TeSys D reversing contactor-3P-AC3 440V 40A 48-130V ACDC coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

Catalogue Number: LC2D40AEHE
TeSys D reversing contactor-3P-AC3 440V 40A 48-130V ACDC coil
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
reversing contactor
Device short name
LC2D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-1
    • AC-3
      • Device presentation
        preassembled with reversing power busbar
        Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 60 A (at <60 °C) at <= 440 V AC-1 for power circuit
      • 40 A (at <60 °C) at <= 440 V AC-3 for power circuit
        • Motor power kW
        • 11 kW at 220...230 V AC 50 Hz
        • 18.5 kW at 380...400 V AC 50 Hz
        • 22 kW at 415 V AC 50 Hz
        • 22 kW at 440 V AC 50 Hz
        • 22 kW at 500 V AC 50 Hz
        • 30 kW at 660...690 V AC 50 Hz
          • Motor power hp
          • 3 hp at 115 V AC 60 Hz for 1 phase motors
          • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 30 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 30 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
            • AC at 50/60 Hz AC/DC electronic
            • DC AC/DC electronic
              • [Uc] control circuit voltage
              • 48...130 V AC 50/60 Hz
              • 48...130 V DC
                • Auxiliary contact composition
                  1 NO + 1 NC
                  [Uimp] rated impulse withstand voltage
                  6 kV conforming to IEC 60947
                  Overvoltage category
                  III
                  [Ith] conventional free air thermal current
                • 10 A (at 60 °C) for signalling circuit
                • 60 A (at 60 °C) for power circuit
                  • Irms rated making capacity
                  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • 800 A at 440 V for power circuit conforming to IEC 60947
                    • Rated breaking capacity
                      800 A at 440 V for power circuit conforming to IEC 60947
                      [Icw] rated short-time withstand current
                    • 100 A - 1 s for signalling circuit
                    • 120 A - 500 ms for signalling circuit
                    • 140 A - 100 ms for signalling circuit
                    • 320 A 40 °C - 10 s for power circuit
                    • 720 A 40 °C - 1 s for power circuit
                    • 72 A 40 °C - 10 min for power circuit
                    • 165 A 40 °C - 1 min for power circuit
                      • Associated fuse rating
                      • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                      • 80 A gG at <= 690 V coordination type 1 for power circuit
                      • 80 A gG at <= 690 V coordination type 2 for power circuit
                        • Average impedance
                          1.5 mOhm - Ith 60 A 50 Hz for power circuit
                          [Ui] rated insulation voltage
                        • power circuit: 690 V conforming to IEC 60947-4-1
                        • signalling circuit: 690 V conforming to IEC 60947-1
                          • Electrical durability
                          • 2 Mcycles 35 A AC-3 at Ue <= 440 V
                          • 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
                            • Power dissipation per pole
                            • 2.4 W AC-3
                            • 5.4 W AC-1
                              • Protective cover
                                with
                                Interlocking type
                                mechanical
                                Mounting support
                              • rail
                              • plate
                                • Standards
                                • EN/IEC 60947-4-1
                                • EN/IEC 60947-5-1
                                • UL 60947-4-1
                                • CSA C22.2 No 60947-4-1
                                  • Product certifications
                                  • CCC
                                  • CSA
                                  • EAC
                                  • UL
                                  • KC
                                  • DNV-GL
                                  • LROS (Lloyds register of shipping)
                                    • Connections - terminals
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                    • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                    • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                    • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                    • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
                                    • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
                                      • Tightening torque
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                      • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                        • Operating time
                                        • 55...65 ms closing
                                        • 20...120 ms opening (date code >= 17221)
                                        • 20...80 ms opening (date code >= 18011)
                                          • Safety reliability level
                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Mechanical durability
                                              6 Mcycles
                                              Maximum operating rate
                                              3600 cyc/h 60 °C
                                              Coil technology
                                              built-in bidirectional peak limiting
                                              Control circuit voltage limits
                                            • drop-out: <= 0.1 Uc (at 60 °C)
                                            • operational: 0.85...1.1 Uc (at 60 °C)
                                              • Inrush power in VA
                                                23-23 VA 50/60 Hz (at 20 °C)
                                                Inrush power in W
                                                19-19 W at 20 °C
                                                Hold-in power consumption in VA
                                                1.4-1.4 VA (at 20 °C) 50/60 Hz
                                                Hold-in power consumption in W
                                                0.9-0.9 W at 20 °C
                                                Heat dissipation
                                                0.9-0.9 W at 50/60 Hz
                                                Auxiliary contacts type
                                              • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                              • type mirror contact 1 NC conforming to IEC 60947-4-1
                                                • Signalling circuit frequency
                                                  25...400 Hz
                                                  Minimum switching current
                                                  5 mA for signalling circuit
                                                  Minimum switching voltage
                                                  17 V for signalling circuit
                                                  Non-overlap time
                                                • 1.5 ms on de-energisation between NC and NO contact
                                                • 1.5 ms on energisation between NC and NO contact
                                                  • Insulation resistance
                                                    > 10 MOhm for signalling circuit
                                                    Compatibility code
                                                    LC2D
                                                    IP degree of protection
                                                    IP20 front face conforming to IEC 60529
                                                    Protective treatment
                                                    TH conforming to IEC 60068-2-30
                                                    Pollution degree
                                                    3
                                                    Ambient air temperature for operation
                                                    -25-60 °C
                                                    Ambient air temperature for storage
                                                    -60-80 °C
                                                    Permissible ambient air temperature around the device
                                                    -40-70 °C at Uc
                                                    Operating altitude
                                                    3000 m without
                                                    Fire resistance
                                                    850 °C conforming to IEC 60695-2-1
                                                    Flame retardance
                                                    V1 conforming to UL 94
                                                    Mechanical robustness
                                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                  • shocks contactor open: 10 Gn for 11 ms
                                                  • shocks contactor closed: 15 Gn for 11 ms
                                                    • Height
                                                      122 mm
                                                      Width
                                                      119 mm
                                                      Depth
                                                      120 mm
                                                      Net weight
                                                      2.154 kg
                                                      Sustainable offer status
                                                      Green Premium product
                                                      EU RoHS Directive
                                                      Compliant
                                                      Mercury free
                                                      Yes
                                                      RoHS exemption information
                                                      Yes
                                                      China RoHS Regulation
                                                      Product out of China RoHS scope. Substance declaration for your information
                                                      Environmental Disclosure
                                                      ENVPEP1607010EN
                                                      Circularity Profile
                                                      ENVEOLI1607010EN
                                                      WEEE
                                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                      Halogen content performance
                                                      Halogen free plastic parts & cables product
                                                      Warranty
                                                      18 months

