Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LP1D
Contactor application
resistive load
Utilisation category
AC-1
Poles description
4P
Pole contact composition
2 NO + 2 NC
[Ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current
      60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
      Control circuit type
      DC wide range
      [Uc] control circuit voltage
      220 V DC
      Coil type
      wide range
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      Overvoltage category
      III
      [Ith] conventional free air thermal current
      60 A (at 60 °C) for power circuit
      Irms rated making capacity
      800 A at 440 V for power circuit conforming to IEC 60947
      Rated breaking capacity
      800 A at 440 V for power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
    • 72 A 40 °C - 10 min for power circuit
    • 165 A 40 °C - 1 min for power circuit
    • 320 A 40 °C - 10 s for power circuit
    • 720 A 40 °C - 1 s for power circuit
      • Associated fuse rating
      • 80 A gG at <= 690 V coordination type 1 for power circuit
      • 80 A gG at <= 690 V coordination type 2 for power circuit
        • Average impedance
          1.5 mOhm - Ith 60 A 50 Hz for power circuit
          [Ui] rated insulation voltage
        • power circuit: 690 V conforming to IEC 60947-4-1
        • power circuit: 600 V CSA certified
        • power circuit: 600 V UL certified
          • Electrical durability
            1.4 Mcycles 60 A AC-1 at Ue <= 440 V
            Power dissipation per pole
            5.4 W AC-1
            Protective cover
            without
            Mounting support
          • rail
          • plate
            • Standards
            • CSA C22.2 No 14
            • EN 60947-4-1
            • EN 60947-5-1
            • IEC 60947-4-1
            • IEC 60947-5-1
            • UL 508
              • Product certifications
              • BV
              • CCC
              • CSA
              • DNV
              • EAC
              • GL
              • LROS (Lloyds register of shipping)
              • UL
                • Connections - terminals
                • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²flexible without cable end
                • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²flexible without cable end
                • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²flexible with cable end
                • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²flexible with cable end
                • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²solid without cable end
                • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²solid without cable end
                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                  • Tightening torque
                  • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                  • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                    • Operating time
                    • 4...19 ms opening
                    • 12...26 ms closing
                      • Safety reliability level
                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                        • Mechanical durability
                          10 Mcycles
                          Maximum operating rate
                          3600 cyc/h 60 °C
                          Coil technology
                          built-in bidirectional peak limiting diode suppressor
                          Control circuit voltage limits
                        • 0.1...0.3 Uc 55-55 °C drop-out DC
                        • 0.75...1.2 Uc 55-55 °C operational DC
                          • Time constant
                            75 ms
                            Inrush power in W
                            22-22 W at 20 °C
                            Hold-in power consumption in W
                            22-22 W at 20 °C
                            Contact compatibility
                            M3
                            Compatibility code
                            LP1D
                            IP degree of protection
                            IP20 front face conforming to IEC 60529
                            Protective treatment
                            TH conforming to IEC 60068-2-30
                            Pollution degree
                            3
                            Ambient air temperature for operation
                            -5-60 °C
                            Ambient air temperature for storage
                            -60-80 °C
                            Permissible ambient air temperature around the device
                            -40-70 °C at Uc
                            Operating altitude
                            3000 m without
                            Fire resistance
                            850 °C conforming to IEC 60695-2-1
                            Flame retardance
                            V1 conforming to UL 94
                            Mechanical robustness
                          • vibrations contactor open: 2 Gn, 5...300 Hz
                          • vibrations contactor closed: 4 Gn, 5...300 Hz
                          • shocks contactor open: 10 Gn for 11 ms
                          • shocks contactor closed: 15 Gn for 11 ms
                            • Height
                              127 mm
                              Width
                              85 mm
                              Depth
                              182 mm
                              Net weight
                              2.21 kg
                              Sustainable offer status
                              Green Premium product
                              REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Compliant
                              Toxic heavy metal free
                              Yes
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              X
                              Environmental Disclosure
                              ENVPEP1503009EN
                              Circularity Profile
                              ENVEOLI1503009EN
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • Product Brochures

                              • Technical Data Catalogues

                              • Product Environmental

                              • End of Life Manual

                              • Certificates (MSDS)

                              • Declaration of Conformity

                              Frequently Asked Questions

                              hide show

                              What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                              Issue:
                              Identifying power terminal lug data for the D2 style contactors

                              Product Line:
                              Tesys D line contactors

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Power terminal lug data required

                              Resolution:
                              For contactors with screw clamp terminals:
                              stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                              stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                              solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum voltage of an LC1D contactor

                              Product Line:
                              TeSys D Contactors

                              Environment:
                              IEC contactors and starters used in North America

                              Cause:
                              n/a

                              Resolution:
                              IThe maximum voltage per UL and CSA is 600VAC. 
                               

