TeSys D Contactor, 4P(2 NO + 2 NC), AC-1, <= 440V, 60A, 42VAC, 50 Hz Coil

TeSys D Contactor, 4P(2 NO + 2 NC), AC-1, <= 440V, 60A, 42VAC, 50 Hz Coil

TeSys D Contactor, 4P(2 NO + 2 NC), AC-1, <= 440V, 60A, 42VAC, 50 Hz Coil

Item Number: LC1D40008D5

Retail
$1,700.68
RRP (Inc. GST)

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth125 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
    • [Ie] rated operational current

      60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

      Electrical durability

      1.4 Mcycles 60 A AC-1 at Ue <= 440 V

      Mounting support

    • rail
    • plate
      • Standards

      • CSA C22.2 No 14
      • EN 60947-4-1
      • EN 60947-5-1
      • IEC 60947-4-1
      • IEC 60947-5-1
      • UL 508
        • Product certifications

        • RINA
        • LROS (Lloyds register of shipping)
        • DNV
        • BV
        • GL
        • UL
        • GOST
        • CCC
        • CSA
          • Connections - terminals

          • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
          • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
          • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
          • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²flexible without cable end
          • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²flexible without cable end
          • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²flexible with cable end
          • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²flexible with cable end
          • power circuit: screw clamp terminals 1 cable(s) 1-35 mm²solid without cable end
          • power circuit: screw clamp terminals 2 cable(s) 1-25 mm²solid without cable end
            • Mechanical durability

              6 Mcycles

              IP degree of protection

              IP20 front face conforming to IEC 60529

              Ambient air temperature for storage

              -60-80 °C

              Height

              127 mm

              Width

              85 mm

              Depth

              125 mm

              Net weight

              1.44 kg

              REACh free of SVHC

              Yes

              EU RoHS Directive

              Compliant

              Toxic heavy metal free

              Yes

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

               Pro-active China RoHS declaration (out of China RoHS legal scope)

              Environmental Disclosure

              ENVPEP1503009EN

              Circularity Profile

              ENVEOLI1503009EN

              Others

              Product name

              TeSys D

              Device short name

              LC1D

              Contactor application

              resistive load

              Utilisation category

              AC-1

              Poles description

              4P

              Pole contact composition

              2 NO + 2 NC

              Control circuit type

              AC at 50 Hz

              [Uc] control circuit voltage

              42 V AC 50 Hz

              [Uimp] rated impulse withstand voltage

              6 kV conforming to IEC 60947

              Overvoltage category

              III

              [Ith] conventional free air thermal current

              60 A (at 60 °C) for power circuit

              Irms rated making capacity

              800 A at 440 V for power circuit conforming to IEC 60947

              Rated breaking capacity

              800 A at 440 V for power circuit conforming to IEC 60947

              [Icw] rated short-time withstand current

            • 320 A 40 °C - 10 s for power circuit
            • 720 A 40 °C - 1 s for power circuit
            • 72 A 40 °C - 10 min for power circuit
            • 165 A 40 °C - 1 min for power circuit
              • Associated fuse rating

              • 80 A gG at <= 690 V coordination type 1 for power circuit
              • 80 A gG at <= 690 V coordination type 2 for power circuit
                • Average impedance

                  1.5 mOhm - Ith 60 A 50 Hz for power circuit

                  [Ui] rated insulation voltage

                • power circuit: 600 V CSA certified
                • power circuit: 600 V UL certified
                • power circuit: 690 V conforming to IEC 60947-4-1
                  • Power dissipation per pole

                    5.4 W AC-1

                    Protective cover

                    without

                    Tightening torque

                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                  • power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
                  • power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
                    • Operating time

                    • 4...19 ms opening
                    • 12...26 ms closing
                      • Safety reliability level

                      • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                      • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                        • Maximum operating rate

                          3600 cyc/h 60 °C

                          Coil technology

                          without built-in suppressor module

                          Inrush power in VA

                          160-160 VA 50 Hz cos phi 0.75 (at 20 °C)