                                                      Documents & downloads

                                                      hide show
                                                      Filter items
                                                      • All

                                                      • Product Brochures

                                                      • CAD Files and Packs

                                                      • Technical Data Catalogues

                                                      • End of Life Manual

                                                      • Product Environmental

                                                      • Installation Instruction

                                                      • Declaration of Conformity

                                                      Frequently Asked Questions

                                                      hide show

                                                      Are 21 volt replacement control coils available for LC2D4011?

                                                      Issue:
                                                      LC2D4011 replacement coil

                                                      Prodcut Line:
                                                      Contactors and Overload Relays

                                                      Product Line:
                                                      TeSys™ D Contactors and Overload Relays

                                                      Resolution:
                                                      21VAC coils are not an option on these reversing change over contactors.
                                                      We do offer the B6 or B7 which is 24VAC.  The tolerance on the 24V coil is 85 to 110%.  So the 24VAC coil will work down to 20.4VAC. 

                                                      Note the LC2D4011 series is obsolete.

                                                      What is the code for a 40A 110VAC contactor ?

                                                      LC1D40AF7

                                                      Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                      No, correct kit is a LAD9R3.

                                                      What is the code for the newer version of the LC1D40U7

                                                      That has been replaced with the Everlink LC1D40AU7

                                                      Do the Everlink reversing contactors come with electrical interlocking?

                                                      Issue:
                                                      Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                      Product line:
                                                      Tesys D LC1D40A, LC1D50A, LC1D65A

                                                      Environment:
                                                      Everlink, all voltage codes

                                                      Cause:
                                                      Old D2 version offered an electrical interlock kit

                                                      Resolution:
                                                      The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                      What is the color scheme of the Tesys D-Line contactors?

                                                      Issue:
                                                      Looking for different color scheme of the Tesys D-Line contactors.

                                                      Product Line:
                                                      Tesys D Contactors

                                                      Environment:
                                                      LC1D contactors

                                                      Resolution:
                                                      Beige and dark gray.
                                                       

                                                      What are the dimensions of LC1D40AB7 ?

                                                      Height 122 mm
                                                      Width 55 mm
                                                      Depth 120 mm
                                                      Product weight 1.4 kg

                                                      What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                                      The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                                      Are contactors LC1D38.. and LC1D40A.. the same size?

                                                      No the two contactor are not the same size, LC1D40A.. is bigger.

                                                      LC1D38N7
                                                      TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 415 V AC 50/60 Hz coil     LC1D40AN7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 415 V AC 50/60 Hz coil

                                                      For more information see:
                                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D38N7;
                                                      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D40AN7




                                                       

                                                      Are the D-Line contactors rated to break DC voltages?

                                                      Issue: 
                                                      Can the TeSys D line be used to control DC loads? 

                                                      Product Line:
                                                      Tesys D contactors

                                                      Environment:
                                                      Products sold and used in the United States
                                                       
                                                      Cause:
                                                       DC power circuit
                                                       
                                                      Resolution:
                                                       
                                                      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                      Devices are suitable but not UL Listed for DC applications.

                                                      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                       

                                                      What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                      Issue:
                                                      Tesys D SCCR

                                                      Product Line:
                                                      Contactors and Overload Relays

                                                      Environment:
                                                      TeSys™ D Contactors and Overload Relays
                                                       
                                                      Resolution:
                                                      The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                      They are as follows:
                                                      Horsepower SCCR (A)

                                                      0 thru 1 1,000
                                                      1 thru 50 5,000
                                                      51 thru 200 10,000
                                                      201 thru 400 18,000
                                                      401 thru 600 30,000
                                                      601 thru 900 42,000
                                                      901 thru 1600 85,000
                                                      1601+ 100,000

                                                      What does the (3) designate in the part number LC1D123G7?

                                                      For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                                      CTA-ID : 2053127
                                                      Show More