TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

TeSys D Reversing Contactor-3 Pole AC3 <= 440V 40A, 48 - 130V ACDC Coil

Item Number: LC2D40AEHE

Retail
$4,055.62
RRP (Inc. GST)

Product Dimensions

Width icon

Width119 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

reversing contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Device presentation

preassembled with reversing power busbar

[Ue] rated operational voltage

power circuit: 690 V AC 25...400 Hz

[Ie] rated operational current

  • 60 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 40 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • Electrical durability

    • 2 Mcycles 35 A AC-3 at Ue <= 440 V
    • 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
      • Mounting support

      • rail
      • plate
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
              • Mechanical durability

                6 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for storage

                -60-80 °C

                Height

                122 mm

                Width

                119 mm

                Depth

                120 mm

                Net weight

                2.154 kg

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP1607010EN

                Circularity Profile

                ENVEOLI1607010EN

                Others

                Product name

                TeSys D Green

                Device short name

                LC2D

                Contactor application

              • motor control
              • resistive load
                • Utilisation category

                • AC-1
                • AC-3
                  • Poles description

                    3P

                    Pole contact composition

                    3 NO

                    Motor power kW

                  • 11 kW at 220...230 V AC 50 Hz
                  • 18.5 kW at 380...400 V AC 50 Hz
                  • 22 kW at 415 V AC 50 Hz
                  • 22 kW at 440 V AC 50 Hz
                  • 22 kW at 500 V AC 50 Hz
                  • 30 kW at 660...690 V AC 50 Hz
                    • Motor power hp

                    • 3 hp at 115 V AC 60 Hz for 1 phase motors
                    • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
                    • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
                    • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
                    • 30 hp at 460/480 V AC 60 Hz for 3 phases motors
                    • 30 hp at 575/600 V AC 60 Hz for 3 phases motors
                      • Control circuit type

                      • AC at 50/60 Hz AC/DC electronic
                      • DC AC/DC electronic
                        • [Uc] control circuit voltage

                        • 48...130 V AC 50/60 Hz
                        • 48...130 V DC
                          • Auxiliary contact composition

                            1 NO + 1 NC

                            [Uimp] rated impulse withstand voltage

                            6 kV conforming to IEC 60947

                            Overvoltage category

                            III

                            [Ith] conventional free air thermal current

                          • 10 A (at 60 °C) for signalling circuit
                          • 60 A (at 60 °C) for power circuit
                            • Irms rated making capacity

                            • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                            • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                            • 800 A at 440 V for power circuit conforming to IEC 60947
                              • Rated breaking capacity

                                800 A at 440 V for power circuit conforming to IEC 60947

                                [Icw] rated short-time withstand current

                              • 100 A - 1 s for signalling circuit
                              • 120 A - 500 ms for signalling circuit
                              • 140 A - 100 ms for signalling circuit
                              • 320 A 40 °C - 10 s for power circuit
                              • 720 A 40 °C - 1 s for power circuit
                              • 72 A 40 °C - 10 min for power circuit
                              • 165 A 40 °C - 1 min for power circuit
                                • Associated fuse rating

                                • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                                • 80 A gG at <= 690 V coordination type 1 for power circuit
                                • 80 A gG at <= 690 V coordination type 2 for power circuit
                                  • Average impedance

                                    1.5 mOhm - Ith 60 A 50 Hz for power circuit

                                    [Ui] rated insulation voltage

                                  • power circuit: 690 V conforming to IEC 60947-4-1
                                  • signalling circuit: 690 V conforming to IEC 60947-1
                                    • Power dissipation per pole

                                    • 2.4 W AC-3
                                    • 5.4 W AC-1
                                      • Protective cover

                                        with

                                        Interlocking type

                                        mechanical

                                        Tightening torque

                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                      • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                      • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                        • Operating time

                                        • 55...65 ms closing
                                        • 20...120 ms opening (date code >= 17221)
                                        • 20...80 ms opening (date code >= 18011)
                                          • Safety reliability level

                                          • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                          • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                            • Maximum operating rate

                                              3600 cyc/h 60 °C

                                              Coil technology

                                              built-in bidirectional peak limiting

                                              Inrush power in VA

                                              23-23 VA 50/60 Hz (at 20 °C)

