TeSys D reversing contactor-3P-AC3 440V 50A 24V DC coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 50A, 24V DC Coil

Catalogue Number: LC2D50ABBE
TeSys D reversing contactor-3P-AC3 440V 50A 24V DC coil
Retail
$5,463.32
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
reversing contactor
Device short name
LC2D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-1
    • AC-3
      • Device presentation
        preassembled with reversing power busbar
        Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 50 A (at <60 °C) at <= 440 V AC-3 for power circuit
      • 80 A (at <60 °C) at <= 440 V AC-1 for power circuit
        • Motor power kW
        • 15 kW at 220...230 V AC 50 Hz
        • 22 kW at 380...400 V AC 50 Hz
        • 25 kW at 415 V AC 50 Hz
        • 30 kW at 440 V AC 50 Hz
        • 30 kW at 500 V AC 50 Hz
        • 33 kW at 660...690 V AC 50 Hz
          • Motor power hp
          • 3 hp at 115 V AC 60 Hz for 1 phase motors
          • 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 15 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 15 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 40 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 40 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
              DC DC low consumption
              [Uc] control circuit voltage
              24 V DC
              Auxiliary contact composition
              1 NO + 1 NC
              [Uimp] rated impulse withstand voltage
              6 kV conforming to IEC 60947
              Overvoltage category
              III
              [Ith] conventional free air thermal current
            • 10 A (at 60 °C) for signalling circuit
            • 80 A (at 60 °C) for power circuit
              • Irms rated making capacity
              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
              • 900 A at 440 V for power circuit conforming to IEC 60947
                • Rated breaking capacity
                  900 A at 440 V for power circuit conforming to IEC 60947
                  [Icw] rated short-time withstand current
                • 100 A - 1 s for signalling circuit
                • 120 A - 500 ms for signalling circuit
                • 140 A - 100 ms for signalling circuit
                • 400 A 40 °C - 10 s for power circuit
                • 810 A 40 °C - 1 s for power circuit
                • 84 A 40 °C - 10 min for power circuit
                • 208 A 40 °C - 1 min for power circuit
                  • Associated fuse rating
                  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                  • 100 A gG at <= 690 V coordination type 1 for power circuit
                  • 100 A gG at <= 690 V coordination type 2 for power circuit
                    • Average impedance
                      1.5 mOhm - Ith 80 A 50 Hz for power circuit
                      [Ui] rated insulation voltage
                    • power circuit: 690 V conforming to IEC 60947-4-1
                    • signalling circuit: 690 V conforming to IEC 60947-1
                      • Electrical durability
                      • 1.8 Mcycles 42 A AC-3 at Ue <= 440 V
                      • 0.5 Mcycles 80 A AC-1 at Ue <= 440 V
                        • Power dissipation per pole
                        • 3.7 W AC-3
                        • 9.6 W AC-1
                          • Protective cover
                            with
                            Interlocking type
                            mechanical
                            Mounting support
                          • rail
                          • plate
                            • Standards
                            • EN/IEC 60947-4-1
                            • EN/IEC 60947-5-1
                            • UL 60947-4-1
                            • CSA C22.2 No 60947-4-1
                              • Product certifications
                              • CCC
                              • CSA
                              • EAC
                              • UL
                              • KC
                              • DNV-GL
                              • LROS (Lloyds register of shipping)
                                • Connections - terminals
                                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
                                • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
                                  • Tightening torque
                                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                  • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                  • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                    • Operating time
                                    • 55...65 ms closing
                                    • 20...120 ms opening (date code >= 17221)
                                    • 20...80 ms opening (date code >= 18011)
                                      • Safety reliability level
                                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                        • Mechanical durability
                                          6 Mcycles
                                          Maximum operating rate
                                          3600 cyc/h 60 °C
                                          Coil technology
                                          built-in bidirectional peak limiting
                                          Control circuit voltage limits
                                        • drop-out: <= 0.1 Uc (at 60 °C)
                                        • operational: 0.8...1.2 Uc (at 60 °C)
                                          • Inrush power in W
                                            11-11 W at 20 °C
                                            Hold-in power consumption in W
                                            0.5-0.5 W at 20 °C
                                            Heat dissipation
                                            0.5-0.5 W
                                            Auxiliary contacts type
                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency
                                              25...400 Hz
                                              Minimum switching current
                                              5 mA for signalling circuit
                                              Minimum switching voltage
                                              17 V for signalling circuit
                                              Non-overlap time
                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Insulation resistance
                                                > 10 MOhm for signalling circuit
                                                Compatibility code
                                                LC2D
                                                IP degree of protection
                                                IP20 front face conforming to IEC 60529
                                                Protective treatment
                                                TH conforming to IEC 60068-2-30
                                                Pollution degree
                                                3
                                                Ambient air temperature for operation
                                                -25-60 °C
                                                Ambient air temperature for storage
                                                -60-80 °C
                                                Permissible ambient air temperature around the device
                                                -40-70 °C at Uc
                                                Operating altitude
                                                3000 m without
                                                Fire resistance
                                                850 °C conforming to IEC 60695-2-1
                                                Flame retardance
                                                V1 conforming to UL 94
                                                Mechanical robustness
                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • vibrations contactor closed: 4 Gn, 5...300 Hz
                                              • shocks contactor open: 10 Gn for 11 ms
                                              • shocks contactor closed: 15 Gn for 11 ms
                                                • Height
                                                  122 mm
                                                  Width
                                                  119 mm
                                                  Depth
                                                  120 mm
                                                  Net weight
                                                  2.164 kg
                                                  Sustainable offer status
                                                  Green Premium product
                                                  EU RoHS Directive
                                                  Compliant
                                                  Mercury free
                                                  Yes
                                                  RoHS exemption information
                                                  Yes
                                                  China RoHS Regulation
                                                  Product out of China RoHS scope. Substance declaration for your information
                                                  Environmental Disclosure
                                                  ENVPEP1607010EN
                                                  Circularity Profile
                                                  ENVEOLI1607010EN
                                                  WEEE
                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                  Halogen content performance
                                                  Halogen free plastic parts & cables product
                                                  Warranty
                                                  18 months

