TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector
TeSys LC1D contactor 3P
TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector
TeSys LC1D contactor 3P

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 18A, 24VDC Coil

Catalogue Number: LC1D18BL
TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector
TeSys LC1D contactor 3P
TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector
TeSys LC1D contactor 3P
Retail
$525.14*
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • motor control
  • resistive load
    • Utilisation category
    • AC-1
    • AC-3
    • AC-4
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
          • Motor power kW
          • 4 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 9 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 10 kW at 500 V AC 50/60 Hz (AC-3)
          • 10 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 4 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 1 hp at 115 V AC 50/60 Hz for 1 phase motors
            • 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
              • Control circuit type
                DC low consumption
                [Uc] control circuit voltage
                24 V DC
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 10 A (at 60 °C) for signalling circuit
              • 32 A (at 60 °C) for power circuit
                • Irms rated making capacity
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                • 300 A at 440 V for power circuit conforming to IEC 60947
                  • Rated breaking capacity
                    300 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 145 A 40 °C - 10 s for power circuit
                  • 240 A 40 °C - 1 s for power circuit
                  • 40 A 40 °C - 10 min for power circuit
                  • 84 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 50 A gG at <= 690 V coordination type 1 for power circuit
                    • 35 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2.5 mOhm - Ith 32 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
                        • 1 Mcycles 32 A AC-1 at Ue <= 440 V
                          • Power dissipation per pole
                          • 2.5 W AC-1
                          • 0.8 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • BV
                                • GOST
                                • CCC
                                • DNV
                                • LROS (Lloyds register of shipping)
                                • UL
                                • GL
                                • CSA
                                • RINA
                                  • Connections - terminals
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²solid without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1.5-6 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-6 mm²flexible with cable end
                                    • Tightening torque
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time
                                      • 65.45...88.55 ms closing
                                      • 20...30 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            30 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting diode suppressor
                                            Control circuit voltage limits
                                          • drop-out: 0.1...0.3 Uc DC (at 60 °C)
                                          • operational: 0.8...1.25 Uc DC (at 60 °C)
                                            • Time constant
                                              40 ms
                                              Inrush power in W
                                              2.4-2.4 W (at 20 °C)
                                              Hold-in power consumption in W
                                              2.4-2.4 W at 20 °C
                                              Auxiliary contacts type
                                            • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                            • type mirror contact 1 NC conforming to IEC 60947-4-1
                                              • Signalling circuit frequency
                                                25...400 Hz
                                                Minimum switching current
                                                5 mA for signalling circuit
                                                Minimum switching voltage
                                                17 V for signalling circuit
                                                Non-overlap time
                                              • 1.5 ms on de-energisation between NC and NO contact
                                              • 1.5 ms on energisation between NC and NO contact
                                                • Insulation resistance
                                                  > 10 MOhm for signalling circuit
                                                  Contact compatibility
                                                  M5
                                                  Compatibility code
                                                  LC1D
                                                  Power range
                                                • 4-6 kW at 200-240 V 3 phases
                                                • 7-11 kW at 380-440 V 3 phases
                                                • 7-11 kW at 480-500 V 3 phases
                                                  • Motor starter type
                                                    direct on-line contactor
                                                    Contactor coil voltage
                                                    24 V DC low consumption
                                                    IP degree of protection
                                                    IP20 front face conforming to IEC 60529
                                                    Protective treatment
                                                    TH conforming to IEC 60068-2-30
                                                    Pollution degree
                                                    3
                                                    Ambient air temperature for operation
                                                    -5-60 °C
                                                    Ambient air temperature for storage
                                                    -60-80 °C
                                                    Permissible ambient air temperature around the device
                                                    -40-70 °C at Uc
                                                    Operating altitude
                                                    3000 m without
                                                    Fire resistance
                                                    850 °C conforming to IEC 60695-2-1
                                                    Flame retardance
                                                    V1 conforming to UL 94
                                                    Mechanical robustness
                                                  • vibrations contactor open: 2 Gn, 5...300 Hz
                                                  • vibrations contactor closed: 4 Gn, 5...300 Hz
                                                  • shocks contactor open: 10 Gn for 11 ms
                                                  • shocks contactor closed: 15 Gn for 11 ms
                                                    • Height
                                                      77 mm
                                                      Width
                                                      45 mm
                                                      Depth
                                                      95 mm
                                                      Net weight
                                                      0.49 kg
                                                      Sustainable offer status
                                                      Green Premium product
                                                      REACh Regulation
                                                      Free of Substances of Very High Concern above the threshold
                                                      REACh free of SVHC
                                                      Yes
                                                      EU RoHS Directive
                                                      Compliant
                                                      Mercury free
                                                      Yes
                                                      RoHS exemption information
                                                      Yes
                                                      China RoHS Regulation
                                                      Product out of China RoHS scope. Substance declaration for your information
                                                      Environmental Disclosure
                                                      ENVPEP1501004EN
                                                      Circularity Profile
                                                      ENVEOLI1501004EN
                                                      WEEE
                                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                      California proposition 65
                                                      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                      Warranty
                                                      18 months

                                                      Documents & downloads

                                                      hide show
                                                      Filter items
                                                      • All

                                                      • CAD Files and Packs

                                                      • Product Brochures

                                                      • Technical Data Catalogues

                                                      • Handout

                                                      • End of Life Manual

                                                      • Product Environmental

                                                      • Installation Instruction

                                                      • Data Bulletin

                                                      • Certificates (MSDS)

                                                      • eTechPub

                                                      • Declaration of Conformity

                                                      Frequently Asked Questions

                                                      hide show

                                                      Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                      Issue:
                                                      Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                      Product Line: 
                                                      Tesys D Contactors

                                                      Environment:
                                                      IEC contactors

                                                      Resolution:
                                                      The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                       

                                                      What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                      Issue:
                                                      Identifying maximum voltage of an LC1D contactor

                                                      Product Line:
                                                      TeSys D Contactors

                                                      Environment:
                                                      IEC contactors and starters used in North America

                                                      Cause:
                                                      n/a

                                                      Resolution:
                                                      IThe maximum voltage per UL and CSA is 600VAC. 
                                                       

                                                      What is the altitude derating for a TeSys D-Line contactor?

