Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-3
    • AC-1
    • AC-4
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: 1000 V AC 25...400 Hz
        [Ie] rated operational current
      • 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
      • 125 A (at <60 °C) at <= 690 V AC-1 for power circuit
        • Motor power kW
        • 25 kW at 220...230 V AC 50 Hz (AC-3)
        • 45 kW at 380...400 V AC 50 Hz (AC-3)
        • 45 kW at 415...440 V AC 50 Hz (AC-3)
        • 55 kW at 500 V AC 50 Hz (AC-3)
        • 45 kW at 660...690 V AC 50 Hz (AC-3)
        • 45 kW at 1000 V AC 50 Hz (AC-3)
          • Motor power hp
          • 7.5 hp at 115 V AC 60 Hz for 1 phase motors
          • 15 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 25 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 30 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 60 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 60 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
              DC wide range
              [Uc] control circuit voltage
              12 V DC
              Auxiliary contact composition
              1 NO + 1 NC
              [Uimp] rated impulse withstand voltage
              8 kV conforming to IEC 60947
              Overvoltage category
              III
              [Ith] conventional free air thermal current
            • 10 A (at 60 °C) for signalling circuit
            • 125 A (at 60 °C) for power circuit
              • Irms rated making capacity
              • 1100 A at 440 V AC for power circuit conforming to IEC 60947
              • 140 A AC for signalling circuit conforming to IEC 60947-5-1
              • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • Rated breaking capacity
                  1100 A at 440 V for power circuit conforming to IEC 60947
                  [Icw] rated short-time withstand current
                • 1100 A 40 °C - 1 s for power circuit
                • 800 A 40 °C - 10 s for power circuit
                • 400 A 40 °C - 1 min for power circuit
                • 135 A 40 °C - 10 min for power circuit
                • 140 A - 100 ms for signalling circuit
                • 120 A - 500 ms for signalling circuit
                • 100 A - 1 s for signalling circuit
                  • Associated fuse rating
                  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                  • 200 A gG at <= 690 V coordination type 1 for power circuit
                  • 160 A gG at <= 690 V coordination type 2 for power circuit
                    • Average impedance
                      0.8 mOhm - Ith 125 A 50 Hz for power circuit
                      [Ui] rated insulation voltage
                    • power circuit: 1000 V conforming to IEC 60947-4-1
                    • signalling circuit: 690 V conforming to IEC 60947-1
                      • Electrical durability
                      • 1.2 Mcycles 95 A AC-3
                      • 1.3 Mcycles 125 A AC-1
                        • Power dissipation per pole
                        • 12.5 W AC-1
                        • 7.2 W AC-3
                          • Protective cover
                            with
                            Mounting support
                          • rail
                          • plate
                            • Standards
                            • EN/IEC 60947-1
                            • EN/IEC 60947-4-1
                            • EN/IEC 60947-5-1
                            • GB/T 14048.4
                              • Product certifications
                              • IECEE CB Scheme
                              • CCC
                              • EAC
                              • LROS (Lloyds register of shipping)
                              • RINA
                              • BV
                              • DNV-GL
                                • Connections - terminals
                                • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                • control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
                                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                • power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end
                                • power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end
                                • power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end
                                • power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end
                                • power circuit: connector 1 cable(s) 4-50 mm²solid without cable end
                                • power circuit: connector 2 cable(s) 4-25 mm²solid without cable end
                                  • Tightening torque
                                  • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                  • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                  • power circuit: 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
                                  • power circuit: 9 N.m - on connector hexagonal screw head 4 mm
                                    • Operating time
                                    • 95...130 ms closing
                                    • 20...35 ms opening
                                      • Safety reliability level
                                      • B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
                                      • B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
                                        • Mechanical durability
                                          10 Mcycles
                                          Maximum operating rate
                                          3600 cyc/h 60 °C
                                          Coil technology
                                          without built-in suppressor module
                                          Time constant
                                          75 ms
                                          Inrush power in W
                                          22-22 W (at 20 °C)
                                          Hold-in power consumption in W
                                          22-22 W at 20 °C
                                          Auxiliary contacts type
                                        • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                        • type mirror contact 1 NC conforming to IEC 60947-4-1
                                          • Signalling circuit frequency
                                            25...400 Hz
                                            Minimum switching current
                                            5 mA for signalling circuit
                                            Minimum switching voltage
                                            17 V for signalling circuit
                                            Non-overlap time
                                          • 1.5 ms on de-energisation between NC and NO contact
                                          • 1.5 ms on energisation between NC and NO contact
                                            • Insulation resistance
                                              > 10 MOhm for signalling circuit
                                              Contact compatibility
                                              M9
                                              Compatibility code
                                              LC1D
                                              IP degree of protection
                                              IP20 front face conforming to IEC 60529
                                              Protective treatment
                                              TH conforming to IEC 60068-2-30
                                              Pollution degree
                                              3
                                              Ambient air temperature for storage
                                              -60-80 °C
                                              Operating altitude
                                              0...3000 m
                                              Fire resistance
                                              850 °C conforming to IEC 60695-2-1
                                              Flame retardance
                                              V1 conforming to UL 94
                                              Mechanical robustness
                                            • vibrations contactor open: 2 Gn, 5...300 Hz
                                            • shocks contactor open: 8 Gn for 11 ms
                                            • vibrations contactor closed: 3 Gn, 5...300 Hz
                                            • shocks contactor closed: 10 Gn for 11 ms
                                              • Height
                                                127 mm
                                                Width
                                                85 mm
                                                Depth
                                                186 mm
                                                Net weight
                                                2.61 kg
                                                Package 1 Weight
                                                2.624 kg
                                                Package 1 Height
                                                2.1 dm
                                                Package 1 width
                                                1.35 dm
                                                Package 1 Length
                                                1 dm
                                                Sustainable offer status
                                                Green Premium product
                                                REACh free of SVHC
                                                Yes
                                                EU RoHS Directive
                                                Compliant
                                                Toxic heavy metal free
                                                Yes
                                                Mercury free
                                                Yes
                                                RoHS exemption information
                                                Yes
                                                China RoHS Regulation
                                                 Pro-active China RoHS declaration (out of China RoHS legal scope)
                                                Environmental Disclosure
                                                ENVPEP110205EN
                                                WEEE
                                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                PVC free
                                                Yes
                                                Warranty
                                                18 months