                              Are the D-Line contactors rated to break DC voltages?

                              Issue: 
                              Can the TeSys D line be used to control DC loads? 

                              Product Line:
                              Tesys D contactors

                              Environment:
                              Products sold and used in the United States
                               
                              Cause:
                               DC power circuit
                               
                              Resolution:
                               
                              Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                              Devices are suitable but not UL Listed for DC applications.

                              More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                               

                              Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                              Issue:
                              Auxiliary contact modules for the LC1D and LC2D contactors

                              Product Line: 
                              Contactor and Starters - IEC

                              Environment:
                              North American Products

                              Resolution:
                              Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                              Front Mounting; maximum of 1 block per contactor:

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------1---------LADN11-----------LA1DN11
                              --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                              --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                              --2-----------0---------LADN20-----------LA1DN20
                              --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                              --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                              --0-----------2---------LADN02-----------LA1DN02
                              --2-----------2---------LADN22-----------LA1DN22
                              --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                              --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                              --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                              --3-----------1---------LADN31------------LA1DN31
                              --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                              --1-----------3---------LADN13------------LA1DN13
                              --4-----------0---------LADN40------------LA1DN40
                              --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                              --0-----------4---------LADN04------------LA1DN04




                              Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------0--------LADN10----------LA1DN10
                              --0-----------1--------LADN01----------LA1DN01

                              Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                              (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                              N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                              --1-----------1--------LAD8N11----------LA8DN11
                              --2-----------0--------LAD8N20----------LA8DN20
                              --0-----------2--------LAD8N02----------N/A

                              Footnotes:
                              {1} EN50 012 Machine Tool Terminal Markings
                              {2} (2) NO Sealed Dust Tight Contacts
                              {3} Gold Flash Contacts
                              {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                              {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                              {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                              What is the color scheme of the Tesys D-Line contactors?

                              Issue:
                              Looking for different color scheme of the Tesys D-Line contactors.

                              Product Line:
                              Tesys D Contactors

                              Environment:
                              LC1D contactors

                              Resolution:
                              Beige and dark gray.
                               

                              What are the stand alone short circuit current ratings on the LC1D** contactors?

                              Issue:
                              Tesys D SCCR

                              Product Line:
                              Contactors and Overload Relays

                              Environment:
                              TeSys™ D Contactors and Overload Relays
                               
                              Resolution:
                              The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                              They are as follows:
                              Horsepower SCCR (A)

                              0 thru 1 1,000
                              1 thru 50 5,000
                              51 thru 200 10,000
                              201 thru 400 18,000
                              401 thru 600 30,000
                              601 thru 900 42,000
                              901 thru 1600 85,000
                              1601+ 100,000

                              Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                              Issue:
                              Can new accessories be used on older style contactors

                              Product Line:
                              IEC contactors and starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying product compatibility

                              Resolution:
                              Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                               

                              What is the part cod for a contactor 4P 2N/C 2N/O 48Vac coil

                               The part code is LC1D40008E7

                              LP1K09008MD is this available in New Zealand

                              This is not set up for sale in NZ

                              What is part number for 4 pole, 80A contactor , 220V DC Coil?

                              The part number for 4 pole, 80A contactor , 220V DC Coil is LP1D80008MD. This Contactor is AC-1 rated only (Slightly Inductive Loads/resistive loads).

                              For more information see:https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LP1D80008MD

                              What is the replacement for LC1D40004N5 Contactor?

                              What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                              Issue:
                              AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                              Product Line:
                              Tesys D Replacement Parts

                              Environment:
                              TeSys™ D AC Coils

                              Resolution:
                              Show More