                                              Inrush power in W

                                              19-19 W at 20 °C

                                              Hold-in power consumption in VA

                                              1.4-1.4 VA (at 20 °C) 50/60 Hz

                                              Hold-in power consumption in W

                                              0.9-0.9 W at 20 °C

                                              Heat dissipation

                                              0.9-0.9 W at 50/60 Hz

                                              Auxiliary contacts type

                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency

                                                25...400 Hz

                                                Minimum switching current

                                                5 mA for signalling circuit

                                                Minimum switching voltage

                                                17 V for signalling circuit

                                                Non-overlap time

                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Compatibility code

                                                  LC2D

                                                  Protective treatment

                                                  TH conforming to IEC 60068-2-30

                                                  Pollution degree

                                                  3

                                                  Operating altitude

                                                  3000 m without derating

                                                  Fire resistance

                                                  850 °C conforming to IEC 60695-2-1

                                                  Flame retardance

                                                  V1 conforming to UL 94

                                                  Mechanical robustness

                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Package 1 Weight

                                                    2.154 kg

                                                    Package 1 Height

                                                    1.4 dm

                                                    Package 1 width

                                                    1.62 dm

                                                    Package 1 Length

                                                    1.98 dm

                                                    WEEE

                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                    Halogen content performance

                                                    Halogen free plastic parts & cables product
                                                    Show all specifications

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • CAD Files and Packs

                                                    • Technical Data Catalogues

                                                    • Product Environmental

                                                    • End of Life Manual

                                                    • Installation Instruction

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    Are 21 volt replacement control coils available for LC2D4011?

                                                    Issue:
                                                    LC2D4011 replacement coil

                                                    Prodcut Line:
                                                    Contactors and Overload Relays

                                                    Product Line:
                                                    TeSys™ D Contactors and Overload Relays

                                                    Resolution:
                                                    21VAC coils are not an option on these reversing change over contactors.
                                                    We do offer the B6 or B7 which is 24VAC.  The tolerance on the 24V coil is 85 to 110%.  So the 24VAC coil will work down to 20.4VAC. 

                                                    Note the LC2D4011 series is obsolete.

                                                    What is the code for a 40A 110VAC contactor ?

                                                    LC1D40AF7

                                                    Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                    No, correct kit is a LAD9R3.

                                                    What is the code for the newer version of the LC1D40U7

                                                    That has been replaced with the Everlink LC1D40AU7

                                                    Do the Everlink reversing contactors come with electrical interlocking?

                                                    Issue:
                                                    Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                    Product line:
                                                    Tesys D LC1D40A, LC1D50A, LC1D65A

                                                    Environment:
                                                    Everlink, all voltage codes

                                                    Cause:
                                                    Old D2 version offered an electrical interlock kit

                                                    Resolution:
                                                    The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                    What is the color scheme of the Tesys D-Line contactors?

                                                    Issue:
                                                    Looking for different color scheme of the Tesys D-Line contactors.

                                                    Product Line:
                                                    Tesys D Contactors

                                                    Environment:
                                                    LC1D contactors

                                                    Resolution:
                                                    Beige and dark gray.
                                                     

                                                    What are the dimensions of LC1D40AB7 ?

                                                    Height 122 mm
                                                    Width 55 mm
                                                    Depth 120 mm
                                                    Product weight 1.4 kg

                                                    What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                                    The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                                    Are contactors LC1D38.. and LC1D40A.. the same size?

                                                    No the two contactor are not the same size, LC1D40A.. is bigger.

                                                    LC1D38N7
                                                    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 415 V AC 50/60 Hz coil     LC1D40AN7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 415 V AC 50/60 Hz coil

                                                    For more information see:
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D38N7;
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D40AN7




                                                     

                                                    Are the D-Line contactors rated to break DC voltages?

                                                    Issue: 
                                                    Can the TeSys D line be used to control DC loads? 

                                                    Product Line:
                                                    Tesys D contactors

                                                    Environment:
                                                    Products sold and used in the United States
                                                     
                                                    Cause:
                                                     DC power circuit
                                                     
                                                    Resolution:
                                                     
                                                    Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                    Devices are suitable but not UL Listed for DC applications.

                                                    More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                     

                                                    What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                    Issue:
                                                    Tesys D SCCR

                                                    Product Line:
                                                    Contactors and Overload Relays

                                                    Environment:
                                                    TeSys™ D Contactors and Overload Relays
                                                     
                                                    Resolution:
                                                    The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                    They are as follows:
                                                    Horsepower SCCR (A)

                                                    0 thru 1 1,000
                                                    1 thru 50 5,000
                                                    51 thru 200 10,000
                                                    201 thru 400 18,000
                                                    401 thru 600 30,000
                                                    601 thru 900 42,000
                                                    901 thru 1600 85,000
                                                    1601+ 100,000

                                                    What does the (3) designate in the part number LC1D123G7?

                                                    For spring termination versions, add (3) to the catalog number prior to adding the voltage code. (ex. LC1D12G7 becomes a LC1D123G7 or LC1D40AG7 becomes LC1D40A3G7). This applies only for the LC1D09 - LC1D65A contactors. Note: For the LC1D40A to D65A, the spring terminals are only on the control terminations and not on power terminations.



                                                    CTA-ID : 2053127
                                                    Show More