                                                Documents & downloads

                                                hide show
                                                Filter items
                                                • All

                                                • CAD Files and Packs

                                                • Product Brochures

                                                • Technical Data Catalogues

                                                • Product Environmental

                                                • Installation Instruction

                                                • Certificates (MSDS)

                                                • Declaration of Conformity

                                                Frequently Asked Questions

                                                hide show

                                                What is the altitude derating for a TeSys D-Line contactor?

                                                Issue:​
                                                What is the altitude derating for a TeSys D-Line contactor?

                                                Product Line:
                                                Digest 177 Section 18 : Contactors and Starters, IEC

                                                Environment:
                                                North American Products

                                                Resolution:
                                                The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                Voltage
                                                3500m x 0.90
                                                4000m x 0.80
                                                4500m x 0.70
                                                5000m x 0.60

                                                Current
                                                3500m x 0.92
                                                4000m x 0.90
                                                4500m x 0.88
                                                5000m x 0.86

                                                For example, an LC1D80 at 5000 meters:
                                                - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                 

                                                What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                Issue:
                                                Identifying maximum voltage of an LC1D contactor

                                                Product Line:
                                                TeSys D Contactors

                                                Environment:
                                                IEC contactors and starters used in North America

                                                Cause:
                                                n/a

                                                Resolution:
                                                IThe maximum voltage per UL and CSA is 600VAC. 
                                                 

                                                What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                Issue:
                                                Identifying power terminal lug data for the D2 style contactors

