpg

        Product Line/ Environment
        FDM128 

        Cause
        This screen is displayed during the initialization of the Runtime.  It displays the hardware's default IP address in the event of a complete recovery.  For FDM128 users who have completed the IP Address configuration, this has no impact on the IP Address.  The IP Address that was configured will be maintained in memory and will be used after the power cycle to complete the firmware update.

        Resolution
        Under normal conditions, the IP Address shown in the screen above will not show the configured address in the FDM128.


         

        Why does the FDM128 (LV434128) V6.1.1 not display values the serial number for some devices?

        Issue
        The FDM128 (LV434128) with firmware version 6.1.1 has fields to show the serial numbers of connected equipment.  However, the values are blank or N/A.

        Product Line/ Environment
        FDM128 

        Cause
        The serial number and firmware version information should be read from the equipment if the equipment has a Modbus register to store the value.  In V6.1.1, the strings were added for some equipment that do not support the field.  For example, FDM121 does not provide the Serial Number.  In addition, the FDM121 and BSCM do not provide the Firmware version over communication. As a result, the fields will be blank or N/A.

        Resolution
        Some fields may not be able to display the serial number and/or firmware version information if it is not communicated between the FDM128 and the other device.