Quantcast

TeSys LRD Thermal Overload Relays, 0.25...0.4A Class, 10A

TeSys LRD Thermal Overload Relays, 0.25...0.4A Class, 10A

TeSys LRD Thermal Overload Relays, 0.25...0.4A Class, 10A

Item Number: LRD03

Product Dimensions

Width icon

Width45 mm

Height icon

Height66 mm

Depth icon

Depth70 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Warranty

18 months

Range

  • TeSys
  • TeSys Deca

Product or component type

differential thermal overload relay

Product compatibility

  • LC1D25
  • LC1D18
  • LC1D38
  • LC1D12
  • LC1D32
  • LC1D09

Physical

Mounting support

  • plate, with specific accessories
  • rail, with specific accessories
  • under contactor

[Ue] rated operational voltage

690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

Control type

  • red push-button: stop
  • blue push-button: reset

Connections - terminals

  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end
  • power circuit: screw clamp terminals 1 cable(s) 1.5-10 mm² flexible without cable end
  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm² flexible with cable end
  • power circuit: screw clamp terminals 1 cable(s) 1-6 mm² solid without cable end

Height

66 mm

Width

45 mm

Depth

70 mm

Net weight

0.124 kg

Climatic withstand

conforming to IACS E10

IP degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for operation

-20...60 °C without derating conforming to IEC 60947...4-1

Ambient air temperature for storage

-60...70 °C

Standards

  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
  • GB/T 14048.5
  • EN 50495

Product certifications

  • IEC
  • UL
  • CSA
  • CCC
  • EAC
  • BV
  • RINA
  • DNV-GL
  • LROS (Lloyds register of shipping)
  • ATEX INERIS
  • UKCA

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Network frequency

0...400 Hz

Tripping threshold

1.14 +/- 0.06 Ir conforming to IEC 60947-4-1

Auxiliary contact composition

1 NO + 1 NC

[Ith] conventional free air thermal current

5 A for signalling circuit

Permissible current

  • 3 A at 120 V AC-15 for signalling circuit
  • 0.22 A at 125 V DC-13 for signalling circuit

Associated fuse rating

  • 4 A gG for signalling circuit
  • 4 A BS for signalling circuit

[Uimp] rated impulse withstand voltage

6 kV

Phase failure sensitivity

tripping current 130 % of Ir on two phase, the last one at 0

Temperature compensation

-20...60 °C

Tightening torque

  • control circuit: 1.7 N.m - on screw clamp terminals
  • power circuit: 1.7 N.m - on screw clamp terminals

Compatibility code

LRD

Flame retardance

V1 conforming to UL 94

Mechanical robustness

  • vibrations: 6 Gn conforming to IEC 60068-2-6
  • shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7

Dielectric strength

1.89 kV at 50 Hz conforming to IEC 60947-1

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

137.0 g

Package 1 Height

5 cm

Package 1 width

7.8 cm

Package 1 Length

8.8 cm

Unit Type of Package 2

S02

Number of Units in Package 2

24

Package 2 Weight

3.596 kg

Package 2 Height

15 cm

Package 2 width

30 cm

Package 2 Length

40 cm

Unit Type of Package 3

P06

Number of Units in Package 3

384

Package 3 Weight

65.536 kg

Package 3 Height

75 cm

Package 3 width

60 cm

Package 3 Length

80 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product name

  • TeSys LRD
  • TeSys Deca

Device short name

LRD

Relay application

motor protection

Network type

  • AC
  • DC

Thermal overload class

class 10A conforming to IEC 60947-4-1

Thermal protection adjustment range

0.25...0.4 A

[Ui] rated insulation voltage

  • power circuit: 600 V conforming to CSA
  • power circuit: 600 V conforming to UL
  • power circuit: 690 V conforming to IEC 60947-4-1
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • End of Life Manual

  • Operating Manuals

  • Certificates (MSDS)