Product or component type
contactor
Contactor application
resistive loadmotor control
Pole contact composition
3 NO
[Ue] rated operational voltage
power circuit: <= 690 V AC 25...400 Hzpower circuit: <= 300 V DC
[Ie] rated operational current
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW
4 kW at 220...230 V AC 50/60 Hz (AC-3)7.5 kW at 380...400 V AC 50/60 Hz (AC-3)9 kW at 415...440 V AC 50/60 Hz (AC-3)10 kW at 500 V AC 50/60 Hz (AC-3)10 kW at 660...690 V AC 50/60 Hz (AC-3)4 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp
1 hp at 115 V AC 50/60 Hz for 1 phase motors3 hp at 230/240 V AC 50/60 Hz for 1 phase motors5 hp at 200/208 V AC 50/60 Hz for 3 phases motors5 hp at 230/240 V AC 50/60 Hz for 3 phases motors10 hp at 460/480 V AC 50/60 Hz for 3 phases motors15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Control circuit type
DC low consumption
[Uc] control circuit voltage
12 V DC
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit32 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1300 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
300 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
145 A 40 °C - 10 s for power circuit240 A 40 °C - 1 s for power circuit40 A 40 °C - 10 min for power circuit84 A 40 °C - 1 min for power circuit100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-150 A gG at <= 690 V coordination type 1 for power circuit35 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
2.5 mOhm - Ith 32 A 50 Hz for power circuit
[Ui] rated insulation voltage
power circuit: 690 V conforming to IEC 60947-4-1power circuit: 600 V CSA certifiedpower circuit: 600 V UL certifiedsignalling circuit: 690 V conforming to IEC 60947-1signalling circuit: 600 V CSA certifiedsignalling circuit: 600 V UL certified
Electrical durability
1.65 Mcycles 18 A AC-3 at Ue <= 440 V1 Mcycles 32 A AC-1 at Ue <= 440 V
Power dissipation per pole
Standards
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product certifications
BVCSACCCGOSTGLULDNVRINALROS (Lloyds register of shipping)
Connections - terminals
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable endcontrol circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable endcontrol circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable endcontrol circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable endcontrol circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable endcontrol circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable endpower circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable endpower circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable endpower circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable endpower circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable endpower circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid without cable endpower circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid without cable end
Tightening torque
power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmpower circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mmcontrol circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Operating time
65.45...88.55 ms closing20...30 ms opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
30 Mcycles
Maximum operating rate
3600 cyc/h 60 °C
Coil technology
built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
drop-out: 0.1...0.3 Uc DC (at 60 °C)operational: 0.8...1.25 Uc DC (at 60 °C)
Inrush power in W
2.4-2.4 W (at 20 °C)
Hold-in power consumption in W
2.4-2.4 W at 20 °C
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact1.5 ms on energisation between NC and NO contact
Insulation resistance
> 10 MOhm for signalling circuit
IP degree of protection
IP20 front face conforming to IEC 60529
Protective treatment
TH conforming to IEC 60068-2-30
Ambient air temperature for operation
-5-60 °C
Ambient air temperature for storage
-60-80 °C
Permissible ambient air temperature around the device
-40-70 °C at Uc
Operating altitude
3000 m without
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
vibrations contactor open: 2 Gn, 5...300 Hzvibrations contactor closed: 4 Gn, 5...300 Hzshocks contactor open: 10 Gn for 11 msshocks contactor closed: 15 Gn for 11 ms
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
Toxic heavy metal free
Yes
RoHS exemption information
Yes
Environmental Disclosure
ENVPEP1501004EN
Circularity Profile
ENVEOLI1501004EN
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov