TeSys LC1D contactor, 3 poles, power connections by EverLink, with cover, 40A to 65A

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 65A, 250VDC, Standard Coil

Catalogue Number: LC1D65AUD
TeSys LC1D contactor, 3 poles, power connections by EverLink, with cover, 40A to 65A
Retail
$2,501.61
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-1
    • AC-4
    • AC-3
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
        • 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
          • Motor power kW
          • 11 kW at 400 V AC 50/60 Hz (AC-4)
          • 18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 30 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 37 kW at 500 V AC 50/60 Hz (AC-3)
          • 37 kW at 660...690 V AC 50/60 Hz (AC-3)
            • Motor power hp
            • 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 5 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                DC standard
                [Uc] control circuit voltage
                250 V DC
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 80 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 1000 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    1000 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 520 A 40 °C - 10 s for power circuit
                  • 900 A 40 °C - 1 s for power circuit
                  • 110 A 40 °C - 10 min for power circuit
                  • 260 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 125 A gG at <= 690 V coordination type 1 for power circuit
                    • 125 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        1.5 mOhm - Ith 80 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                      • power circuit: 690 V conforming to IEC 60947-4-1
                        • Electrical durability
                        • 0.5 Mcycles 80 A AC-1 at Ue <= 440 V
                        • 1.45 Mcycles 65 A AC-3 at Ue <= 440 V
                          • Power dissipation per pole
                          • 9.6 W AC-1
                          • 6.3 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • rail
                            • plate
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • CCC
                                • CSA
                                • UL
                                • GOST
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
                                  • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid without cable end
                                  • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid without cable end
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                    • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                      • Operating time
                                      • 42.5...57.5 ms closing
                                      • 16...24 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            10 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting diode suppressor
                                            Control circuit voltage limits
                                          • drop-out: 0.1...0.3 Uc DC (at 60 °C)
                                          • operational: 0.75...1.25 Uc DC (at 60 °C)
                                            • Time constant
                                              34 ms
                                              Inrush power in W
                                              19-19 W (at 20 °C)
                                              Hold-in power consumption in W
                                              7.4-7.4 W at 20 °C
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Contact compatibility
                                                  M4
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -5-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                • shocks contactor open: 10 Gn for 11 ms
                                                  • Height
                                                    122 mm
                                                    Width
                                                    55 mm
                                                    Depth
                                                    120 mm
                                                    Net weight
                                                    0.935 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    REACh Regulation
                                                    Free of Substances of Very High Concern above the threshold
                                                    REACh free of SVHC
                                                    Yes
                                                    EU RoHS Directive
                                                    Compliant
                                                    Toxic heavy metal free
                                                    Yes
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    X
                                                    Environmental Disclosure
                                                    ENVPEP1503009EN
                                                    Circularity Profile
                                                    ENVEOLI1503009EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    California proposition 65
                                                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • CAD Files and Packs

                                                    • Product Brochures

                                                    • Technical Data Catalogues

                                                    • Installation Instruction

                                                    • Data Bulletin

                                                    • Product Environmental

                                                    • End of Life Manual

                                                    • Certificates (MSDS)

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum voltage of an LC1D contactor

                                                    Product Line:
                                                    TeSys D Contactors

                                                    Environment:
                                                    IEC contactors and starters used in North America

                                                    Cause:
                                                    n/a

                                                    Resolution:
                                                    IThe maximum voltage per UL and CSA is 600VAC. 
                                                     

                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Issue:​
                                                    What is the altitude derating for a TeSys D-Line contactor?

                                                    Product Line:
                                                    Digest 177 Section 18 : Contactors and Starters, IEC

                                                    Environment:
                                                    North American Products

                                                    Resolution:
                                                    The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                    Voltage
                                                    3500m x 0.90
                                                    4000m x 0.80
                                                    4500m x 0.70
                                                    5000m x 0.60

                                                    Current
                                                    3500m x 0.92
                                                    4000m x 0.90
                                                    4500m x 0.88
                                                    5000m x 0.86

                                                    For example, an LC1D80 at 5000 meters:
                                                    - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                    - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                     

                                                    What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                    Issue:
                                                    Identifying power terminal lug data for the D2 style contactors

                                                    Product Line:
                                                    Tesys D line contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Power terminal lug data required

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                    stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                    solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                    What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                                    The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                                    see data sheets for comparrisons...
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                                    User-added image.................User-added image

                                                    Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                    Issue:
                                                    Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                    Product Line: 
                                                    Tesys D Contactors

                                                    Environment:
                                                    IEC contactors

                                                    Resolution:
                                                    The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                     

                                                    Do the Everlink reversing contactors come with electrical interlocking?

                                                    Issue:
                                                    Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                    Product line:
                                                    Tesys D LC1D40A, LC1D50A, LC1D65A

                                                    Environment:
                                                    Everlink, all voltage codes

                                                    Cause:
                                                    Old D2 version offered an electrical interlock kit

                                                    Resolution:
                                                    The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                    What replaces LC1D50BD

                                                    Replacement LC1D50ABD

                                                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                    Issue:
                                                    Mounting adaptor for GV2 and LC1D contactor

                                                    Product Line:
                                                    Motor Starters and Protectors

                                                    Environment:
                                                    TeSys GV Manual Starter and Protectors
                                                    Tesys D Contactors
                                                     
                                                    Resolution:
                                                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                    What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                                                    Issue:
                                                    AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                                                    Product Line:
                                                    Tesys D Replacement Parts

                                                    Environment:
                                                    TeSys™ D AC Coils

                                                    Resolution:

                                                    What is the replacement for the Tesys D Contactor LC1D65U7?

                                                    use the new code - LC1D65AU7
                                                    3P EVERLINK CONTACTOR 65A 30kW AC3 240VAC
                                                    See link for Data Sheet:
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=LC1D65AU7

                                                    What is the replacement code for the LC1D633Q?

                                                    The new code for this is LC1D65AU7.

                                                    What is the overload for LC1D65AU7 Contactor, when rating is 20-25A ?

                                                    17-25 Amps = LRD325
                                                    23-32 Amps =LRD332
                                                    Show More