                          Hold-in power consumption in VA

                          15-15 VA 50 Hz cos phi 0.3 (at 20 °C)

                          Heat dissipation

                          4-5 W at 50 Hz

                          Contact compatibility

                          M1

                          Compatibility code

                          LC1D

                          Protective treatment

                          TH conforming to IEC 60068-2-30

                          Pollution degree

                          3

                          Operating altitude

                          3000 m without derating

                          Fire resistance

                          850 °C conforming to IEC 60695-2-1

                          Flame retardance

                          V1 conforming to UL 94

                          Mechanical robustness

                        • vibrations contactor open: 2 Gn, 5...300 Hz
                        • vibrations contactor closed: 4 Gn, 5...300 Hz
                        • shocks contactor closed: 15 Gn for 11 ms
                        • shocks contactor open: 10 Gn for 11 ms
                          • Unit Type of Package 1

                            PCE

                            Number of Units in Package 1

                            1

                            Package 1 Weight

                            1.5 kg

                            Package 1 Height

                            9.1 cm

                            Package 1 width

                            12.6 cm

                            Package 1 Length

                            13.2 cm

                            WEEE

                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                            Show all specifications

                            Documents & downloads

                            hide show
                            Filter items
                            • All

                            • Product Brochures

                            • Technical Data Catalogues

                            • Product Environmental

                            • End of Life Manual

                            • Certificates (MSDS)

                            • Declaration of Conformity

                            Frequently Asked Questions

                            hide show

                            What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                            Issue:
                            Identifying power terminal lug data for the D2 style contactors

                            Product Line:
                            Tesys D line contactors

                            Environment:
                            Products sold and used in the United States

                            Cause:
                            Power terminal lug data required

                            Resolution:
                            For contactors with screw clamp terminals:
                            stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                            stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                            solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                            What is the color scheme of the Tesys D-Line contactors?

                            Issue:
                            Looking for different color scheme of the Tesys D-Line contactors.

                            Product Line:
                            Tesys D Contactors

                            Environment:
                            LC1D contactors

                            Resolution:
                            Beige and dark gray.
                             

                            What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                            Issue:
                            Identifying maximum voltage of an LC1D contactor

                            Product Line:
                            TeSys D Contactors

                            Environment:
                            IEC contactors and starters used in North America

                            Cause:
                            n/a

                            Resolution:
                            IThe maximum voltage per UL and CSA is 600VAC. 
                             

                            Are the D-Line contactors rated to break DC voltages?

                            Issue: 
                            Can the TeSys D line be used to control DC loads? 

                            Product Line:
                            Tesys D contactors

                            Environment:
                            Products sold and used in the United States
                             
                            Cause:
                             DC power circuit
                             
                            Resolution:
                             
                            Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                            Devices are suitable but not UL Listed for DC applications.

                            More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                             

                            What are the stand alone short circuit current ratings on the LC1D** contactors?

                            Issue:
                            Tesys D SCCR

                            Product Line:
                            Contactors and Overload Relays

                            Environment:
                            TeSys™ D Contactors and Overload Relays
                             
                            Resolution:
                            The contactors have a stand alone withstand rating that has been established by UL and is based on the maximum horsepower rating for a given device. However, only combination type starters are supplied with short circuit protective devices having a short circuit current rating.

                            They are as follows:
                            Horsepower SCCR (A)

                            0 thru 1 1,000
                            1 thru 50 5,000
                            51 thru 200 10,000
                            201 thru 400 18,000
                            401 thru 600 30,000
                            601 thru 900 42,000
                            901 thru 1600 85,000
                            1601+ 100,000

                            Video: What auxiliary contact modules are available for the LC1D and LC2D contactors?