                                                Product Line:
                                                Tesys D line contactors

                                                Environment:
                                                Products sold and used in the United States

                                                Cause:
                                                Power terminal lug data required

                                                Resolution:
                                                For contactors with screw clamp terminals:
                                                stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                Issue:
                                                Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                Product Line:
                                                IEC Contactors and Starters

                                                Environment:
                                                Products sold and used in the United States

                                                Cause:
                                                Replacement coil is needed

                                                Resolution:
                                                DC replacement coils are not available.
                                                AC Coils are 50/60 hertz for voltages as listed below:

                                                Volts - Part Number
                                                12 ____ LXD1J7
                                                21 ____ LXD1Z7
                                                24 ____ LXD1B7
                                                32 ____ LXD1C7
                                                36 ____ LXD1CC7
                                                42 ____ LXD1D7
                                                48 ____ LXD1E7
                                                60 ____ LXD1EE7
                                                100 ___ LXD1K7 ( never brought to North America )
                                                110 ___ LXD1F7
                                                115 ___ LXD1FE7
                                                120 ___ LXD1G7
                                                127 ___ LXD1FC7
                                                200 ___ LXD1L7
                                                208 ___ LXD1LE7
                                                220 ___ LXD1M7
                                                230 ___ LXD1P7
                                                240 ___ LXD1U7
                                                277 ___ LXD1W7
                                                380 ___ LXD1Q7
                                                400 ___ LXD1V7
                                                415 ___ LXD1N7
                                                440 ___ LXD1R7
                                                480 ___ LXD1T7
                                                575 ___ LXD1SC7
                                                600 ___ LXD1X7
                                                690 ___ LXD1Y7


                                                Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                Issue:
                                                Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                Product Line: 
                                                Tesys D Contactors

                                                Environment:
                                                IEC contactors

                                                Resolution:
                                                The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                 

                                                Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                Issue:
                                                Mounting adaptor for GV2 and LC1D contactor

                                                Product Line:
                                                Motor Starters and Protectors

                                                Environment:
                                                TeSys GV Manual Starter and Protectors
                                                Tesys D Contactors
                                                 
                                                Resolution:
                                                The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                What is the code for a complete LC1D95 with a 415vAC Coil?

                                                   The code for the contactor is LC1D95N7

                                                Are the D-Line contactors rated to break DC voltages?

                                                Issue: 
                                                Can the TeSys D line be used to control DC loads? 

                                                Product Line:
                                                Tesys D contactors

                                                Environment:
                                                Products sold and used in the United States
                                                 
                                                Cause:
                                                 DC power circuit
                                                 
                                                Resolution:
                                                 
                                                Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                Devices are suitable but not UL Listed for DC applications.

                                                More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                 

                                                What overload to suit LC1D95U7 need to be 80-104A

                                                 Part code for the overload LRD3365

                                                What is the color scheme of the Tesys D-Line contactors?

                                                Issue:
                                                Looking for different color scheme of the Tesys D-Line contactors.

                                                Product Line:
                                                Tesys D Contactors

                                                Environment:
                                                LC1D contactors

                                                Resolution:
                                                Beige and dark gray.
                                                 

                                                what is the replacement for an LC1D2510 contactor with 240v coil ?

                                                The replacement is an LC1D25U7

                                                What are the stand alone short circuit current ratings on the LC1D** contactors?

                                                Issue:
                                                Tesys D SCCR

                                                Product Line:
                                                Contactors and Overload Relays

                                                Environment:
                                                TeSys™ D Contactors and Overload Relays
                                                 
                                                Resolution:
                                                The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                                                They are as follows:
                                                Horsepower SCCR (A)

                                                0 thru 1 1,000
                                                1 thru 50 5,000
                                                51 thru 200 10,000
                                                201 thru 400 18,000
                                                401 thru 600 30,000
                                                601 thru 900 42,000
                                                901 thru 1600 85,000
                                                1601+ 100,000