TeSys D Contactor-3 Pole AC3 <= 440V 40A, 24V DC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 40A, 24V DC Coil

TeSys D Contactor-3 Pole AC3 <= 440V 40A, 24V DC Coil

Item Number: LC1D40ABBE

Retail
$1,763.20
RRP (Inc. GST)

Product Dimensions

Width icon

Width55 mm

Height icon

Height122 mm

Depth icon

Depth120 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

  • 60 A (at <60 °C) at <= 440 V AC-1 for power circuit
  • 40 A (at <60 °C) at <= 440 V AC-3 for power circuit
    • Electrical durability

    • 2 Mcycles 35 A AC-3 at Ue <= 440 V
    • 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
      • Mounting support

      • plate
      • rail
        • Standards

        • EN/IEC 60947-4-1
        • EN/IEC 60947-5-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • CCC
          • CSA
          • EAC
          • UL
          • KC
          • DNV-GL
          • LROS (Lloyds register of shipping)
            • Connections - terminals

            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²solid
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²solid
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible without cable end
            • power circuit: EverLink BTR screw connectors 1 cable(s) 1-35 mm²flexible with cable end
            • power circuit: EverLink BTR screw connectors 2 cable(s) 1-25 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
              • Mechanical durability

                6 Mcycles

                Insulation resistance

                > 10 MOhm for signalling circuit

                IP degree of protection

                IP20 front face conforming to IEC 60529

                Ambient air temperature for storage

                -60-80 °C

                Height

                122 mm

                Width

                55 mm

                Depth

                120 mm

                Net weight

                0.992 kg

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP1607010EN

                Circularity Profile

                ENVEOLI1607010EN

                Others

                Product name

                TeSys D Green

                Device short name

                LC1D

                Contactor application

              • motor control
              • resistive load
                • Utilisation category

                • AC-1
                • AC-3
                  • Poles description

                    3P

                    Pole contact composition

                    3 NO

                    Motor power kW

                  • 11 kW at 220...230 V AC 50 Hz (AC-3)
                  • 18.5 kW at 380...400 V AC 50 Hz (AC-3)
                  • 22 kW at 415 V AC 50 Hz (AC-3)
                  • 22 kW at 440 V AC 50 Hz (AC-3)
                  • 22 kW at 500 V AC 50 Hz (AC-3)
                  • 30 kW at 660...690 V AC 50 Hz (AC-3)
                    • Motor power hp

                    • 3 hp at 115 V AC 60 Hz for 1 phase motors
                    • 5 hp at 230/240 V AC 60 Hz for 1 phase motors
                    • 10 hp at 200/208 V AC 60 Hz for 3 phases motors
                    • 10 hp at 230/240 V AC 60 Hz for 3 phases motors
                    • 30 hp at 460/480 V AC 60 Hz for 3 phases motors
                    • 30 hp at 575/600 V AC 60 Hz for 3 phases motors
                      • Control circuit type

                        DC DC low consumption

                        [Uc] control circuit voltage

                        24 V DC

                        Coil type

                        DC low consumption

                        Auxiliary contact composition

                        1 NO + 1 NC

                        [Uimp] rated impulse withstand voltage

                        6 kV conforming to IEC 60947

                        Overvoltage category

                        III

                        [Ith] conventional free air thermal current

                      • 60 A (at 60 °C) for power circuit
                      • 10 A (at 60 °C) for signalling circuit
                        • Irms rated making capacity

                        • 800 A at 440 V for power circuit conforming to IEC 60947
                        • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                        • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                          • Rated breaking capacity

                            800 A at 440 V for power circuit conforming to IEC 60947

                            [Icw] rated short-time withstand current

                          • 72 A 40 °C - 10 min for power circuit
                          • 165 A 40 °C - 1 min for power circuit
                          • 320 A 40 °C - 10 s for power circuit
                          • 720 A 40 °C - 1 s for power circuit
                          • 100 A - 1 s for signalling circuit
                          • 120 A - 500 ms for signalling circuit
                          • 140 A - 100 ms for signalling circuit
                            • Associated fuse rating

                            • 80 A gG at <= 690 V coordination type 1 for power circuit
                            • 80 A gG at <= 690 V coordination type 2 for power circuit
                            • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                              • Average impedance

                                1.5 mOhm - Ith 60 A 50 Hz for power circuit

                                [Ui] rated insulation voltage

                              • power circuit: 690 V conforming to IEC 60947-4-1
                              • signalling circuit: 690 V conforming to IEC 60947-1
                                • Power dissipation per pole

                                • 5.4 W AC-1
                                • 2.4 W AC-3
                                  • Protective cover

                                    with

                                    Tightening torque

                                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                  • power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
                                  • power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
                                    • Operating time

                                    • 55...65 ms closing
                                    • 20...120 ms opening (date code >= 17221)
                                    • 20...80 ms opening (date code >= 18011)
                                      • Safety reliability level

                                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                        • Maximum operating rate

                                          3600 cyc/h 60 °C

                                          Coil technology

                                          built-in bidirectional peak limiting

                                          Control circuit voltage limits

                                        • <= 0.1 Uc 60-60 °C drop-out
                                          • Inrush power in W

                                            11-11 W at 20 °C

                                            Hold-in power consumption in W

                                            0.5-0.5 W at 20 °C

                                            Heat dissipation

                                            0.5-0.5 W

                                            Auxiliary contacts type

                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency

                                              25...400 Hz

                                              Minimum switching current

                                              5 mA for signalling circuit

                                              Minimum switching voltage

                                              17 V for signalling circuit

                                              Non-overlap time

                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Compatibility code

                                                LC1D

                                                Protective treatment

                                                TH conforming to IEC 60068-2-30

                                                Pollution degree

                                                3

                                                Operating altitude

                                                3000 m without derating

                                                Fire resistance

                                                850 °C conforming to IEC 60695-2-1

                                                Flame retardance

                                                V1 conforming to UL 94

                                                Mechanical robustness

                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • vibrations contactor closed: 4 Gn, 5...300 Hz
                                              • shocks contactor open: 10 Gn for 11 ms
                                              • shocks contactor closed: 15 Gn for 11 ms
                                                • Unit Type of Package 1

                                                  PCE

                                                  Number of Units in Package 1

                                                  1

                                                  Package 1 Weight

                                                  1.071 kg

                                                  Package 1 Height

                                                  6.2 cm

                                                  Package 1 width

                                                  13.6 cm

                                                  Package 1 Length

                                                  15.2 cm

                                                  Unit Type of Package 2

                                                  S02

                                                  Number of Units in Package 2

                                                  9

                                                  Package 2 Weight

                                                  10.04 kg

                                                  Package 2 Height

                                                  15 cm

                                                  Package 2 width

                                                  30 cm

                                                  Package 2 Length

                                                  40 cm

                                                  WEEE

                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                                  Halogen content performance

                                                  Halogen free plastic parts & cables product
                                                  Show all specifications

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • Product Brochures

                                                  • CAD Files and Packs

                                                  • Technical Data Catalogues

                                                  • Product Environmental

                                                  • End of Life Manual

                                                  • Installation Instruction

                                                  • Data Bulletin

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  Do the Everlink reversing contactors come with electrical interlocking?

                                                  Issue:
                                                  Looking for electrical interlock kit for the LC1D65A Everlnk contactors

                                                  Product line:
                                                  Tesys D LC1D40A, LC1D50A, LC1D65A

                                                  Environment:
                                                  Everlink, all voltage codes

                                                  Cause:
                                                  Old D2 version offered an electrical interlock kit

                                                  Resolution:
                                                  The current Everlink version does not offer an electrical interlock kit.  The customer can wire electrical interlocking using the normally closed contacts provided on the contactor.

                                                  What replaces LC1D50BD

                                                  Replacement LC1D50ABD

                                                  What are the dimensions of LC1D40AB7 ?

                                                  Height 122 mm
                                                  Width 55 mm
                                                  Depth 120 mm
                                                  Product weight 1.4 kg

                                                  What is the part number for a 3 POLE, 40A, 24V AC coil contactor?

                                                  The Part number for a 3 pole, 40A, 24V AC coil contactor is LC1D40AB7

                                                  What is the code for a 40A 110VAC contactor ?

                                                  LC1D40AF7

                                                  Can I use a LA9D6569 reversing kit with LC1D40AU7 contactors

                                                  No, correct kit is a LAD9R3.

                                                  Is there a retrofit plate available for replacement of LC1D40-D65 contactors with the LC1D40A-65A contactors?

                                                  Use a LAD7X3 retrofit plate.


                                                  CTA-ID : 2053453

                                                  What is the code for the newer version of the LC1D40U7

                                                  That has been replaced with the Everlink LC1D40AU7

                                                  What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                                                  Issue:
                                                  Identifying power terminal lug data for the D2 style contactors

                                                  Product Line:
                                                  Tesys D line contactors

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Power terminal lug data required

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                                                  stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                                                  solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                                                  Looking for a LC1D50A.. with a 240v coil

                                                   Part code is LC1D50AU7

                                                  What is the code for a spare 240V coil for a LC1D40A contact (replacement for LC1D40AU7)?

                                                  The code for a spare coil is LXD3U7
                                                   

                                                  What is difference between LC1D50U7 and LC1D50AU7?

                                                  Following are the differences between the LC1D50U7 and the LC1D50AU7:

                                                  LC1D50AU7 has everlink terminals.
                                                  LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                                                  Whereas
                                                  LC1D50U7 contactors accommodate LRD33XX overloads.

                                                   
                                                  Show More