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • Product Brochures

                                                  • CAD Files and Packs

                                                  • Technical Data Catalogues

                                                  • End of Life Manual

                                                  • Product Environmental

                                                  • Installation Instruction

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  What replaces LC1D50BD

                                                  Replacement LC1D50ABD

                                                  Looking for a LC1D50A.. with a 240v coil

                                                   Part code is LC1D50AU7

                                                  Do the Everlink reversing contactors come with electrical interlocking?

                                                  Issue:
                                                  Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                  Product line:
                                                  Tesys D LC1D40A, LC1D50A, LC1D65A

                                                  Environment:
                                                  Everlink, all voltage codes

                                                  Cause:
                                                  Old D2 version offered an electrical interlock kit

                                                  Resolution:
                                                  The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                  What is difference between LC1D50U7 and LC1D50AU7?

                                                  Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                  LC1D50AU7 has everlink terminals.
                                                  LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                  Whereas
                                                  LC1D50U7 contactors accommodate LRD33XX overloads.

                                                   

                                                  What mechanical interlock should I use with the LC1D50A••?

                                                  The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                                  See attached datasheet for futher information on the LAD4CM.

                                                  How Can the LC1D50AU7 Contactor be mounted?

                                                  Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                                                  See the attached datasheet for further information.

                                                  What is the Overload for LC1D50AU7 range is 37..50 Amps?

                                                  LRD350

                                                  What are the dimensions of LC1D40AB7 ?

                                                  Height 122 mm
                                                  Width 55 mm
                                                  Depth 120 mm
                                                  Product weight 1.4 kg

                                                  What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                                  The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                                  Is there an accessory to reduce the electrical noise in D line contactor with DC coil?

                                                  Issue:
                                                  What is the catalog number for the diode surpressors or noise reducer for an LC2D09BD?

                                                  Product Line:
                                                  Contactors and Starters - IEC

                                                  Environment:
                                                  LC*D09 - D32

                                                  Resolution:
                                                  Diode for Reduction of Electrical Noise in DC Contactor Coils, use LAD4DDL.

                                                  What are the coil voltage codes for the LC1D115 / LC2D115 and LC1D150 / LC2D150 TeSys contactor?

                                                  Issue:
                                                  LC1D115 / LC2D115 and LC1D150 / LC2D150

                                                  Product Line:
                                                  Tesys D line Contactors

                                                  Environment:
                                                  North America

                                                  Resolution:
                                                  The following list the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                  Note 1: LC1D150 contactors are only available with *7 coil codes.
                                                  Note 2: Coil Code ending number represents frequency rating as follows:
                                                  5 = 50 Hertz
                                                  6 = 60 Hertz
                                                  7 = 50/60 Hertz

                                                  AC Volts ___Code                DC Volts ___Code
                                                  24 ___ B5 or B6 or B7          12 ___ Not Avail.        
                                                  42 ___ D5 or D7                   24 ___ BD
                                                  48 ___ E5 or E6 or E7          36 ___ CD
                                                  110 ___ F5 or F6 or F7         48 ___ ED
                                                  115 ___ FE5 or FE7             60 ___ ND
                                                  120 ___ G6 or G7                72 ___ SD
                                                  127 ___ FC5 or FC7            110 ___ FD
                                                  208 ___ L6 or LE7               125 ___ GD
                                                  220 ___ M5 or M6 or M7       220 ___ MD
                                                  230 ___ P5 or P7                 250 ___ UD
                                                  240 ___ U5 or U6 or U7        440 ___ RD
                                                  277 ___ W6 or UE7                
                                                  380 ___ Q5 or Q6 or Q7                
                                                  400 ___ V5 or V7                
                                                  415 ___ N5 or N7                
                                                  440 ___ R5 or R6 or R7                
                                                  480 ___ T6 or T7                
                                                  500 ___ S5 or S7                


                                                   

                                                  What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                                  Issue:
                                                  LC*D09-38 coil consumption

                                                  Product Line:
                                                  Contactors and Overload Relays

                                                  Environment:
                                                  TeSys™ D Contactors and Overload Relays

                                                  Resolution:
                                                  The standard DC coil is 5.4 watts of consumption.