TeSys D Contactor-3 Pole AC3 <= 440V 50A,100 - 250V ACDC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 50A,100 - 250V ACDC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 50A,100 - 250V ACDC Coil

Item Number: LC1D50AKUE

Retail
$2,258.52
RRP (Inc. GST)

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

  • 80 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 50 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • Electrical durability

    • 1.8 Mcycles 42 A AC-3 at Ue <= 440 V
    • 0.5 Mcycles 80 A AC-1 at Ue <= 440 V
      • Mounting support

      • rail
      • plate
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
              • Mechanical durability

                6 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for storage

                -60-80 °C

                Height

                122 mm

                Width

                55 mm

                Depth

                120 mm

                Net weight

                0.997 kg

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP1607010EN

                Circularity Profile

                ENVEOLI1607010EN

                Others

                Product name

                TeSys D Green

                Device short name

                LC1D

                Contactor application

              • motor control
              • resistive load
                • Utilisation category

                • AC-1
                • AC-3
                  • Poles description

                    3P

                    Pole contact composition

                    3 NO

                    Motor power kW

                  • 15 kW at 220...230 V AC 50 Hz (AC-3)
                  • 22 kW at 380...400 V AC 50 Hz (AC-3)
                  • 25 kW at 415 V AC 50 Hz (AC-3)
                  • 30 kW at 440 V AC 50 Hz (AC-3)
                  • 30 kW at 500 V AC 50 Hz (AC-3)
                  • 33 kW at 660...690 V AC 50 Hz (AC-3)
                    • Motor power hp

                    • 3 hp at 115 V AC 60 Hz for 1 phase motors
                    • 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors
                    • 15 hp at 200/208 V AC 60 Hz for 3 phases motors
                    • 15 hp at 230/240 V AC 60 Hz for 3 phases motors
                    • 40 hp at 460/480 V AC 60 Hz for 3 phases motors
                    • 40 hp at 575/600 V AC 60 Hz for 3 phases motors
                      • Control circuit type

                        AC/DC at 50/60 Hz AC/DC electronic

                        [Uc] control circuit voltage

                      • 100...250 V AC 50/60 Hz
                      • 100...250 V DC
                        • Coil type

                          AC/DC electronic

                          Auxiliary contact composition

                          1 NO + 1 NC

                          [Uimp] rated impulse withstand voltage

                          6 kV conforming to IEC 60947

                          Overvoltage category

                          III

                          [Ith] conventional free air thermal current

                        • 80 A (at 60 °C) for power circuit
                        • 10 A (at 60 °C) for signalling circuit
                          • Irms rated making capacity

                          • 900 A at 440 V for power circuit conforming to IEC 60947
                          • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                          • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                            • Rated breaking capacity

                              900 A at 440 V for power circuit conforming to IEC 60947

                              [Icw] rated short-time withstand current

                            • 100 A - 1 s for signalling circuit
                            • 120 A - 500 ms for signalling circuit
                            • 140 A - 100 ms for signalling circuit
                            • 84 A 40 °C - 10 min for power circuit
                            • 208 A 40 °C - 1 min for power circuit
                            • 400 A 40 °C - 10 s for power circuit
                            • 810 A 40 °C - 1 s for power circuit
                              • Associated fuse rating

                              • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                              • 100 A gG at <= 690 V coordination type 1 for power circuit
                              • 100 A gG at <= 690 V coordination type 2 for power circuit
                                • Average impedance

                                  1.5 mOhm - Ith 80 A 50 Hz for power circuit

                                  [Ui] rated insulation voltage

                                • power circuit: 690 V conforming to IEC 60947-4-1
                                • signalling circuit: 690 V conforming to IEC 60947-1
                                  • Power dissipation per pole

                                  • 9.6 W AC-1
                                  • 3.7 W AC-3
                                    • Protective cover

                                      with

                                      Tightening torque

                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                    • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                      • Operating time

                                      • 55...65 ms closing
                                      • 20...120 ms opening (date code >= 17221)
                                      • 20...80 ms opening (date code >= 18011)
                                        • Safety reliability level

                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Maximum operating rate

                                            3600 cyc/h 60 °C

                                            Coil technology

                                            built-in bidirectional peak limiting

                                            Control circuit voltage limits

                                          • <= 0.1 Uc 60-60 °C drop-out
                                            • Inrush power in VA

                                              18-18 VA 50/60 Hz (at 20 °C)

