LC1D18KUE

Catalogue Number: LC1D18KUE

TeSys D Contactor-3 Pole AC3 <= 440V 18A,100 - 250V ACDC Coil

LC1D18KUE
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • Up to 80% less energy consumption compared to traditional electro mechanical contactor
  • Noise free design
  • Green Premium ecoLabel
  • Direct PLC control for contactors from 40 to 65A
  • High uptime thanks to wide band coil with high resistance to voltage fluctuation
Range of product
TeSys D
Range
TeSys
Product name
TeSys D Green
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-1
    • AC-3
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
        power circuit: <= 690 V AC 25...400 Hz
        [Ie] rated operational current
      • 18 A (at <60 °C) at <= 440 V AC-3 for power circuit
      • 32 A (at <60 °C) at <= 440 V AC-1 for power circuit
        • Motor power kW
        • 4 kW at 220...230 V AC 50 Hz (AC-3)
        • 7.5 kW at 380...400 V AC 50 Hz (AC-3)
        • 9 kW at 415 V AC 50 Hz (AC-3)
        • 9 kW at 440 V AC 50 Hz (AC-3)
        • 10 kW at 500 V AC 50 Hz (AC-3)
        • 10 kW at 660...690 V AC 50 Hz (AC-3)
          • Motor power hp
          • 1 hp at 115 V AC 60 Hz for 1 phase motors
          • 3 hp at 230/240 V AC 60 Hz for 1 phase motors
          • 5 hp at 200/208 V AC 60 Hz for 3 phases motors
          • 5 hp at 230/240 V AC 60 Hz for 3 phases motors
          • 10 hp at 460/480 V AC 60 Hz for 3 phases motors
          • 15 hp at 575/600 V AC 60 Hz for 3 phases motors
            • Control circuit type
              AC/DC at 50/60 Hz AC/DC electronic
              [Uc] control circuit voltage
            • 100...250 V AC 50/60 Hz
            • 100...250 V DC
              • Coil type
                AC/DC electronic
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 32 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 300 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    300 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                  • 40 A 40 °C - 10 min for power circuit
                  • 84 A 40 °C - 1 min for power circuit
                  • 145 A 40 °C - 10 s for power circuit
                  • 240 A 40 °C - 1 s for power circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 50 A gG at <= 690 V coordination type 1 for power circuit
                    • 35 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2.5 mOhm - Ith 32 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • signalling circuit: 690 V conforming to IEC 60947-1
                        • Electrical durability
                        • 2.2 Mcycles 15 A AC-3 at Ue <= 440 V
                        • 0.9 Mcycles 32 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 2.5 W AC-1
                          • 0.8 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • EN/IEC 60947-4-1
                              • EN/IEC 60947-5-1
                              • UL 60947-4-1
                              • CSA C22.2 No 60947-4-1
                                • Product certifications
                                • CCC
                                • CSA
                                • EAC
                                • UL
                                • KC
                                • DNV-GL
                                • LROS (Lloyds register of shipping)
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid
                                    • Tightening torque
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time
                                      • 45...55 ms closing
                                      • 20...90 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            15 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting
                                            Control circuit voltage limits
                                          • <= 0.1 Uc 60-60 °C drop-out
                                          • 0.85...1.1 Uc 60-60 °C operational
                                            • Inrush power in VA
                                              25-25 VA 50/60 Hz (at 20 °C)
                                              Inrush power in W
                                              18-18 W at 20 °C
                                              Hold-in power consumption in VA
                                              1.6-1.6 VA (at 20 °C) 50/60 Hz
                                              Hold-in power consumption in W
                                              1.1-1.1 W at 20 °C
                                              Heat dissipation
                                              1.1-1.1 W at 50/60 Hz
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Compatibility code
                                                  LC1D
                                                  IP degree of protection
                                                  IP20 front face conforming to IEC 60529
                                                  Protective treatment
                                                  TH conforming to IEC 60068-2-30
                                                  Pollution degree
                                                  3
                                                  Ambient air temperature for operation
                                                  -25-60 °C
                                                  Ambient air temperature for storage
                                                  -60-80 °C
                                                  Permissible ambient air temperature around the device
                                                  -40-70 °C at Uc
                                                  Operating altitude
                                                  3000 m without
                                                  Fire resistance
                                                  850 °C conforming to IEC 60695-2-1
                                                  Flame retardance
                                                  V1 conforming to UL 94
                                                  Mechanical robustness
                                                • vibrations contactor open: 2 Gn, 5...300 Hz
                                                • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                • shocks contactor open: 10 Gn for 11 ms
                                                • shocks contactor closed: 15 Gn for 11 ms
                                                  • Height
                                                    77 mm
                                                    Width
                                                    45 mm
                                                    Depth
                                                    86 mm
                                                    Net weight
                                                    0.378 kg
                                                    Sustainable offer status
                                                    Green Premium product
                                                    REACh Regulation
                                                    Reference contains Substances of Very High Concern above the threshold
                                                    EU RoHS Directive
                                                    Compliant
                                                    Mercury free
                                                    Yes
                                                    RoHS exemption information
                                                    Yes
                                                    China RoHS Regulation
                                                    Product out of China RoHS scope. Substance declaration for your information
                                                    Environmental Disclosure
                                                    ENVPEP1609001EN
                                                    Circularity Profile
                                                    ENVEOLI1609001EN
                                                    WEEE
                                                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                    Warranty
                                                    18 months

                                                    Documents & downloads

                                                    hide show
                                                    Filter items
                                                    • All

                                                    • Product Brochures

                                                    • CAD Files and Packs

                                                    • Movies

                                                    • Catalog Page

                                                    • Technical Data Catalogues

                                                    • Technical Leaflet

                                                    • End of Life Manual

                                                    • Handout

                                                    • Product Environmental

                                                    • Data Bulletin

                                                    • Installation Instruction

                                                    • Operating Manuals

                                                    • Application Solutions

                                                    • Certificates (MSDS)

                                                    • Declaration of Conformity

                                                    • White Paper

                                                    • eTechPub

                                                    • Marine Certificate

                                                    • Software - Released