Specifications

hide show
Range
TeSys
Product name
TeSys LE
Device short name
LE2D
Product or component type
enclosed DOL reversing starter
Device application
standard
Utilisation category
AC-3
Device composition
  • thermal overload relay ordered separately
  • reversing contactor
    • [Ie] rated operational current
      12 A AC-3
      Motor power kW
    • 3 kW at 220/230 V AC 50/60 Hz
    • 7.5 kW at 500 V AC 50/60 Hz
    • 7.5 kW at 660/690 V AC 50/60 Hz
    • 5.5 kW at 380/400 V AC 50/60 Hz
    • 5.5 kW at 415 V AC 50/60 Hz
    • 5.5 kW at 440 V AC 50/60 Hz
      • [Ithe] conventional enclosed thermal current
        12 A
        [Uc] control circuit voltage
        110 V AC 50/60 Hz
        Control type
      • push-button stop/reset red O
      • selector switch 2 positions start I-II
        • Cable entry number
        • 2 ISO20 top
        • 2 ISO25 top
        • 2 Pg 16 bottom
        • 2 Pg 21 bottom
        • 2 ISO20 bottom
        • 2 ISO25 bottom
          • Width
            101 mm
            Height
            201 mm
            Depth
            160 mm
            Net weight
            2.1 kg
            Compatibility code
            LE2D
            Material
            polycarbonate
            IP degree of protection
            IP65 conforming to IEC 60529
            IK degree of protection
            IK07 conforming to IEC 60529
            Standards
            IEC 60947-4-1
            Ambient air temperature for operation
            -5-40 °C
            Environmental characteristic
            standard environment
            Warranty
            18 months

            Frequently Asked Questions

            hide show

            Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

            Issue:
            Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

            Product Line: 
            Tesys D Contactors

            Environment:
            IEC contactors

            Resolution:
            The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
             

            Can the LE1D and LE2D enclosed Tesys D-Line contactors be obtained with DC control coils?

            Issue:  
            Tesys D enclosed starter with a DC control 

            Product Line:
             Enclosed Tesys D line starters

            Environment:
            North American Products
             
            Cause:
            DC control circuit 
             
            Resolution:
            Yes but limited to 24 VDC.

            What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

            Issue:
            Identifying replacement coils for tesys D non-reversing and reversing conactors

            Product Line:
            IEC Contactors and Starters

            Environment:
            Products sold and used in the United States

            Cause:
            Replacement coil is needed

            Resolution:
            DC replacement coils are not available.
            AC Coils are 50/60 hertz for voltages as listed below:

            Volts - Part Number
            12 ____ LXD1J7
            21 ____ LXD1Z7
            24 ____ LXD1B7
            32 ____ LXD1C7
            36 ____ LXD1CC7
            42 ____ LXD1D7
            48 ____ LXD1E7
            60 ____ LXD1EE7
            100 ___ LXD1K7 ( never brought to North America )
            110 ___ LXD1F7
            115 ___ LXD1FE7
            120 ___ LXD1G7
            127 ___ LXD1FC7
            200 ___ LXD1L7
            208 ___ LXD1LE7
            220 ___ LXD1M7
            230 ___ LXD1P7
            240 ___ LXD1U7
            277 ___ LXD1W7
            380 ___ LXD1Q7
            400 ___ LXD1V7
            415 ___ LXD1N7
            440 ___ LXD1R7
            480 ___ LXD1T7
            575 ___ LXD1SC7
            600 ___ LXD1X7
            690 ___ LXD1Y7


            Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

            What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

            Issue:
            Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

            Product Line:
            NEMA combination starters

            Environment:
            Products sold and used in the United States

            Resolution:
            For contactors with screw clamp terminals:
            stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
            stranded cable w/cable end: One or Two #18-10 AWG per terminal.
            solid cable: One or Two #18-8 AWG per terminal.

            What is the coil consumption or burden for the Tesys LC*D** contactors?

            * 1 or 2
            ** 09 through 38

            Issue:
            Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A

            Product Line: 
            Contactors and Starters - IEC

            Environment:
            North American Products

            Resolution:
            All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.

            Is part number LE3D12N7 available with latching on button?

            No part number LE3D12N7 does not have latching push button.

            What is the altitude derating for a TeSys D-Line contactor?

            Issue:​
            What is the altitude derating for a TeSys D-Line contactor?

            Product Line:
            Digest 177 Section 18 : Contactors and Starters, IEC

            Environment:
            North American Products

            Resolution:
            The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

            Voltage
            3500m x 0.90
            4000m x 0.80
            4500m x 0.70
            5000m x 0.60

            Current
            3500m x 0.92
            4000m x 0.90
            4500m x 0.88
            5000m x 0.86

            For example, an LC1D80 at 5000 meters:
            - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
            - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



             

            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

            Issue:
            Identifying maximum voltage of an LC1D contactor

            Product Line:
            TeSys D Contactors

            Environment:
            IEC contactors and starters used in North America

            Cause:
            n/a

            Resolution:
            IThe maximum voltage per UL and CSA is 600VAC. 
             

            What is the overload to suit LE3D12N7 star delta starter?

            Overload to suit LE3D12N7 will be either LRD12, LRD14 or LRD16 depending on application.

            What is the replacement base for a LE1D12N7

            The base is not available on it's own but a replacement enclosure including base is a DE1DS1

            Will a LC1D12F7 operate on 60V DC as a control voltage

            No it will not

            What is the Mechanical Interlock for the LC1D12F7 ?

            LAD9R1V Is the code for the Mechanical and Electrical Interlock kit.
            Show More