                                              Inrush power in W

                                              14-14 W at 20 °C

                                              Hold-in power consumption in VA

                                              1.8-1.8 VA (at 20 °C) 50/60 Hz

                                              Hold-in power consumption in W

                                              1.2-1.2 W at 20 °C

                                              Heat dissipation

                                              1.2-1.2 W at 50/60 Hz

                                              Auxiliary contacts type

                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency

                                                25...400 Hz

                                                Minimum switching current

                                                5 mA for signalling circuit

                                                Minimum switching voltage

                                                17 V for signalling circuit

                                                Non-overlap time

                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Compatibility code

                                                  LC1D

                                                  Protective treatment

                                                  TH conforming to IEC 60068-2-30

                                                  Pollution degree

                                                  3

                                                  Operating altitude

                                                  3000 m without derating

                                                  Fire resistance

                                                  850 °C conforming to IEC 60695-2-1

                                                  Flame retardance

                                                  V1 conforming to UL 94

                                                  Mechanical robustness

                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Unit Type of Package 1

                                                    PCE

                                                    Number of Units in Package 1

                                                    1

                                                    Package 1 Weight

                                                    1.07 kg

                                                    Package 1 Height

                                                    6.5 cm

                                                    Package 1 width

                                                    14 cm

                                                    Package 1 Length

                                                    15.5 cm

                                                    Unit Type of Package 2

                                                    S02

                                                    Number of Units in Package 2

                                                    9

                                                    Package 2 Weight

                                                    9.974 kg

                                                    Package 2 Height

                                                    15 cm

                                                    Package 2 width

                                                    30 cm

                                                    Package 2 Length

                                                    40 cm

                                                    WEEE

                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                    Halogen content performance

                                                    Halogen free plastic parts & cables product
                                                    Show all specifications

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • CAD Files and Packs

                                                    • Technical Data Catalogues

                                                    • Product Environmental

                                                    • End of Life Manual

                                                    • Installation Instruction

                                                    • Data Bulletin

                                                    • Declaration of Conformity

                                                    Frequently Asked Questions

                                                    hide show

                                                    Looking for a LC1D50A.. with a 240v coil

                                                     Part code is LC1D50AU7

                                                    What is difference between LC1D50U7 and LC1D50AU7?

                                                    Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                    LC1D50AU7 has everlink terminals.
                                                    LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                    Whereas
                                                    LC1D50U7 contactors accommodate LRD33XX overloads.

                                                     

                                                    How Can the LC1D50AU7 Contactor be mounted?

                                                    Two ways -  the LC1D50AU7 can be DIN Rail mounted and Plate mounted.

                                                    See the attached datasheet for further information.

                                                    What is the Overload for LC1D50AU7 range is 37..50 Amps?

                                                    LRD350

                                                    Do the Everlink reversing contactors come with electrical interlocking?

                                                    Issue:
                                                    Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                    Product line:
                                                    Tesys D LC1D40A, LC1D50A, LC1D65A

                                                    Environment:
                                                    Everlink, all voltage codes

                                                    Cause:
                                                    Old D2 version offered an electrical interlock kit

                                                    Resolution:
                                                    The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                    What replaces LC1D50BD

                                                    Replacement LC1D50ABD

                                                    What mechanical interlock should I use with the LC1D50A••?

                                                    The mechanical interlock LAD4CM is the correct one for use with the LC1D50A••.

                                                    See attached datasheet for futher information on the LAD4CM.

                                                    Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                    No, correct kit is a LAD9R3.

                                                    What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                    Issue:
                                                    Identifying maximum voltage of an LC1D contactor

                                                    Product Line:
                                                    TeSys D Contactors

                                                    Environment:
                                                    IEC contactors and starters used in North America

                                                    Cause:
                                                    n/a

                                                    Resolution:
                                                    IThe maximum voltage per UL and CSA is 600VAC. 
                                                     

                                                    What is the code for the newer version of the LC1D40U7

                                                    That has been replaced with the Everlink LC1D40AU7

                                                    What is the difference between a LC1D65A3U7 and LC1D65AU7?

                                                    The difference between the LC1D65A3U7 and the LC1D65AU7 is that the Control connections are spring terminals for the LC1D65A3U7 and screw clamp terminals for the LC1D65AU7
                                                    see data sheets for comparrisons...
                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65a3u7

                                                    https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=lc1d65au7
                                                    User-added image.................User-added image

                                                    What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                    Issue:
                                                    Identifying power terminal lug data for the D2 style contactors

                                                    Product Line:
                                                    Tesys D line contactors

                                                    Environment:
                                                    Products sold and used in the United States

                                                    Cause:
                                                    Power terminal lug data required

                                                    Resolution:
                                                    For contactors with screw clamp terminals:
                                                    stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                    stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                    solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.
                                                    Show More