                                                      Issue:​
                                                      What is the altitude derating for a TeSys D-Line contactor?

                                                      Product Line:
                                                      Digest 177 Section 18 : Contactors and Starters, IEC

                                                      Environment:
                                                      North American Products

                                                      Resolution:
                                                      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                      Voltage
                                                      3500m x 0.90
                                                      4000m x 0.80
                                                      4500m x 0.70
                                                      5000m x 0.60

                                                      Current
                                                      3500m x 0.92
                                                      4000m x 0.90
                                                      4500m x 0.88
                                                      5000m x 0.86

                                                      For example, an LC1D80 at 5000 meters:
                                                      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                       

                                                      Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                      Issue:
                                                      Mounting adaptor for GV2 and LC1D contactor

                                                      Product Line:
                                                      Motor Starters and Protectors

                                                      Environment:
                                                      TeSys GV Manual Starter and Protectors
                                                      Tesys D Contactors
                                                       
                                                      Resolution:
                                                      The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                      What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                      Issue:
                                                      Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                      Product Line:
                                                      IEC Contactors and Starters

                                                      Environment:
                                                      Products sold and used in the United States

                                                      Cause:
                                                      Replacement coil is needed

                                                      Resolution:
                                                      DC replacement coils are not available.
                                                      AC Coils are 50/60 hertz for voltages as listed below:

                                                      Volts - Part Number
                                                      12 ____ LXD1J7
                                                      21 ____ LXD1Z7
                                                      24 ____ LXD1B7
                                                      32 ____ LXD1C7
                                                      36 ____ LXD1CC7
                                                      42 ____ LXD1D7
                                                      48 ____ LXD1E7
                                                      60 ____ LXD1EE7
                                                      100 ___ LXD1K7 ( never brought to North America )
                                                      110 ___ LXD1F7
                                                      115 ___ LXD1FE7
                                                      120 ___ LXD1G7
                                                      127 ___ LXD1FC7
                                                      200 ___ LXD1L7
                                                      208 ___ LXD1LE7
                                                      220 ___ LXD1M7
                                                      230 ___ LXD1P7
                                                      240 ___ LXD1U7
                                                      277 ___ LXD1W7
                                                      380 ___ LXD1Q7
                                                      400 ___ LXD1V7
                                                      415 ___ LXD1N7
                                                      440 ___ LXD1R7
                                                      480 ___ LXD1T7
                                                      575 ___ LXD1SC7
                                                      600 ___ LXD1X7
                                                      690 ___ LXD1Y7


                                                      Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                      What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                      Issue:
                                                      Identifying the difference between LAD4TB and LAD4TBDL

                                                      Product Line:
                                                      IEC contactors and starters

                                                      Environment:
                                                      Products sold and used in the United States

                                                      Cause:
                                                      Identifying the difference between two similar part numbers

                                                      Resolution:
                                                      The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                       

                                                      What replaces a LC1D18M7

                                                      Use the LC1D18U7

                                                      Are the D-Line contactors rated to break DC voltages?

                                                      Issue: 
                                                      Can the TeSys D line be used to control DC loads? 

                                                      Product Line:
                                                      Tesys D contactors

                                                      Environment:
                                                      Products sold and used in the United States
                                                       
                                                      Cause:
                                                       DC power circuit
                                                       
                                                      Resolution:
                                                       
                                                      Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                      Devices are suitable but not UL Listed for DC applications.

                                                      More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                       

                                                      What is the coil burden for the standard DC control coil for the LC*D09__ through LC*D38__ TeSys contactors?

                                                      Issue:
                                                      LC*D09-38 coil consumption

                                                      Product Line:
                                                      Contactors and Overload Relays

                                                      Environment:
                                                      TeSys™ D Contactors and Overload Relays

                                                      Resolution:
                                                      The standard DC coil is 5.4 watts of consumption.

                                                      What are the dimensional differences in the LC1D1810 and the LC1D18?

                                                      Issue:
                                                      What are the dimensional differences in the LC1D1810 and the LC1D18?

                                                      Product Line:
                                                      TeSys D Line Contactors

                                                      Environment:
                                                      All Product Lines

                                                      Cause:
                                                      Can not find the dimensions for obsoleted LC1D1810

                                                      Resolution:
                                                      Please see attached PDF for dimensions of the LC1D1810 and the LC1D18.

                                                      What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                      Issue:
                                                      Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                      Product Line:
                                                      NEMA combination starters

                                                      Environment:
                                                      Products sold and used in the United States

                                                      Resolution:
                                                      For contactors with screw clamp terminals:
                                                      stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                      stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                      solid cable: One or Two #18-8 AWG per terminal.

                                                      What is the replacement for a LP1D1210BD

                                                      You can use a LC1D12BD or for low consumption a LC1D12BL.
                                                      Show More