                            Issue:
                            Auxiliary contact modules for the LC1D and LC2D contactors

                            Product Line: 
                            Contactor and Starters - IEC

                            Environment:
                            North American Products

                            Resolution:
                            Select based on application requirements. Please note that the TeSys and Pre-TeSys auxiliary blocks are backward/forward compatible.
                            Front Mounting; maximum of 1 block per contactor:

                            N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                            --1-----------1---------LADN11-----------LA1DN11
                            --1-----------1---------LADN11G---------LA1DN11G (See Footnote 1)
                            --1-----------1---------LADN11P---------LA1DN11P (See Footnote 1)
                            --2-----------0---------LADN20-----------LA1DN20
                            --2-----------0---------LA1DX20---------LA1DX20 (See Footnote 2)
                            --2-----------0---------LA1DY20---------LA1DY20 (See Footnote 3)
                            --0-----------2---------LADN02-----------LA1DN02
                            --2-----------2---------LADN22-----------LA1DN22
                            --2-----------2---------LADN22G---------LA1DN22G (See Footnote 1)
                            --2-----------2---------LADN22P---------LA1DN22P (See Footnote 1)
                            --2-----------2---------LADC22------------LA1DC22 (See Footnote 4)
                            --3-----------1---------LADN31------------LA1DN31
                            --3-----------1---------LA1DZ31----------LA1DZ31 (See Footnote 5)
                            --1-----------3---------LADN13------------LA1DN13
                            --4-----------0---------LADN40------------LA1DN40
                            --4-----------0---------LA1DZ40-----------LA1DZ40 (See Footnote 6)
                            --0-----------4---------LADN04------------LA1DN04




                            Front Mounting; maximum of 1 block per contactor: For use with D2 Series 25 amp through 80 amp contactors and TeSys Series 40 amp through 80 amp only.

                            N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                            --1-----------0--------LADN10----------LA1DN10
                            --0-----------1--------LADN01----------LA1DN01

                            Side Mounting; maximum of 1 block on each side for D2 Series and Tesys Series 40 through 80 amp contactors. Tesys 9 through 32, 115, and 150 amps contactors will accept 1 block and is limited to left side only. (*) DC control devices will not accept side mount auxiliaries.
                            (*) DC control exceptions that will accept one left side mounted auxiliary: LC1D115 & LC1D150.

                            N.O.-------N.C.-----TeSys P/N--------Pre-TeSys P/N
                            --1-----------1--------LAD8N11----------LA8DN11
                            --2-----------0--------LAD8N20----------LA8DN20
                            --0-----------2--------LAD8N02----------N/A

                            Footnotes:
                            {1} EN50 012 Machine Tool Terminal Markings
                            {2} (2) NO Sealed Dust Tight Contacts
                            {3} Gold Flash Contacts
                            {4} (1) NO & (1) NC Standard and (1) NO & (1) NC Make Before Break
                            {5} (2) NO Dust Tight Contacts & (1) NO & (1) NC Standard Contacts
                            {6} (2) NO Dust Tight Contacts & (2) NO Standard Contacts

                            What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

                            Issue:
                            AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

                            Product Line:
                            Tesys D Replacement Parts

                            Environment:
                            TeSys™ D AC Coils

                            Resolution:

                            What is the replacement for LC1D40004N5 Contactor?

                            What is the part cod for a contactor 4P 2N/C 2N/O 48Vac coil

                             The part code is LC1D40008E7

                            Will the LAD** time delay auxiliary contact module fit the D2 series pre-Tesys contactors?

                            Issue:
                            Can new accessories be used on older style contactors

                            Product Line:
                            IEC contactors and starters

                            Environment:
                            Products sold and used in the United States

                            Cause:
                            Identifying product compatibility

                            Resolution:
                            Yes, all front mount D2 and Tesys series auxiliary modules are backward forward compatible.


                             

                            What is the 240V coil needed for a LC1D80008 contactor

                             The coil is a LX1D6U7

                            Is there a retrofit plate available for replacement of LC1D40-D65 contactors with the LC1D40A-65A contactors?

                            Use a LAD7X3 retrofit plate.


                            CTA-ID : 2053453